CAUTION
CAUTION
WARNING
1. This unit requires no additional refrig-
erant charge up to tubing length 30 m.
In case of more than 30 m, additional
refrigerant charge is required. Refer to
Tables 1-2 and 1-3.
2. In case of multi type installation,
indoor units should be installed within
the same room. If multi type indoor
units are installed in different rooms,
temperature control may develop prob-
lems because thermostat operation
must follow the thermostat condition
of 1 indoor unit only (the main unit).
Always check the gas density
for the room in which the unit is
installed.
Pay special attention to any
location, such as a basement
or recessed area, etc. where
leaked refrigerant can collect,
since refrigerant gas is heav-
ier than air.
10
13.5
27.0
40.5
54.0
67.5
81.0
94.5
108
121.5
135
5
10
15
20
25
30
35
40
45
50
m
3
m
2
Total amount of refrigerant
Min. indoor floor area
(when the ceiling is 2.7 m high)
Min. indoor volume
20
30
40 kg
Range below the
density limit of
0.3 kg/m
3
(Countermeasures
not needed)
Range above the
density limit of
0.3 kg/m
3
(Countermeasures
needed)
■
Check of limit density
When installing an air conditioner in a room, it is neces-
sary to ensure that even if the refrigerant gas acciden-
tally escapes, its density does not exceed the limit level.
If the density might exceed the limit level, it is neces-
sary to set up an opening between it and the adjacent
room, or to install mechanical ventilation which is inter-
locked with a leak detector.
(Total refrigerant charged amount: kg)
(Min. indoor volume where the indoor unit is installed: m
3
)
≤
Limit density 0.3 (kg/m
3
)
The limit density of refrigerant which is used in this unit
is 0.3 kg/m
3
(ISO 5149).
The shipped outdoor unit comes charged with the
amount of refrigerant fixed for each type, so add it to
the amount that is charged at the field. (For the refriger-
ant charge amount at shipment, refer to the unit’s
nameplate.)
Minimum indoor volume & floor area relative to
the amount of refrigerant is roughly as given in
the following table.
04-309 Sanyo-1_p96-127 10/27/04 2:10 PM Page 121
Содержание ACS100PH
Страница 95: ...3 3 2 3 1 Indoor Units Wall Mounted Type AWS36PH Electric Wiring Diagram ...
Страница 96: ...3 3 3 3 1 Indoor Units Wall Mounted Type AWS36PH Schematic Diagram ...
Страница 97: ...3 3 4 3 1 Indoor Units Wall Mounted Type AWS71PH Electric Wiring Diagram ...
Страница 98: ...3 3 5 3 1 Indoor Units Wall Mounted Type AWS71PH Schematic Diagram ...
Страница 99: ...3 3 6 3 2 Outdoor Units Electric Wiring Diagram AES71PIC ...
Страница 100: ...3 3 7 3 2 Outdoor Units Schematic Diagram AES71PIC ...
Страница 101: ...3 3 8 3 2 Outdoor Units Electric Wiring Diagram AES71PIH ...
Страница 102: ...3 3 9 3 2 Outdoor Units Schematic Diagram AES71PIH ...
Страница 103: ...3 3 10 3 2 Outdoor Units Electric Wiring Diagram AES100PIC ...
Страница 104: ...3 3 11 3 2 Outdoor Units Schematic Diagram AES100PIC ...
Страница 105: ...3 3 12 3 2 Outdoor Units Electric Wiring Diagram AES100PIH ...
Страница 106: ...3 3 13 3 2 Outdoor Units Schematic Diagram AES100PIH ...
Страница 107: ...3 3 14 3 2 Outdoor Units Electric Wiring Diagram AES125PIC ...
Страница 108: ...3 3 15 3 2 Outdoor Units Schematic Diagram AES125PIC ...
Страница 109: ...3 3 16 3 2 Outdoor Units Electric Wiring Diagram AES125PIH ...
Страница 110: ...3 3 17 3 2 Outdoor Units Schematic Diagram AES125PIH ...