P341/EN O/B11
Operation Guide
CHAPTER 3
Commissioning and
Page 10/80
Maintenance
MiCOM P341
The insulation resistance should be greater than 100Mý at 500V.
On completion of the insulation resistance tests, ensure all external wiring is correctly
reconnected to the unit.
4.1.4
External wiring
Check that the external wiring is correct to the relevant relay diagram or scheme
diagram. The relay diagram number appears on the rating label under the top
access cover on the front of the relay. The corresponding connection diagram will
have been supplied with the ALSTOM order acknowledgement for the relay.
If an MMLG test block is provided, the connections should be checked against the
scheme (wiring) diagram. It is recommended that the supply connections are to the
live side of the test block (coloured orange with the odd numbered terminals (1, 3, 5,
7 etc.)). The auxiliary supply is normally routed via terminals 13 (supply positive) and
15 (supply negative), with terminals 14 and 16 connected to the relay’s positive and
negative auxiliary supply terminals respectively. However, check the wiring against
the schematic diagram for the installation to ensure compliance with the customer’s
normal practice.
4.1.5
Watchdog contacts
Using a continuity tester, check that the watchdog contacts are in the states given in
Table 2 for a de-energised relay.
Contact State
Terminals
Relay De-energised
Relay Energised
F11 – F12
Closed
Open
F13 – F14
Open
Closed
Table 2:
Watchdog contact status
4.1.6
Auxiliary supply
The relay can be operated from either a dc only or an ac/dc auxiliary supply
depending on the relay’s nominal supply rating. The incoming voltage must be
within the operating range specified in Table 3.
Without energising the relay, measure the auxiliary supply to ensure it is within the
operating range.
Nominal Supply Rating
DC Operating Range
AC Operating Range
24 – 48V
[ – ]
19 to 65V
–
48 – 125V
[30 - 100]
37 to 150V
24 to 110V
110 – 250V [100 - 240V]
87 to 300V
80 to 265V
Table 3:
Operational range of auxiliary supply Vx
It should be noted that the relay can withstand an ac ripple of up to 12% of the upper
rated voltage on the dc auxiliary supply.
DO NOT ENERGISE THE RELAY USING THE BATTERY CHARGER WITH THE
BATTERY DISCONNECTED AS THIS CAN IRREPARABLY DAMAGE THE
RELAY’S POWER SUPPLY CIRCUITRY.
Содержание MiCOM P341
Страница 1: ...MiCOM P341 Interconnection Protection Relay Operation Guide P341 EN O B11...
Страница 2: ......
Страница 3: ...Operation Guide MiCOM P341 Interconnection Protection Relay Volume 2...
Страница 4: ......
Страница 6: ...P341 EN O A11 Operation Guide Issue Control MiCOM P341...
Страница 8: ...P341 EN O B11 Operation Guide MiCOM P341...
Страница 10: ......
Страница 12: ......
Страница 17: ...Operation Guide P341 EN O B11 MiCOM P341 CHAPTER 1 Introduction...
Страница 18: ...P341 EN O B11 Operation Guide MiCOM P341...
Страница 41: ...Operation Guide P341 EN O B11 MiCOM P341 CHAPTER 2 Installation...
Страница 42: ...P341 EN O B11 Operation Guide MiCOM P341...
Страница 44: ...P341 EN O B11 Operation Guide CHAPTER 2 Installation Page 2 10 MiCOM P341...
Страница 53: ...Operation Guide P341 EN O B11 MiCOM P341 CHAPTER 3 Commissioning and Maintenance...
Страница 54: ...P341 EN O B11 Operation Guide MiCOM P341...
Страница 58: ...P341 EN O B11 Operation Guide CHAPTER 3 Commissioning and Page 4 80 Maintenance MiCOM P341...
Страница 135: ...Operation Guide P341 EN O B11 MiCOM P341 CHAPTER 4 Problem Analysis...
Страница 136: ...P341 EN O B11 Operation Guide MiCOM P341...
Страница 138: ...P341 EN O B11 Operation Guide CHAPTER 4 Problem Analysis Page 2 8 MiCOM P341...
Страница 145: ...Operation Guide P341 EN O B11 MiCOM P341 APPENDIX A Relay Menu Database...
Страница 273: ...Operation Guide P341 EN O B11 MiCOM P341 APPENDIX B External Connection Diagrams...
Страница 274: ...P341 EN O B11 Operation Guide MiCOM P341...
Страница 278: ...P341 EN O A11 Operation Guide MiCOM P341...
Страница 281: ......