Argo MAGICO 9.2 AMG26MIR Скачать руководство пользователя страница 1

TECHNICAL DATA & SERVICE MANUAL

MAGICO 9.2

AMG26MIR

0.8180.469.0     07/2005

Содержание MAGICO 9.2 AMG26MIR

Страница 1: ...TECHNICAL DATA SERVICE MANUAL MAGICO 9 2 AMG26MIR 0 8180 469 0 07 2005...

Страница 2: ...4 Protection operations in cool and dry modes 11 5 5 Sleep function 12 5 6 Daily timer function 12 5 7 I Feel function 12 5 8 Manual unit control and led indicators 13 5 9 Recovery from power failure...

Страница 3: ...h mm Package dimensions Height mm Width mm Depth mm Volume m Weight Net kg Shipping kg Data subject to change without notice Rating conditions 1 Cooling indoor air temperature 27 C d b 19 C w b 2 Cool...

Страница 4: ...aust tube retracted Power input 230 V W Hi Lo 109 84 80 GRY WHT 87 3 101 WHT VLT 36 2 41 6 VLT YEL 22 8 26 3 YEL PNK 22 8 26 3 GRY BRN 51 9 59 6 type Thermostat open C 150 10 close C Automatic C1 F 3...

Страница 5: ...220 V Coil supply VAC 230 Coil resistance 20 C k 17 2 10 Heat exchanger coil EVAPORATOR COIL Coils Aluminium fin 3 8 Copper tube Rows 4 Fin pitch mm Face area m 0 042 Heat exchanger coil CONDENSER COI...

Страница 6: ...2 DIMENSIONAL DATA 2 1 Unit Dimensions 6...

Страница 7: ...OTECTOR OLRx BLUE BLU ELECTRONIC CONTROL PCB BROWN BRN ALARM LIGHT AL GREEN YELLOW GRN YEL CONDENSATE PUMP PC ORANGE ORG PUMP RELAY RP RED RED ON OFF SWITCH SW WHITE WHT FLOAT MICROSWITCH MS YELLOW YE...

Страница 8: ...4 REFRIGERANT FLOW DATA 4 1 Refrigerant flow diagram 8...

Страница 9: ...ph the FAN is operating in the auto fan speed setting If the user has selected the low medium or high fan speed the FAN will run constantly at that speed only 2 In addition to the value of RT SPT the...

Страница 10: ...RT SPT the unit will operate in dry off state The COMP is forced to operate for 6 min after it has stopped working for 15 min If RT SPT the unit will operate in dry on state The COMP is forced off for...

Страница 11: ...des 1 Evaporate coil defrost protection The evaporate coil defrost protection can prevent the ice formation at the coil when the ambient temperature is low t1 5 min minimum for COMP starting t2 20 min...

Страница 12: ...rammed to be ON and OFF automatically at preset time everyday by using a remote controller The resolutions of the ON OFF timers are 10 min 5 7 I Feel Function This feature is provided if the unit is u...

Страница 13: ...hts up during Timer and Sleep operation 2 Active on off timer setting will become invalid after a power failure When this happens the unit is forced to restart in STBY mode and the timer indicator ind...

Страница 14: ...RFORMANCE DATA 6 1 Performance Chart 4 9 32 Operating characteristics with relative humidity around 50 2 50 3 00 3 50 4 00 4 50 5 00 18 20 22 24 26 28 30 32 34 36 Room temperature C Operating current...

Страница 15: ...e rating Check that power is being supplied 7 1 Air conditioner does not operate Circuit breaker trips or fuse blows When circuit breaker is set to ON it trips in a few moments resetting is not possib...

Страница 16: ...parts of air conditioner does not operate Only fan does not run Only compressor motor does not run 7 3 Air conditioner operate but abnormalities are observed Check remote control unit Check fuse on PC...

Страница 17: ...If a sensor is defective TH1 coil sensor TH2 room ambient teperature are defective NOTE Alarm signal Standby lamp on front side of the unit will blink when the thermistor is defective At the same tim...

Страница 18: ...for electrical parts Disconnect the lead wires of the desired electrical part from terminal plate PCB assy capacitor etc Similarly disconnect the connector then measure the insulation resistance fig 1...

Страница 19: ...Via Varese 90 21013 Gallarate Va Italy Tel 39 0331 755111 Fax 39 0331 776240 www argoclima it...