User Guide 

P12x/EN FT/A96

 
MiCOM P121/P122/P123 

 

Page 9/72

 

3. PASSWORD 

3.1 

Password protection  

A password is required for relay settings, especially when changing the various thresholds, 
time delays, communication parameters, allocation of inputs and outputs relays. 

The password consists of four capital characters. When leaving factory, the password is set 
to AAAA. The user can define his own combination of four characters.  

Should the password be lost or forgotten, the modification of the stored parameters is 
blocked. It is then necessary to contact the manufacturer or his representative and a stand-
by password specific to the relay may be obtained.  

The programming mode is indicated with the letter "P" on the right hand side of the display 
on each menu heading. The letter 

"P"

 remains present as long as the password is active 

(

5 minutes

 if there is no action on the keypad). 

3.1.1 Password 

entry 

The input of the password is requested as soon as a modification of a parameter is made for 
any one of the six/eight menus and the submenus. The user enters each one of the 4 
characters and then validates the entire password with 

After 5 seconds, the display returns to the point of the preceding menu. 

If no key is pressed inside of 5 minutes, the password is deactivated. A new password 
request is associated with any subsequent parameter modification. 

3.1.2 

Changing the password 

To change an active password, go to the OP. PARAMETERS menu and then to the 
Password submenu. Enter the current password and validate it. Then press 

 and enter the 

new password character by character and validate the new password using 

The message NEW PASSWORD OK is displayed to indicate that the new password has 
been accepted. 

3.1.3 

Change of setting invalidation 

The procedure to modify a setting is described in the following sections of this manual. 

If there is a need to get back to the old setting push key 

 before validating the setting 

change. The following message will then appear on the LCD for a few seconds and the old 
setting will remain unchanged. 

UPGRADE 
CANCEL 

 

Содержание MiCom P120

Страница 1: ...MiCOM P120 P121 P122 P123 Overcurrent Relays Version 11 Technical Guide P12X EN T A96...

Страница 2: ......

Страница 3: ...Case Dimensions P12x EN IN A96 User Guide P12x EN FT A96 Menu Content Tables P12x EN HI A96 Technical Data and Curve Characteristics P12x EN TD A96 Application Guide P12x EN AP A96 Communication Data...

Страница 4: ...P12x EN T A96 Technical Guide Contents Page 2 2 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 5: ...3 1 Symbols 3 3 2 Labels 3 4 INSTALLING COMMISSIONING AND SERVICING 3 5 DECOMMISSIONING AND DISPOSAL 6 6 EQUIPMENT WHICH INCLUDES ELECTROMECHANICAL ELEMENTS 6 7 TECHNICAL SPECIFICATIONS FOR SAFETY 6 7...

Страница 6: ...miliar with the contents of that Safety Section or this Safety Guide When electrical equipment is in operation dangerous voltages will be present in certain parts of the equipment Failure to observe w...

Страница 7: ...ng procedures to ensure safety The equipment documentation should be consulted before installing commissioning or servicing the equipment Terminals exposed during installation commissioning and mainte...

Страница 8: ...potential the pre wired but unused connections should be connected to the common potential of the grouped connections Before energizing the equipment the following should be checked Voltage rating pol...

Страница 9: ...each part of the test the voltage should be gradually reduced to zero to discharge capacitors before the test leads are disconnected Insertion of modules and pcb cards Modules and PCB cards must not...

Страница 10: ...k of electric shock Exposure of live parts Removal of the cover may expose hazardous live parts such as relay contacts these should not be touched before removing the electrical power 7 TECHNICAL SPEC...

Страница 11: ...monstrated by reference to safety standards Electromagnetic Compatibility Directive EMC 89 336 EEC amended by 93 68 EEC The following Product Specific Standard was used to establish conformity EN 5026...

Страница 12: ...on UL Underwriters Laboratory of America If applicable the following marks will be present on the equipment UL Recognized to UL USA requirements UL Recognized to UL USA and CSA Canada requirements UL...

Страница 13: ...Introduction P12x EN IT A96 MiCOM P120 P121 P122 P123 INTRODUCTION...

Страница 14: ......

Страница 15: ...ction P12x EN IT A96 MiCOM P120 P121 P122 P123 Page 1 8 CONTENTS 1 INTRODUCTION 3 2 HOW TO USE THIS MANUAL 4 3 INTRODUCTION TO THE MiCOM P120 P121 P122 P123 RELAYS 5 4 MAIN FUNCTIONS 6 5 EQUIVALENCE T...

Страница 16: ...P12x EN IT A96 Introduction Page 2 8 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 17: ...s of the MiCOM P120 range are AREVA T D universal overcurrent relays MiCOM P120 P121 P122 and P123 relays have been designed to control protect and monitor industrial installations public distribution...

Страница 18: ...ing installation and case dimensions Caution to be taken when handling electronic equipment P12x EN FT User Guide of MiCOM P120 P121 P122 and P123 relays A detailed description of the features of MiCO...

Страница 19: ...to its protective functions each relay offers control and recording features They can be fully integrated to a control system so protection control data acquisition and recording of faults events and...

Страница 20: ...stantaneous start contact X X X X Latching output contacts 86 X X X X Setting groups 1 1 2 2 Circuit breaker failure detection 50BF X X Trip circuit supervision X X Circuit Breaker monitoring and cont...

Страница 21: ...2220B TA 521x 5320R TAS 1xxx 2xxx 3xxx TAS 5xxx 6xxx P121 KCGG 11x 12x 13x 14x KCGU 11x 14x MCAG 1x 3x MCGG 22 42 5x MCGG 6x 82 MCSU MCTD 01 MCHD 04 MCTI 14 34 44 MCTI 15 35 TA 1xxx 2xxx 3xxx TA 2220...

Страница 22: ...P12x EN IT A96 Introduction Page 8 8 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 23: ...Handling Installation and Case Dimensions P12x EN IN A96 MiCOM P120 P121 P122 P123 HANDLING INSTALLATION AND CASE DIMENSIONS...

Страница 24: ......

Страница 25: ...GENERAL CONSIDERATIONS 3 1 1 Receipt of relays 3 1 2 Electrostatic discharge ESD 3 2 HANDLING OF ELECTRONIC EQUIPMENT 4 3 RELAY MOUNTING 5 4 UNPACKING 6 5 STORAGE 7 6 DIMENSIONS 8 6 1 Connection of po...

Страница 26: ...P12x EN IN A96 Handling Installation and Case Dimensions Page 2 10 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 27: ...ed immediately should be returned with their protective polythene bags 1 2 Electrostatic discharge ESD The relays use components that are sensitive to electrostatic discharges The electronic circuits...

Страница 28: ...e by its frontplate frame or edges of the printed circuit board Avoid touching the electronic components printed circuit track or connectors 3 Do not pass the module to another person without first en...

Страница 29: ...anel rack assembly If an MMLG test block is to be included it should be positioned at the right hand side of the assembly viewed from the front Modules should remain protected by their metal case duri...

Страница 30: ...ed Relays must only be handled by skilled personnel The installation should be clean dry and reasonably free from dust and excessive vibration The site should be well lit to facilitate inspection Rela...

Страница 31: ...in the packing they should be retained The action of the de humidifier crystals will be impaired if the bag has been exposed to ambient conditions and may be restored by gently heating the bag for ab...

Страница 32: ...section of the wire see below Each reference corresponds to a sachet of 100 terminals Push on connector 4 8 x 0 8 wire size 0 75 1 5mm AREVA T D S Automation Information Systems Business reference ZB9...

Страница 33: ...ent transformers circuits The other circuits must be protected by fuses 6 2 Communication port RS485 Connections to RS485 is made using annular terminals It is recommended that a two core screened cab...

Страница 34: ...case 252 mm 97 39 158 168 49 5 Panel cut out Flush mounting fiwing details Flush mounting 25 1 226 151 2 max MiCOM 103 177 IA 214 50A C C C C 26 4 holes 3 4 4 holes 4 4 M4 screw All dimensions in mm 4...

Страница 35: ...User Guide P12x EN FT A96 MiCOM P120 P121 P122 P123 USER GUIDE...

Страница 36: ......

Страница 37: ...y Hardware or Software Warning Messages 12 5 MENUS 14 5 1 Default display 14 5 2 Access to the menu 14 5 3 Menu contents description 14 5 4 OP PARAMETERS Menu 17 5 4 1 P121 P122 and P123 additional OP...

Страница 38: ...9 4 Blocking Logic submenu 47 5 9 5 Inrush Blocking Logic submenu P122 and P123 only 49 5 9 6 Logic Select submenus P122 P123 only 50 5 9 7 Outputs Relays submenu 50 5 9 8 Latch of the auxiliary outp...

Страница 39: ...23 Page 3 72 6 WIRING 70 6 1 Auxiliary supply 70 6 2 Current measurement inputs 70 6 3 Logic inputs 70 6 4 Output relays 70 6 5 Communication 71 6 5 1 RS485 rear communication port 71 6 5 2 RS232 fron...

Страница 40: ...P12x EN FT A96 User Guide Page 4 72 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 41: ...hese relays it is possible to combine 1 and 5 Amp current inputs together i e a mix between 1A for earth fault and 5A for phase connections MiCOM 120 P121 P122 and P123 relays continuously measure pha...

Страница 42: ...ds are stored on a flash memory card that doesn t need to be backed up by a battery 2 1 LCD display and keypad description 2 1 1 LCD display In the front panel a liquid crystal display LCD displays se...

Страница 43: ...alarm This alarm can either be a threshold crossing instantaneous or a trip order time delayed As soon as an alarm is detected the LED starts blinking After all the alarms have been read the LED light...

Страница 44: ...more easily the active part of the MiCOM relay i e the chassis from its case open the two flaps then with a 3mm screwdriver turn the extractor located under the upper flap and pull it out of its case...

Страница 45: ...quested as soon as a modification of a parameter is made for any one of the six eight menus and the submenus The user enters each one of the 4 characters and then validates the entire password with Af...

Страница 46: ...splayed The user can read all the alarm messages pressing c The user acknowledges and clears the alarm messages from the LCD pressing The user can acknowledge each alarm message one by one or all by g...

Страница 47: ...sion menu Amps n Total measured current broken by CB is higher than the value set in AUTOMAT CTRL CB Supervision menu TRIP CIRCUIT Circuit breaker trip circuit failure longer than the supervision time...

Страница 48: ...s message can only be cleared once the cause of the hardware or software failure has been removed The control of the WARNING LED LED 3 is directly assigned to the status of the warning messages stored...

Страница 49: ...ted To reset this alarm it is necessary to power ON and OFF the relay Following this the last unsuccessful setting change will then need to be re applied If the alarm persists i e the SETTING ERROR al...

Страница 50: ...u Navigation through the different menus is done pressing the keys The organisation of the menus is shown in figure 2 for P120 and P121 and figure 3 for P122 and P123 There is no need of a password wh...

Страница 51: ...press OP PARAMETERS DEFAULT DISPLAY CONFIGURATION MEASUREMENTS COMMUNICATION PROTECTION AUTOMAT CTRL IA 1245A P0003ENa FIGURE 2 ORGANISATION OF MiCOM P120 AND P121 MAIN MENU NOTE The content of the me...

Страница 52: ...RL RECORDS IA 1245A P0004ENa FIGURE 3 ORGANISATION OF MiCOM P122 AND P123 MAIN MENU NOTE The content of the menu is presented in the document P12x EN HI This table helps the user to navigate through t...

Страница 53: ...ys the reference number that lists the equipment associated with the relay The entry of the reference is made character by character using After each character letter number or sign press to enter the...

Страница 54: ...ly Relays Maintenance P122 P123 only Phase rotation P122 P123 only Press to access the CONFIGURATION menu from the default display then until the desired submenu header is displayed 5 5 1 Submenu DISP...

Страница 55: ...T RATIO menu and until the desired submenu is reached CT Ratio Heading of the CT RATIO submenu To access the submenu press Line CT primary 1000 Choose the rated primary current of the line CT The sett...

Страница 56: ...tus of the Logic Input delayed by t Aux 2 Equation A Output of Boolean Equation A Equation B Output of Boolean Equation B Equation C Output of Boolean Equation C Equation D Output of Boolean Equation...

Страница 57: ...No Setting choice Yes LED 5 lights up when I threshold is crossed Setting choice No No operation when I threshold is crossed Led tI No Setting choice Yes LED 5 lights up when tI delay time has elapse...

Страница 58: ...e Yes LED 5 lights up when tIe delay time has elapsed Setting choice No No operation when tIe delay time has elapsed Led tIe Yes Setting choice Yes LED 5 lights up when tIe delay time has elapsed Sett...

Страница 59: ...n Boolean Equation C output is active Led Conf EQU D No Setting choice Yes LED 5 lights up when Boolean Equation D is active Setting choice No No operation when Boolean Equation D output is active Led...

Страница 60: ...when CB failure occurs Setting choice No No operation when CB failure occurs Led Input 3 No Setting choice Yes LED 5 lights up with signal present at logic input 3 Setting choice No No operation with...

Страница 61: ...ration when time Aux4 has elapsed 5 5 4 Submenu Selecting Active Protection Group P122 P123 only CONFIGURATION Heading of the CONFIGURATION menu Press to access the Group Select menu and until the des...

Страница 62: ...ss to modify and use to select your choice Press to validate the setting INH Alarm Taux2 No Setting choice Yes activation of auxiliary timer 2 output will not raise an alarm provided it does not lead...

Страница 63: ...On edge Start of disturbance record On edge Trip circuit supervision On level Change of setting group On level since version V6G CB Fail start On edge The user has to set under the Menu CONFIGURATION...

Страница 64: ...nt to activate the MAINTENANCE MODE of the relay If the user selects Yes output relays are disconnected from the protection and automation functions P122 P123 only Relays CMD 8765W4321 000000001 If th...

Страница 65: ...nal MEASUREMENTS Menu I1 103A Displays the positive sequence component I2 50A Displays the negative sequence component RATIO I2 I1 50 Displays the ratio of I2 I1 This derived measurement is used by th...

Страница 66: ...true RMS average value on a number of subperiod set in Record menu ROLLING AVERAGE IB Rms 0A Displays the IB average value demand The value is the true RMS average value on a number of subperiod set...

Страница 67: ...0 or 38400 bd Parity None Choose the parity in the ModBus data frame Select parity Even Odd or Non Stop Bits 1 Choose the number of stop bits in the ModBus data frame Select stop bit 0 or 1 Relay Addr...

Страница 68: ...hoice Baud Rate 9600 bd Choose the baud rate of MODBUS transmission Select from 300 600 1200 2400 4800 9600 19200 38400 bauds using Press to validate your choice Parity None Choose the parity in the M...

Страница 69: ...ated with I The setting range is from 0 to 150 s Use to change setting and press to validate your choice t Reset 0 ms Set the reset time value The setting range is from 0 to 600 s Use to change settin...

Страница 70: ...old I Press to modify this value The threshold setting range is from 0 5 to 40In Press to validate your choice Delay Type DMT Select the threshold delay time type associated with I Setting choices are...

Страница 71: ...curves Note available for 0 01 to 8 Ien range only 5 8 2 1 Ie DMT threshold menu Delay Type DMT Display of the Ie DMT time delay tIe 100 ms Set the time delay associated with Ie The setting range is f...

Страница 72: ...dditional Ie DMT reset time RI curves menu t Reset 60 ms Set the value for the time reset Press to modify this value The setting range is from 0 to 600 s Press to validate your choice 5 8 2 4 P122 P12...

Страница 73: ...if you select NO Only P122 P123 Ie 10 Ien Set the value for the third earth fault current threshold Ie Press to modify this value The threshold setting range is from 0 5 to 40 Ien Press to validate y...

Страница 74: ...Tempo Reset DMT Select the type of reset time delay Select between DMT Definitive Time and IDMT Inverse Time using and press to validate your choice t Reset 40 ms Set the value for the time reset The...

Страница 75: ...No the thermal overload function is not enabled and no menu content is displayed I 0 5 In Set the value for the thermal current threshold I Press to modify this value The setting range is from 0 1 to...

Страница 76: ...ROTECTION menu Press to access the menu then 4 times 79 Autoreclose Heading of the 79 AUTORECLOSER submenu Press to access the submenu Autoreclose Yes Setting choice Yes the autoreclose function is en...

Страница 77: ...of 10 ms Use to change setting and press to validate your choice Inhib Time tI 120 ms Set the value for the Inhibit Time tI associated with the autoreclose function Setting range is from 20 ms to 600...

Страница 78: ...ser can program the different automation functions available in the MiCOM P120 P121 P122 and P123 The different submenus are listed below Trip Commands Latch of the trip output relay RL1 by function P...

Страница 79: ...e Yes or No Trip tIe Yes Assign the first earth fault overcurrent tIe to the trip output relay RL1 Setting choice Yes or No Trip tIe No Assign the second earth fault overcurrent tIe to the trip output...

Страница 80: ...delayed threshold tI2 to the trip output relay RL1 Setting choice Yes or No Trip tI2 No Assign the second negative phase sequence overcurrent time delayed threshold tI2 to the trip output relay RL1 Se...

Страница 81: ...trip output relay RL1 associated with the second phase time delay overcurrent threshold tI Setting choice Yes or No Latch tI No Latch the trip output relay RL1 associated with the third phase time de...

Страница 82: ...ice Yes or No 5 9 2 3 P123 additional latch functions submenu Latch t Aux 4 No Latch the trip output relay RL1 associated with the delayed auxiliary input Aux 4 Setting choice Yes or No Latch SOTF No...

Страница 83: ...tI has disappeared Setting choice No The output relay will be active when the relevant command is active the relays will not be active if the relevant command is reset NOTE To reset the latched relays...

Страница 84: ...1 P121 P122 P123 additional Blocking Logic menu Block 1 t Aux 1 No Enables disables Blocking Logic of time delay of auxiliary input Aux1 Setting choice Yes No Block 1 t Aux 2 No Enables disables Bloc...

Страница 85: ...threshold doesn t activate the Inrush Blocking logic function Inr Harmonic 2 Ratio 20 Set the value for the 2nd harmonic threshold ratio calculated as a percentage of the fundamental component Press t...

Страница 86: ...Logic Select 1 of the second earth fault time delay overcurrent threshold tIe Setting choice Yes No Sel1 tIe No Enables disables Logic Select 1 of the third earth fault time delay overcurrent thresho...

Страница 87: ...t Ie 8765432 1100010 Assign second earth fault instantaneous overcurrent threshold Ie to output relays Setting choice 1 assigns the output relay 0 no assignment tIe 8765432 1100010 Assign second earth...

Страница 88: ...7 2 P122 P123 additional Outputs menu tI 8765432 1100010 Assign threshold for undercurrent I to the output relays i e to output 3 7 8 RL3 RL7 RL8 Setting choice 1 assigns the output relay 0 no assignm...

Страница 89: ...e 8765432 Group 0010000 Assign the Active Group indication to the output relays i e to output 6 RL6 Setting choice 1 assigns the output relay 0 no assignment Input3 8765432 0000000 Assign opto input 3...

Страница 90: ...hoice Yes No Output 4 Yes Latch the auxiliary output relay RL4 Setting choice Yes No 5 9 8 1 P122 P123 additional latch output relays menu Output 5 Yes Latch the auxiliary output relay RL5 Setting cho...

Страница 91: ...el 1 Logic selectivity 1 Log Sel 2 Logic selectivity 2 Change set Change of setting group default setting group 1 Reset Reset of the thermal state Trip Circ Trip circuit supervision input Strt tBF Sta...

Страница 92: ...tion Setting choice Yes No Input 2 Aux1 No Assign logic input 2 to the Auxiliary Timer 1 input function Setting choice Yes No Input 2 Aux2 No Assign logic input 2 to the Auxiliary Timer 2 input functi...

Страница 93: ...2 Manual Close No Assign logic input 2 to the Manual control close signal input Setting choice Yes No Input 2 Local Mode No Assign logic input 2 to the Local Mode input function Setting choice Yes No...

Страница 94: ...d load pick up function Selected threshold values can temporary be raised AUTOMAT CTRL Heading of the AUTOMAT CTRL menu Press to access the menu then until the submenu is reached Cold Load PU Heading...

Страница 95: ...ted and associated parameters can be set AUTOMAT CTRL Heading of the AUTOMAT CTRL menu Press to access the menu then until the menu is reached CB Fail Heading of the CB Fail submenu To navigate within...

Страница 96: ...CB open operations Setting range from 0 05 to 1 0 s in steps of 10 ms CB Close S vision Yes Selection of the time monitoring function of CB close operations Setting choice Yes No If Yes is selected th...

Страница 97: ...se to modify and press to validate your choice t Comm 4 1 s Selection of the t Comm 4 pulse time The setting range for t Comm 4 is from 0 1 s to 5 s in steps of 0 05 s Use to modify and press to valid...

Страница 98: ...and once elapsed the relay issues a trip order Setting choice No The crossing of the I threshold doesn t activate the SOTF function I No Setting choice Yes The crossing of the I threshold activates th...

Страница 99: ...h threshold tIe Time delayed second earth threshold tIe Time delayed third earth threshold t Aux 1 Copy of the status of the Logic Input delayed by t Aux 1 t Aux 2 Copy of the status of the Logic Inpu...

Страница 100: ...x1 tAux2 Equation A 03 OR Null Setting choice OR OR NOT AND AND NOT Setting Choice Null I tI I tI I tI Ie tIe Ie tIe Ie tIe tAux1 tAux2 Equation A 04 OR Null Setting choice OR OR NOT AND AND NOT Setti...

Страница 101: ...2 Equation A 13 OR Null Setting choice OR OR NOT AND AND NOT Setting Choice Null I tI I tI I tI Ie tIe Ie tIe Ie tIe tAux1 tAux2 Equation A 14 OR Null Setting choice OR OR NOT AND AND NOT Setting Choi...

Страница 102: ...access the different submenus CB Opening Time 95 ms Displays the circuit breaker opening time in ms CB Closing Time 115 ms Displays the circuit breaker closing time in ms CB Operations RST C 5489 Dis...

Страница 103: ...m and 420ms fault Date 12 11 99 Displays the date when the fault was recorded The format of the Date is DD MM YY In this example the fault was recorded on November 12th 1999 Active Set Group 1 Display...

Страница 104: ...splays which threshold has been crossed Length 57 ms Displays the period of time during which the threshold has been exceeded Trip No Displays if a trip followed the crossing of the threshold or not 5...

Страница 105: ...nd press to validate your choice 5 10 6 ROLLING DEMAND submenu P122 P123 only The Rolling Demand submenu makes it possible to set the values for rolling sub period and number of the sub period used fo...

Страница 106: ...voltage range of the inputs is identical to the DC or AC auxiliary supply range of the MiCOM relay e g Uaux 48 250 Vdc logic input voltage range 48 250 Vdc On the same MiCOM P12x relay the user can m...

Страница 107: ...P121 P122 P123 MiCOM P120 P121 P122 and P123and P123 relays provide a RS 232 communication port This port is dedicated to Setting software MiCOM S1 The cable between the relay and the PC is a standar...

Страница 108: ...P12x EN FT A96 User Guide Page 72 72 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 109: ...Menu Content Tables P12x EN HI A96 MiCOM P120 P121 P122 P123 MENU CONTENT TABLES...

Страница 110: ......

Страница 111: ...P122 V5 SOFTWARE 8 4 MiCOM P123 V5 SOFTWARE 14 5 MiCOM P122 V6 SOFTWARE 20 6 MiCOM P123 V6 SOFTWARE 26 7 MiCOM P120 V10 SOFTWARE 32 8 MiCOM P121 V10 SOFTWARE 34 9 MiCOM P122 V10 SOFTWARE 37 10 MiCOM...

Страница 112: ...P12x EN HI A96 Menu Content Tables Page 2 68 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 113: ...tatus 01 OP PARAMETERS Relay 4321 Status 1011 CONFIGURATION CT Ratio CT primary 1000 CT sec 1 Led 5 6 7 8 Led I Y N tI Y N l Y N tI Y N I Y N tI Y N Ie Y N tIe Y N Ie Y N tIe Y N Ie Y N tIe Y N MiCOM...

Страница 114: ...ip tI Yes Trip tI Yes Latch Functions Latch tI Yes Latch tI Yes Latch tI Yes Blocking Logic Block tI Yes Block tI Yes Block tI Yes Output Relays Trip 432 100 I tl I tl I tl CB Close PROTECTION 50 51 P...

Страница 115: ...N tI Y N l Y N tI Y N I Y N tI Y N Ie Y N tIe Y N Ie Y N tIe Y N Ie Y N tIe Y N MiCOM P121 V5 Software Menu content E Gnd CT primary 1000 E Gnd CT sec 1 Frequency 50 01 Hz I L 1 257 05 A I L 2 258 80...

Страница 116: ...ip tIe Yes Ie Yes Ie 1 0 Ien t Ie 300 ms Latch Functions Latch tI Yes Latch tI Yes Latch tI Yes Latch tIe Yes Latch tIe Yes Latch tIe Yes Blocking Logic Block tI Yes Block tI Yes Block tI Yes Block tI...

Страница 117: ...96 MiCOM P120 P121 P122 P123 Page 7 68 DEFAULT DISPLAY IL1 1245 A AUTOMAT CTRL MiCOM P121 V5 Software Menu content Latch Output Relays Output 2 No Output 3 Yes Output 4 No Inputs 1 2 None Unlatch 52 a...

Страница 118: ...Ratio Line CT primary 1000 Line CT sec 1 Led 5 6 7 8 Led I Y N tI Y N l Y N tI Y N I Y N tI Y N Ie Y N tIe Y N Ie Y N tIe Y N Ie Y N tIe Y N Therm Trip Y N Brkn Cond Y N CB Fail Y N tI2 Y N tI2 Y N In...

Страница 119: ...age IB RMS 148 A Average IC RMS 153 A MAX SUBPERIOD RST C MAX SUBPERIOD I A RMS 254 2 A MAX SUBPERIOD I C RMS 254 1 A ROLLING AVERAGE RST C MAX SUBPERIOD I B RMS 254 2 A ROLLING AVERAGE I A RMS 0 00 A...

Страница 120: ...Yes I 0 1 In Te 1 mn Trip 100 Alarm Yes k 1 05 Alarm 100 37 Undercurrent I Yes I 0 2 In tI 200 ms Ie Yes Ie 1 0 Ien t Ie 300 ms 50N 51N E Gnd Ie Yes Ie 0 01 Ien Delay Type INV Tms 0 025 t Reset 60 ms...

Страница 121: ...No Trip tAux 2 Yes Trip tAux 1 Yes Trip Brkn Cond No Trip tAux 3 Yes Latch tAux 3 Yes Latch tI2 Yes Latch tI2 No Blocking Logic 1 2 Block 1 tI Yes Block 1 tI Yes Block 1 tI Yes Block 1 tIe Yes Block...

Страница 122: ...C 32 s Ratio I 2 I 1 20 Cold Load PU Cold Load PU Yes Cold Load PU tl Yes Cold Load PU tl Yes Cold Load PU tle Yes Cold Load PU tle Yes Cold Load PU tTherm Yes Cold Load PU Level 120 Cold Load PU tCL...

Страница 123: ...Magnitude 500 A IC Magnitude 480 A IN Magnitude 103 A Active Set Group 2 Magnitude 1200 A Instantaneous Number 5 Hour 13 07 15 53 Date 10 12 00 Length 57 ms Trip No Origin Io Disturb Record Pre Time...

Страница 124: ...ine CT sec 1 LED 5 6 7 8 Led I Y N tI Y N l Y N tI Y N I Y N tI Y N Ie Y N tIe Y N Ie Y N tIe Y N Ie Y N tIe Y N Therm Trip Y N Brkn Cond Y N CB Fail Y N tI2 Y N Input 1 Y N Input 2 Y N Input 3 Y N In...

Страница 125: ...ses 0 DEFAULT DISPLAY IA 1245 A Phase Rotation CONFIGURATION MiCOM P123 V5 Software Menu content Communication Yes Baud Rate 19200 Bd Parity None Stop bits 1 Relay Address 12 COMMUNICATION Phase rotat...

Страница 126: ...Ie 1 0 Ien t Ie 300 ms Idmt IEC SI Ie Yes PROTECTION G1 G2 49 Therm OL Therm OL Yes I 0 1 In Te 1 mn Trip 100 Alarm Yes k 1 05 Alarm 100 37 Undercurrent I Yes I 0 2 In 79 Autoreclose Autoreclose Yes E...

Страница 127: ...rip tAux 1 Yes Trip tI2 No Trip Brkn Cond No Output Relays Trip 8765432 1000100 I tl I tl I tl Ie tle Ie tle Ie tle tl tl2 tI2 Therm Alarm Therm Trip CB Alarm 52 Fail Brkn Cond CB Fail CB Close tAux1...

Страница 128: ...s Cold Load PU tl Yes Cold Load PU tle Yes Cold Load PU tle Yes Cold Load PU tI2 Yes Cold Load PU tTherm Yes Cold Load PU Level 120 Cold Load PU tCL 2 s Cold Load PU tl Yes Cold Load PU tle Yes Cold L...

Страница 129: ...Time Peak Value Time Window 5 mn Disturb Rec Trig ON INST RECORDS Amps n IC 5 E6 Amps n IB 5 E6 Record Number 4 Fault Time 12 05 23 42 Fault Date 09 01 01 Faulted Phase EARTH Threshold Ie IA Magnitude...

Страница 130: ...Ratio Line CT primary 1000 Line CT sec 1 LED 5 6 7 8 Led I Y N tI Y N l Y N tI Y N I Y N tI Y N Ie Y N tIe Y N Ie Y N tIe Y N Ie Y N tIe Y N Therm Trip Y N Brkn Cond Y N CB Fail Y N tI2 Y N tI2 Y N I...

Страница 131: ...A Average IC RMS 153 A DEFAULT DISPLAY IA 1245 A Phase Rotation MiCOM P122 V6 Software Menu content Communication Yes Baud Rate 19200 Bd Parity None Date format PRIVATE Stop bits 1 Relay Address 12 C...

Страница 132: ...Ie Yes Ie 0 01 Ien Delay Type IDMT Tms 0 025 t Reset 60 ms Ie 0 01 Ien t Ie 300 ms Ie Yes Ie 1 0 Ien t Ie 300 ms Idmt IEC SI Ie Yes 49 Therm OL Therm OL Yes I 0 1 In Te 1 mn Trip 100 Alarm Yes k 1 05...

Страница 133: ...tIe Yes Trip tI Yes Trip tAux 2 Yes Trip tAux 1 Yes Trip tI2 No Trip Brkn Cond No Output Relays Trip 65432 00100 I tl I tl I tl Ie tle Ie tle Ie tle tl tl2 tI2 Therm Alarm Therm Trip CB Alarm 52 Fail...

Страница 134: ...Output 5 Yes Cold Load PU Cold Load PU Yes Cold Load PU tl Yes Cold Load PU tl Yes Cold Load PU tle Yes Cold Load PU tle Yes Cold Load PU tI2 Yes Cold Load PU tTherm Yes Cold Load PU Level 120 Cold Lo...

Страница 135: ...Time Peak Value Time Window 5 mn Disturb Rec Trig ON INST RECORDS Amps n IC 5 E6 Amps n IB 5 E6 Record Number 4 Fault Time 12 05 23 42 Fault Date 09 01 01 Faulted Phase EARTH Threshold Ie IA Magnitude...

Страница 136: ...ine CT sec 1 LED 5 6 7 8 Led I Y N tI Y N l Y N tI Y N I Y N tI Y N Ie Y N tIe Y N Ie Y N tIe Y N Ie Y N tIe Y N Therm Trip Y N Brkn Cond Y N CB Fail Y N tI2 Y N tI2 Y N Input 1 Y N Input 2 Y N Input...

Страница 137: ...DEFAULT DISPLAY IA 1245 A Phase Rotation MiCOM P123 V6 Software Menu content Communication Yes Baud Rate 19200 Bd Parity None Date format PRIVATE Stop bits 1 Relay Address 12 COMMUNICATION Phase rotat...

Страница 138: ...Ien t Ie 300 ms Idmt IEC SI Ie Yes PROTECTION G1 G2 49 Therm OL Therm OL Yes I 0 1 In Te 1 mn Trip 100 Alarm Yes k 1 05 Alarm 100 37 Undercurrent I Yes I 0 2 In 79 Autoreclose Autoreclose Yes Ext CB F...

Страница 139: ...1 Yes Trip tI2 No Trip Brkn Cond No Output Relays Trip 8765432 1000100 I tl I tl I tl Ie tle Ie tle Ie tle tl tl2 tI2 Therm Alarm Therm Trip CB Alarm 52 Fail Brkn Cond CB Fail CB Close tAux1 tAux2 tA...

Страница 140: ...utput 5 Yes Output 8 No Cold Load PU Cold Load PU Yes Cold Load PU tl Yes Cold Load PU tl Yes Cold Load PU tle Yes Cold Load PU tle Yes Cold Load PU tI2 Yes Cold Load PU tTherm Yes Cold Load PU Level...

Страница 141: ...Time Peak Value Time Window 5 mn Disturb Rec Trig ON INST RECORDS Amps n IC 5 E6 Amps n IB 5 E6 Record Number 4 Fault Time 12 05 23 42 Fault Date 09 01 01 Faulted Phase EARTH Threshold Ie IA Magnitude...

Страница 142: ...Rate 19200 Bd Parity None Stop bits 1 Relay Address 12 COMMUNICATION Phase Text L1 Display Language ENGLISH Description P120 2 Software Version 10 D DEFAULT DISPLAY IL1 1245 A Password Reference ALST...

Страница 143: ...Tms 0 025 I 2 0 In I 10 0 In t I 110 ms Idmt IEC SI I Yes t I 300 ms I Yes Inputs 1 2 None Unlatch 52 a 52 b CB FLT Aux 1 Aux 2 Blk Log DEFAULT DISPLAY IL1 1245 A MiCOM P120 V10 Software Menu content...

Страница 144: ...pe IDMT Tms 0 025 I 2 0 In t I 300 ms I Yes I 10 0 In t I 110 ms Idmt IEC SI I Yes tReset 60 ms Delay Type DMT Software version 5 F Language ENGLISH DEFAULT DISPLAY IL1 1245 A Password Description P12...

Страница 145: ...et 60 ms Ie 0 01 Ien t Ie 300 ms Idmt IEC SI Ie Yes Delay Type DMT Output Relays Trip 432 100 I tl I tl I tl Ie tle Ie tle Ie tle Close DEFAULT DISPLAY IL1 1245 A PROTECTION MiCOM P121 V10 Software Me...

Страница 146: ...ware Menu content Latch Output Relays Output 2 No Output 3 Yes Output 4 No Inputs 1 2 None Unlatch 52 a 52 b CB FLT Aux 1 Aux 2 Blk Log DEFAULT DISPLAY IL1 1245 A AUTOMAT CTRL MiCOM P121 V10 Software...

Страница 147: ...ive Group 1 Setting Group 1 Alarms Inst Self reset No Reset led on fault No Inputs Inputs 321 001 Voltage input DC Alarm Battery No Language ENGLISH DEFAULT DISPLAY IA 1245 A Password Description P122...

Страница 148: ...ING AVERAGE I B RMS 0 00 A ROLLING AVERAGE I C RMS 0 00 A REL MAINTENANCE CONFIGURATION Maintenance Mode Yes RELAYS 65W4321 CMD 0000000 Frequency 50 01 Hz I A 257 05 A I B 258 80 A I C 257 50 A I 1 10...

Страница 149: ...2 0 In t I 300 ms Idmt IEC SI I Yes tReset 60 ms Delay Type DMT I Yes I 10 0 In t I 110 ms I sample Yes Ie sample Yes Interlock Ie YES MiCOM P122 V10 Software Menu content 46 Neg Seq OC I2 Yes I2 0 1...

Страница 150: ...2 Sel1 tI Yes Sel 1 tI Yes Sel1 tle Yes t Sel 1 150 ms Sel 1 tle Yes Block 1 tI2 No Trip tAux 3 Yes Latch tAux 3 Yes Block 1 tAux 3 No MiCOM P122 V10 Software Menu content DEFAULT DISPLAY IA 1245 A L...

Страница 151: ...n 2 CB Open Time 150 ms CB Open Alarm Yes tOpen Pulse 300ms tClose Pulse 500 ms I 0 1 In Bloc Ie Yes Block I No Aux3 Time tAux3 300 ms DEFAULT DISPLAY IA 1245 A Inputs 1 2 3 Broken Conductor Brkn Con...

Страница 152: ...ent Instantaneous Number 5 Hour 13 07 15 53 Date 09 01 01 Length 57 ms Trip No Origin Ie Rolling Demand Sub Period 1mn Num of Sub Per 1 DEFAULT DISPLAY IA 1245 A CB Monitoring CB Opening Time 83 ms CB...

Страница 153: ...Group 1 Setting Group 1 Alarms Inst Self reset No Reset led on fault No Inputs Inputs 54321 00001 Voltage input DC Alarm Battery No Language ENGLISH DEFAULT DISPLAY IA 1245 A Password Description P12...

Страница 154: ...NFIGURATION Maintenance Mode Yes RELAYS 8765W4321 CMD 000000000 I Yes I 10 0 In t I 110 ms I sample Yes tReset 0 ms Frequency 50 01 Hz I A 257 05 A I B 258 80 A I C 257 50 A I 1 103 A I 2 50 A MEASURE...

Страница 155: ...2 0111 CYCLES 4321 tAux1 1112 CYCLES 4321 tIe 1111 CYCLES 4321 tIe 1111 CYCLES 4321 tIe 1111 Ie sample Yes tReset 0 ms Interlock Ie YES MiCOM P123 V10 Software Menu content 46 Neg Seq OC I2 Yes I2 0 1...

Страница 156: ...Yes Latch tAux 4 Yes Block 1 tAux 3 No Block 1 tAux 4 No Trip CB fail Yes Trip Soft Yes Ctrl Trip Yes Latch Soft Yes Latch CB Fail Yes MiCOM P123 V10 Software Menu content DEFAULT DISPLAY IA 1245 A L...

Страница 157: ...250 ms Aux3 Time tAux3 300 ms Aux4 Time tAux4 50 ms Soft Soft Yes tSoft 100 ms I Yes I Yes MiCOM P123 V10 Software Menu content DEFAULT DISPLAY IA 1245 A Inputs 1 2 3 4 5 Broken Conductor Brkn Cond Ye...

Страница 158: ...ent Instantaneous Number 5 Hour 13 07 15 53 Date 09 01 01 Length 57 ms Trip No Origin Ie Rolling Demand Sub Period 1mn Num of Sub Per 1 DEFAULT DISPLAY IA 1245 A CB Monitoring CB Opening Time 83 ms CB...

Страница 159: ...6 07 Time 14 15 34 Language ENGLISH Output relays Fail 4321 Safe R 0000 Frequency 50 01 Hz I N 10 05 A MEASUREMENTS Primary 1000 Secondary 1 CT Ratio DEFAULT DISPLAY IN 10 05 A Password Description P1...

Страница 160: ...tl I tl Close Input1 Input2 Inputs 1 2 Unlatch 52 a 52 b CB FLT Aux 1 Aux 2 Blk Log 1 Start Disturb Synchro Inputs DEFAULT DISPLAY IN 10 05 A MiCOM P120 V11 Software Menu content Communication Yes Ba...

Страница 161: ...nitude 1200 A Instantaneous Number 5 Time 13 07 15 53 Date 09 01 01 Length 57 ms Trip No Origin Ie MiCOM P120 V11 Software Menu content DEFAULT DISPLAY IN 10 05 A Fault Record Disturb Record Pre Time...

Страница 162: ...rm tAux1 No Inh Alarm tAux2 No Output relays Fail 4321 Safe R 0000 Frequency 50 01 Hz I A 257 05 A I B 258 80 A I C 257 50 A MEASUREMENTS I N 20 00 A DEFAULT DISPLAY IA 1245 A Password Description P12...

Страница 163: ...2 0 In t I 300 ms Idmt IEC SI I Yes tReset 60 ms Delay Type DMT I Yes I 10 0 In t I 110 ms I sample Yes tReset 0 ms DEFAULT DISPLAY IA 1245 A 50N 51N E Gnd Ie Yes Ie 0 01 Ien Delay Type IDMT Tms 0 025...

Страница 164: ...G H Equation A 00 I T operate 10 ms T reset 30 ms Logic Equations Equation A 01 OR Aux4 Equation A 02 AND NOT tI2 Equation A 03 OR None DEFAULT DISPLAY IA 1245 A Latch Functions Latch tI Yes Latch tI...

Страница 165: ...Self reset No Reset led on fault No Inputs Inputs 321 001 Voltage input DC Language ENGLISH Inh Alarm tAux1 No Inh Alarm tAux2 No Inh Alarm tAux3 Yes DEFAULT DISPLAY IA 1245 A Password Description P12...

Страница 166: ...10 ms I sample Yes tReset 0 ms MiCOM P122 V11 Software Menu content Maintenance Mode Yes Relays 65W4321 CMD 0000000 Frequency 50 01 Hz I A 257 05 A I B 258 80 A I C 257 50 A I 1 103 A I 2 50 A MEASURE...

Страница 167: ...k 1 05 Alarm 100 37 Undercurrent I Yes I 0 2 In tI 200 ms Delay Type DMT Ie sample Yes tReset 0 ms MiCOM P122 V11 Software Menu content 46 Neg Seq OC I2 Yes I2 0 1 In Delay Type IDMT Tms 0 025 Curve I...

Страница 168: ...ng Ie Yes Inrush blocking Ie No Inrush blocking Ie No Inrush blocking I2 Yes Inrush blocking I2 No MiCOM P122 V11 Software Menu content DEFAULT DISPLAY IA 1245 A Latch Functions Latch tI Yes Latch tI...

Страница 169: ...oad PU Level 120 Cold Load PU tCL 2 s Cold Load PU tl Yes Cold Load PU tle Yes Cold Load PU tl2 No MiCOM P122 V11 Software Menu content DEFAULT DISPLAY IA 1245 A AUTOMAT CTRL Output Relays Trip 65432...

Страница 170: ...ion A B C D E F G H Equation A 00 I T operate 10 ms T reset 30 ms Equation A 01 OR Aux4 Equation A 02 AND NOT tI2 Equation A 03 OR None DEFAULT DISPLAY IA 1245 A AUTOMAT CTRL CB Fail CB Fail Yes CB Fa...

Страница 171: ...15 53 Date 09 01 01 Length 57 ms Trip No Origin Ie Rolling Demand Sub Period 1mn Num of Sub Per 1 MiCOM P122 V11 Software Menu content DEFAULT DISPLAY IA 1245 A CB Monitoring CB Opening Time 83 ms CB...

Страница 172: ...on fault No Inputs Inputs 54321 00001 Voltage input DC Language ENGLISH Inh Alarm tAux1 No Inh Alarm tAux2 No Inh Alarm tAux3 Yes Inh Alarm tAux4 Yes DEFAULT DISPLAY IA 1245 A Password Description P12...

Страница 173: ...s I sample Yes tReset 0 ms MiCOM P123 V11 Software Menu content Maintenance Mode Yes Relays 8765W4321 CMD 000000000 Frequency 50 01 Hz I A 257 05 A I B 258 80 A I C 257 50 A I 1 103 A I 2 50 A MEASURE...

Страница 174: ...Aux1 1112 CYCLES 4321 tIe 1111 CYCLES 4321 tIe 1111 CYCLES 4321 tIe 1111 Ie sample Yes tReset 0 ms MiCOM P123 V11 Software Menu content 46 Neg Seq OC I2 Yes I2 0 1 In Delay Type IDMT Tms 0 025 Curve I...

Страница 175: ...ng Ie Yes Inrush blocking Ie No Inrush blocking Ie No Inrush blocking I2 Yes Inrush blocking I2 No MiCOM P123 V11 Software Menu content DEFAULT DISPLAY IA 1245 A Latch Functions Latch tI Yes Latch tI...

Страница 176: ...ad PU tl Yes Cold Load PU tle Yes Cold Load PU tl2 No MiCOM P123 V11 Software Menu content DEFAULT DISPLAY IA 1245 A AUTOMAT CTRL Output Relays Trip 8765432 1000100 I tl I tl I tl Ie tle Ie tle Ie tle...

Страница 177: ...ion A B C D E F G H Equation A 00 I T operate 10 ms T reset 30 ms Equation A 01 OR Aux4 Equation A 02 AND NOT tI2 Equation A 03 OR None DEFAULT DISPLAY IA 1245 A AUTOMAT CTRL CB Fail CB Fail Yes CB Fa...

Страница 178: ...15 53 Date 09 01 01 Length 57 ms Trip No Origin Ie Rolling Demand Sub Period 1mn Num of Sub Per 1 MiCOM P123 V11 Software Menu content DEFAULT DISPLAY IA 1245 A CB Monitoring CB Opening Time 83 ms CB...

Страница 179: ...Technical Data P12x EN TD A96 MiCOM P120 P121 P122 P123 TECHNICAL DATA AND CHARACTERISTIC CURVES...

Страница 180: ......

Страница 181: ...1 Protection Setting Ranges 8 8 2 50N 51N Earth fault protection P120 P121 P122 P123 8 8 2 1 Protection Setting Ranges 9 8 3 Undercurrent Protection P122 P123 10 8 3 1 Protection Setting Ranges 10 8...

Страница 182: ...ogical gates 16 9 8 3 Available signals 17 9 8 4 An example logic implementation using Equation A is shown below 17 9 9 INRUSH BLOCKING 18 9 9 1 Setting Ranges 18 10 RECORDING FUNCTIONS P120 P121 P122...

Страница 183: ...Burden Stand by 3W DC or 8VA AC Max 6W DC or 14VA AC 1 2 Frequency Frequency protection functions From 45 to 65Hz Nominal frequency 50 60Hz 1 3 Current Inputs Phase current inputs 1 and 5A by connect...

Страница 184: ...250 Vdc 48 240 Vac Special EA 38 4 300 Vdc 38 4 264 Vac 24 250 Vdc 24 240 Vac 19 2 Vdc 19 2 Vac 35 mA 2 3 mA 300 Vdc 264 Vac H 48 250 Vdc 48 240 Vac 38 4 300 Vdc 38 4 264 Vac 129 Vdc 105 Vdc 3 0 mA 12...

Страница 185: ...995 and IEC 60255 22 5 2002 4kV common mode Level 4 2kV differential mode Level 4 Conducted Emissions EN 55022 1998 0 15 0 5MHz 79dB V quasi peak 66dB V average 0 5 30MHz 73dB V quasi peak 60dB V aver...

Страница 186: ...e 6 hour duration within any 24 hour period Humidity dam heat IEC 60068 2 78 2001 56 days at 93 RH and 40 C Enclosure protection IEC 60 529 2001 Dust IP50 whole case Front IP 52 Back IP 10 Sinusoidal...

Страница 187: ...t elements I2 I2 I2 0 1 to 40 In 2 DT I2s 2 IDMT 1 1I2s 2 0 95 I2s 2 1 05 I2s 2 2 30 50ms 5 30 50ms Phase undercurrent element I 0 02 to 1 In 2 DT I 2 0 95 I 2 2 30 50ms Broken conductor I2 I1 20 to 1...

Страница 188: ...TMS 0 025 1 5 0 001 I Reset Delay Type DT or IDMT I RTMS 0 025 3 2 0 025 I tReset 0 00 s 100 s 0 01 s I No or Yes I 0 5 In 40 In 0 01 In Delay type DT or IDMT IEC_STI IEC_SI IEC_VI IEC_EI IEC_LTI C02...

Страница 189: ...Ien 0 1 Ien Ie 0 5 Ien 40 Ien 0 1 Ien Ie No or Yes Delay type DT or IDMT IEC_STI IEC_SI IEC_VI IEC_EI IEC_LTI C02 C08 IEEE_MI IIEEE_VI IEEE_EI RI RECT curve or RXIDG only for Cortec code P12 B X X tIe...

Страница 190: ...ction P122 P123 Phase current Fundamental only NOTE When I2 is associated to an IDMT curve the maximum setting recommended should be 2In 8 4 1 Protection Setting Ranges Setting ranges 46 Neg Seq OC Mi...

Страница 191: ...P123 Page 11 40 8 5 Thermal Overload Protection P122 P123 Phase Current RMS 8 5 1 Protection Setting Ranges 49 Therm OL Setting ranges Therm OL No or Yes I 0 1 In 3 2 In 0 01 Te 1 mn 200 mn 1mn k 1 1...

Страница 192: ...0 01 s 600 s 0 01 s Aux1 I Yes or No Aux2 Ie Yes or No Ext Block Yes or No Dead time tD1 0 01 s 300 s 0 01 s tD2 0 01 s 300 s 0 01 s tD3 0 01 s 600 s 0 01 s tD4 0 01 s 600 s 0 01 s Reclaim time tR 0 0...

Страница 193: ...rther timing Fixed time out for lacking of CB opening signal on trip protection 2 00 s at 50 Hz 1 67 s at 60 Hz Time out for lacking of CB closing signal on close control after dead time tClose Pulse...

Страница 194: ...s 0 01 s tAux2 0 200 s 0 01 s tAux3 0 200 s 0 01 s tAux4 0 200 s 0 01 s 9 3 Broken Conductor Detection P122 P123 Principle used I2 I1 Functionality available for IA or IB or IC 10 In 9 3 1 Broken Con...

Страница 195: ...10 s 5 s 0 01 s tClose Pulse 0 10 s 5 s 0 01 s Note The tOpen Close Pulse is available in the P123 for the Local Remote functionality 9 7 SOTF TOR Switch on to fault Trip on reclose P123 9 7 1 Settin...

Страница 196: ...EQU D Toperat 0 s 600 s 0 01 s EQU D Treset 0 s 600 s 0 01 s EQU E Toperat 0 s 600 s 0 01 s EQU E Treset 0 s 600 s 0 01 s EQU F Toperat 0 s 600 s 0 01 s EQU F Treset 0 s 600 s 0 01 s EQU G Toperat 0...

Страница 197: ...t earth threshold tIe Time delayed second earth threshold tIe Time delayed third earth threshold t Aux 1 Copy of the status of the Logic Input delayed by t Aux 1 t Aux 2 Copy of the status of the Logi...

Страница 198: ...uation A 05 OR Null Equation A 06 OR Null Equation A 07 OR Null Equation A 08 A 14 OR Null Equation A 15 OR Null 9 9 INRUSH BLOCKING 9 9 1 Setting Ranges Inrush Block Setting range Min Max Step Inrush...

Страница 199: ...tantaneous recorder Capacity 5 starting informations instantaneous Time tag 1 millisecond Triggers Any selected protection alarm and threshold Data date hour origin any protection alarm length duratio...

Страница 200: ...ion Physical Link Connectors Data Rate Protocol RS485 Rear port Screened twister pair Screws or snap on 300 to 38400 baud programmable ModBus RTU Courier IEC60870 5 103 DNP3 0 RS232 Front port P120 P1...

Страница 201: ...ves is L I I K T t S 1 Where t Operation time K Factor see table I Value of measured current Is Value of the programmed threshold pick up value Factor see table L ANSI IEEE constant zero for IEC and R...

Страница 202: ...re the corresponding phase or earth time delay is reset NOTE There is an exception to this rule when the protection triggers In fact in this case the time delays tI and tIe are immediately reset The v...

Страница 203: ...s permanent When the reset time of the overcurrent relay is set to minimum the relay will be repeatedly reset and will not be able to trip until the fault becomes permanent By using the reset timer ho...

Страница 204: ...ves of the thermal overload time characteristic are given in Technical Data The mathematical formula applicable to MiCOM Relays is the following trip K K In Te Trip t Where t Trip Time to trip in seco...

Страница 205: ...following curves are given for indication only 12 3 IEC Curves IEC AREVA Curves TMS 0 025 0 001 0 01 0 1 1 10 1 10 100 MULTIPLES OF PICK UP SETTING Short time inverse AREVA Standard Inverse Very Inve...

Страница 206: ...hnical Data Page 26 40 MiCOM P120 P121 P122 P123 Short Time Inverse AREVA 0 001 0 01 0 1 1 10 1 10 100 MULTIPLES OF PICK UP SETTING TMS 0 025 TMS 0 2 TMS 0 5 TMS 1 TMS 1 25 B B C C D D E E A A TIME IN...

Страница 207: ...P12x EN TD A96 MiCOM P120 P121 P122 P123 Page 27 40 0 01 0 1 1 10 100 1 10 100 E TMS 0 025 D TMS 0 2 C TMS 0 5 B TMS 1 A TMS 1 25 MULTIPLES OF PICK UP SETTING TIME IN SECONDS STANDARD INVERSE IEC A B...

Страница 208: ...Technical Data Page 28 40 MiCOM P120 P121 P122 P123 0 001 0 01 1 10 100 1 10 100 E TMS 0 025 D TMS 0 2 C TMS 0 5 B TMS 1 A TMS 1 25 VERY INVERSE IEC TIME IN SECONDS MULTIPLES OF PICK UP SETTING A B C...

Страница 209: ...A96 MiCOM P120 P121 P122 P123 Page 29 40 EXTREMEMELY INVERSE IEC 0 001 0 01 0 1 1 10 100 1000 10000 1 10 100 E TMS 0 025 D TMS 0 2 C TMS 0 5 B TMS 1 A TMS 1 25 A B C D E TIME IN SECONDS MULTIPLES OF...

Страница 210: ...hnical Data Page 30 40 MiCOM P120 P121 P122 P123 0 1 1 100 1000 10000 1 10 100 E TMS 0 025 D TMS 0 2 C TMS 0 5 B TMS 1 A TMS 1 25 LONG TIME INVERSE AREVA A B C D E TIME IN SECONDS MULTIPLES OF PICK UP...

Страница 211: ...ical Data P12x EN TD A96 MiCOM P120 P121 P122 P123 Page 31 40 12 4 RI Curves RI CURVES A B C D E 0 1 1 10 100 1 10 100 E k 0 1 D k 1 C k 2 B k 5 A k 10 TIME IN SECONDS MULTIPLES OF PICK UP SETTING P00...

Страница 212: ...P123 12 5 IEEE ANSI CO Curves ANSI IEEE CO curves TMS RTMS 0 025 0 0001 0 001 0 01 0 1 1 10 100 0 01 0 1 1 10 100 MULTIPLES OF PICK UP SETTING Short Time Inverse CO2 Moderately Inverse Long Time Inver...

Страница 213: ...1 P122 P123 Page 33 40 SHORT TIME INVERSE CO2 0 0001 0 001 0 01 0 1 1 10 100 0 01 0 1 1 10 100 MULTIPLES OF PICK UP SETTING A B C D E A B C D E E TMS RTMS 0 025 D TMS RTMS 0 2 C TMS RTMS 0 5 B TMS RTM...

Страница 214: ...COM P120 P121 P122 P123 MODERATELY INVERSE ANSI IEEE 0 01 0 1 1 10 100 1000 0 01 0 1 1 10 100 MULTIPLES OF PICK UP SETTING A B C D E A B C D E E TMS RTMS 0 025 D TMS RTMS 0 2 C TMS RTMS 0 5 B TMS RTMS...

Страница 215: ...P121 P122 P123 Page 35 40 LONG TIME INVERSE CO8 0 001 0 01 0 1 1 10 100 0 01 0 1 1 10 100 MULTIPLES OF PICK UP SETTING E TMS RTMS 0 025 D TMS RTMS 0 2 C TMS RTMS 0 5 B TMS RTMS 1 A TMS RTMS 1 25 TIME...

Страница 216: ...MiCOM P120 P121 P122 P123 VERY INVERSE ANSI IEEE 0 01 0 1 1 10 100 1000 0 01 0 1 1 10 100 MUL TIPLES OF PICK UP SETTING E TMS RTMS 0 025 D TMS RTMS 0 2 C TMS RTMS 0 5 B TMS RTMS 1 A TMS RTMS 1 25 TIME...

Страница 217: ...P122 P123 Page 37 40 EXTREMELY INVERSE ANSI IEEE 0 001 0 01 0 1 1 10 100 1000 0 01 0 1 1 10 100 MULTIPLES OF PICK UP SETTING E TMS RTMS 0 025 D TMS RTMS 0 2 C TMS RTMS 0 5 B TMS RTMS 1 A TMS RTMS 1 25...

Страница 218: ...hnical Data Page 38 40 MiCOM P120 P121 P122 P123 12 6 Rectifier protection curve 0 1 1 100 1000 10000 1 1 6 10 100 TMS 1 RECTIFIER P122 P123 only TIME IN SECONDS MULTIPLES OF PICK UP SETTING t 45900 I...

Страница 219: ...MiCOM P120 P121 P122 P123 Page 39 40 12 7 RXIDG curve RXIDG Curves 0 1 2 3 4 5 6 7 1 3 5 6 8 5 11 13 5 16 18 5 21 23 5 26 28 5 31 33 5 36 38 5 I Is Tripping time in seconds K 1 K 0 9 K 0 8 K 0 7 K 0...

Страница 220: ...ad curves TRIPPING CURVE FUNCTION OF THE PREFAULT LOAD k 1 1 T e 10mn 0 1 1 10 100 1000 10000 1 10 MULTIPLES OF THERMAL THRESHOLD SETTING I A No prefault load thermal state 0 B Thermal state 30 C Ther...

Страница 221: ...Application Guide P12x EN AP A96 MiCOM P120 P121 P122 P123 APPLICATION GUIDE...

Страница 222: ......

Страница 223: ...ection 13 3 TRANSFORMER INRUSH CURRENT 14 3 1 TRANSFORMER INRUSH BLOCKING P122 and P123 only 14 4 BUSBAR PROTECTION ON RADIAL SYSTEMS 15 5 BLOCKING LOGIC FUNCTION BLOCKED OVERCURRENT PROTECTION 16 6 R...

Страница 224: ...IMERS P121 P122 P123 ONLY 38 16 SETTING GROUP SELECTION P122 P123 ONLY 39 17 MAINTENANCE MODE 41 18 SELECTIVE SCHEME LOGIC P122 P123 ONLY 42 19 LOGIC EQUATIONS P121 P122 P123 ONLY 43 20 NEGATIVE SEQUE...

Страница 225: ...Circuit Breaker Failure Protection mechanism 63 26 2 Typical settings 66 26 2 1 Breaker Fail Timer Settings 66 26 2 2 Breaker Fail Undercurrent Settings 66 27 TRIP CIRCUIT SUPERVISION P122 P123 ONLY 6...

Страница 226: ...P12x EN AP A96 Application Guide Page 4 80 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 227: ...nes most of faults are transient or semi permanent in nature In order to increase system availability multi shot autoreclose cycles are commonly used in conjunction with instantaneous tripping element...

Страница 228: ...industrial and distribution network applications as well as in high voltage and extremely high voltage protection applications They can operate in networks with neutral earthed by impedance by resona...

Страница 229: ...d load pickup X X Instantaneous start contact X X X X Latching output contacts 86 X X X X Setting groups 1 1 2 2 Circuit breaker failure detection 50BF X X Trip circuit supervision TCS X X Switch on t...

Страница 230: ...f the settings chosen for the phases The instantaneous thresholds are represented by the symbol I for the first threshold I and I for the second and third instantaneous thresholds Ie Ie and Ie for ear...

Страница 231: ...ent signal However with a high X R ratio it is recommended to use the sample base method As soon as a phase or earth threshold is running the instantaneous output associated with this threshold is act...

Страница 232: ...maximum 20ms at 50Hz For DMT curves a reset timer t Reset is associated with the first and second thresholds phase and earth elements 2 4 IDMT thresholds 2 4 1 Inverse time curves The first and secon...

Страница 233: ...urves tend towards infinite when the current approaches Is the minimum guaranteed value of the operating current for all the curves with the inverse time characteristic is 1 1Is with a tolerance of 0...

Страница 234: ...rth threshold only 2 5 1 Reset timer P122 P123 only For the first phase and earth overcurrent stages MiCOM P122 and P123 have a timer hold facility t Reset which can be set to a definite time value or...

Страница 235: ...Value of the measured current IS Value of the programmed threshold pick up value Coefficient see table T Reset Time Multiplier Rtms between 0 025 and 3 2 Type of curves Standard K factor factor Short...

Страница 236: ...vity of overcurrent thresholds need to be set below the prospective peak inrush current the inrush block function can be used to block the overcurrent earth fault and negative sequence overcurrent sta...

Страница 237: ...tion are grouped together and wired to the Blocking logic logic input of the relay protecting the incomer The blocking function is programmed to inhibit either the first or first two thresholds The th...

Страница 238: ...breaker fails to trip Thus for a fault downstream from relay C the start output from relay C will prevent relay B from operating and the start output of relay B will prevent relay A from operating Thu...

Страница 239: ...or REF application The results of the third threshold will be similar to one of the first and second threshold since all the thresholds are based on Fast Fourier Transformation NOTE For P122 and P123...

Страница 240: ...ility of the relay under external fault conditions This resistor will limit the spill current under Is Vs Is RST Is Current relay setting Vs Stability Voltage setting Note that the relay consumption h...

Страница 241: ...Transformer ratio Relay operating current IS Number of CT in parallel with the relay element n The inrush current of each CT Ie at the stability voltage Iop CTRatio Is n Ie Current setting should be...

Страница 242: ...2 for Vk Vs 16 6 4 Use of METROSIL non linear resistors Metrosils are used to limit the peak voltage developed by the current transformers under internal fault conditions to a value below the insulat...

Страница 243: ...rough the non linear resistor Metrosil With the sinusoidal voltage applied across the Metrosil the RMS current would be approximately 0 25 times the peak current This current value can be calculated a...

Страница 244: ...ernal fault current the Metrosil unit should limit the voltage to 1500V rms for 0 25 second At the higher relay settings it is not possible to limit the fault voltage to 1500V rms hence higher voltage...

Страница 245: ...ge without being damaged To give an idea they can generally withstand 150 of the load for 2 hours and 300 for 1 minute A typical application is shown on the diagram below A B C C B A N Rs Protection T...

Страница 246: ...ation time can be modified by adjusting the time multiplier setting TMS so that the time lies between limiting characteristic of the rectifier and the tolerated load area Typical settings for the TMS...

Страница 247: ...tI time delay at 60ms active threshold for the high phase faults 2nd threshold tI time delay selectively greater than for the third threshold i e 360ms The output contact associated with the 2nd thres...

Страница 248: ...her values than the ones set for the phase thresholds of the downstream relays the fault shall be cleared selectively by the relay of the faulty feeder selectivity between the relay of the incomer and...

Страница 249: ...set either as time constant or as time dependent The value of the time delay of I Ie is set to a value that is compatible with thresholds Z2 or Z3 2nd and 3rd distance protection zone Busbar Circuit B...

Страница 250: ...trip is an essential criteria to be considered when choosing this protection MiCOM P121 P122 or P123 relays are perfectly suited for this application The time delay of the first threshold tI is set to...

Страница 251: ...anced with heat dissipated by radiation etc Over temperature conditions therefore occur when currents in excess of rating are allowed to flow for a certain period of time It can be shown that temperat...

Страница 252: ...nding to the RMS value of the largest phase current I Full load current rating given by the national standard or by the supplier k Factor associated to the thermal state formula Initial thermal state...

Страница 253: ...he table shows in minutes for different cable rated voltages and conductor cross sectional areas CSA mm2 6 11 kV 22 kV 33 kV 66 kV 25 50 10 15 40 70 120 15 25 40 60 150 25 40 40 60 185 25 40 60 60 240...

Страница 254: ...ithout compromising protection performance during starting Note that any of the disabled overcurrent stages in the main relay menu will not appear in the Cold Load PU Menu The following table shows th...

Страница 255: ...ettings in this case must be chosen with regard to the motor starting characteristic As previously described the CLP logic includes the option of raising the settings of the first stage of the earth f...

Страница 256: ...clear the fault as fast as possible The SOTF acronym means Switch On To Fault The TOR acronym means Trip on Recloser Activation and setting of the SOTF TOR function can be done under the AUTOMATIC CTR...

Страница 257: ...nsidered a trip delay time that substitutes the trip timer of the threshold that has been crossed so that the time to trip is accelerated If a trip due to switch on to fault occurs during the reclaim...

Страница 258: ...ued by the protection elements time delay threshold crossing This is done to identify if the trip order has been issued by a remote command by the crossing of a time delay threshold or by the activati...

Страница 259: ...P RL 2 RL 3 P0573ENb Control trip Protection trip Control close AR close 1 2 3 4 5 6 7 8 Local trip Local close Switch REMOTE LOCAL DC V P123 REMOTE 1 2 closed 7 8 closed 3 4 open 5 6 open LOCAL 3 4 c...

Страница 260: ...e energised the associated timers start and when the set time has elapsed the associated output relays close refer to AUTOMAT CRTL OUTPUTS menu Time delays can be independently set from 0 ms to 200 s...

Страница 261: ...output relay Using a normally open contact this means that an open contact will indicate that the active group is Group 1 a close contact will indicate that the active group is Group 2 Change of setti...

Страница 262: ...ont panel the priority is given to the user that takes local control of the relay when entering a password Change of setting group done via a remote command is not allowed for as long as the password...

Страница 263: ...nce Mode YES When this menu is activated set to YES the Alarm led will start to flash and the alarm message MAINTENANCE MODE will be displayed In this case all the output contacts are blocked and no c...

Страница 264: ...some utilities than the blocked overcurrent arrangement A B C P0024ENa FIGURE 13 TYPICAL SCHEME LOGIC The SOL function temporarily increase the time delay settings of the second and third stages of p...

Страница 265: ...Output I tAUX 1 input1 1 tAUX 2 input2 5sec 10sec P0697ENa AUTOMAT CTRL Logic Equations Equation A Equation A 00 I Equation A 01 AND NOT tAux1 Equation A 02 OR tAux2 Equation A 03 OR Null Equation A...

Страница 266: ...T AND OR most to less preponderant Every equation has a rising temporisation from 0 s to 600 s with a step of 0 01 s Every equation has a falling temporisation from 0 s to 600 s with a step of 0 01 s...

Страница 267: ...lement may be used to provide time delayed back up protection for any uncleared asymmetrical faults Where fuses are used to protect motors on rotating machines a blown fuse produces a large amount of...

Страница 268: ...is function is usually set with a long time delay Care must be made to ensure that the time delay is set above the operating time of any other protection device at minimum fault level present on the s...

Страница 269: ...dition may be very close to or even inferior to the full load steady state unbalance generated by CT errors load unbalance etc As a consequence a negative sequence protection element would not work fo...

Страница 270: ...onditions to be sure that all single phase loads are taken into account When sensitive settings are used it is probable that the element will operate for any unbalance condition occurring on the syste...

Страница 271: ...On HV MV distribution networks the autoreclose function is used mainly for radial feeders where system stability problems do not generally arise Using the autoreclose bring the following advantages M...

Страница 272: ...in the isolation of the faulted section However for certain applications where the majority of the faults are likely to be transient it is not uncommon to allow more than one instantaneous trip before...

Страница 273: ...ose cycle the autoreclose function is totally disabled 22 2 2 Autoreclose menu The setting of the Autoreclose function is described in the following table The same settings apply for the Menu PROTECTI...

Страница 274: ...ead time the CB FLT input indicates that there is not enough energy availableduring the time tCFE a lockout occur and the CB remains open This function is disabled if not assigned under the PROTECTION...

Страница 275: ...el of the system Generally on medium voltage networks where the percentage of transient and non permanent faults is likely to be high a multi shot autoreclose device will increase the possibility for...

Страница 276: ...common to use two or three autoreclose shots However in some countries for specific applications the use of four shots is not uncommon The advantage of using four shots is that the final dead time ca...

Страница 277: ...tem depends on the minimum time delay imposed by the circuit breaker during a trip and reclose operation Since a circuit breaker is a mechanical device it has an inherent contact separation time This...

Страница 278: ...e spring For high speed autoreclose the reclaim time may be set longer than the spring charging time to ensure that there is sufficient energy in the circuit breaker to perform a trip close trip cycle...

Страница 279: ...arth faults caused by a broken overhead conductor in contact with dry ground or a wood fence are rarely transient faults and may be dangerous to people It is therefore common practice to block the aut...

Страница 280: ...itching operations The MiCOM P120 P121 P122 P123 relays incorporate a circuit breaker state monitoring giving an indication of the position of the circuit breaker This indication is available either o...

Страница 281: ...RECORDS CB Monitoring menu cells shown are counter values only This information is for reading only MENU TEXT CB Monitoring CB Opening Time Display the CB opening time Note 1 CB Closing Time Display t...

Страница 282: ...rtion of the life cycle cost of the switchgear Generally oil changes are performed at a fixed interval of circuit breaker fault operations However this may result in premature maintenance where fault...

Страница 283: ...hing a operations threshold This prevents further reclosure when the circuit breaker has not been maintained to the standard demanded by the switchgear manufacturer s maintenance instructions Certain...

Страница 284: ...xiliary contact of the CB status is connected to the relay A logic input should be energised via the 52a contact of the CB In this way a logic input 1 to 5 for P123 1 to 3 for P122 is allocated to the...

Страница 285: ...mer is initiated when a trip order is given to the output relay RL1 Note that the trip order can be issued either by a protection element or by a logic input Then the relay monitors the current signal...

Страница 286: ...g this digital input signal If the CB is not opened by an another protection relay once the tBF has elapsed the relay declares that the CB has failed The user can associate the digital input to the CB...

Страница 287: ...ass CTs which are built with air gap in their magnetic core Before the drop off of the t BF timer the relay has detected an opening of the CB pole thus no CB failure signal is given as it is required...

Страница 288: ...Timer Settings A typical timer setting used with a 2 cycle circuit breaker is around 150 ms 26 2 2 Breaker Fail Undercurrent Settings The phase undercurrent settings I must be set to a value that is...

Страница 289: ...Circ within the AUTOMAT CTRL Inputs menu Then this logic input is wired in the trip circuit according to one of the typical application diagrams shown in the following example When the function TC Su...

Страница 290: ...nput 2 6 P0038ENa FIGURE 22 TRIP COIL MONITORING Example 2 In this example both 52a and 52b auxiliary contacts are available the MiCOM P122 and P123 relays monitor the complete trip circuit when the C...

Страница 291: ...on of the R1 resistor value will take into account that a minimum current is flowing through the logic input This minimum current value is a function of the relay auxiliary voltage range Ua 1 Case of...

Страница 292: ...n minimum current value needed for the opto logic input to operate Rcoil Trip coil resistance value Relay auxiliary voltage range Ua 24 60 VDC ordering code P12xx00Axxxxx 48 250 VDC AC ordering code P...

Страница 293: ...onnected to the substation control system or via an opto input Any of the available opto inputs on the P12x relay can be selected for synchronization Pulsing this input will result in the real time cl...

Страница 294: ...sequence of events that occurred within the relay after a particular power system condition or switching sequence etc When the available space is exhausted the new fault automatically overwrites the...

Страница 295: ...lt automatically overwrites the oldest fault The user can view actual fault record under the RECORD Fault Record menu where he can select to display up to 25 stored records These records are fault fla...

Страница 296: ...d and displayed under the RECORDS Instantaneous menu The last five starting information with the duration of the information are available The following information is displayed under the RECORDS Faul...

Страница 297: ...amples per cycle Each disturbance record consists of analogue and digital channels Note that the relevant CT ratios for the analogue channels are also extracted to enable scaling to primary quantities...

Страница 298: ...the number of Num of Sub Periods periods The number of Sub Period Num of Sub Periods can be set under the RECORDS Rolling Demand Num of Sub Per menu Setting range from 1 to 24 Display of the first res...

Страница 299: ...e other way if this new value is lower than the previous value already stored then the previous value is stored This way the average peak vale will be refreshed each Sub Period There is no dedicated s...

Страница 300: ...11 ohms 34 1 Definite time IDMT overcurrent earth fault protection Time delayed Phase overcurrent elements VK Icp 2 RCT RL Rrp Time delayed Earth Fault overcurrent elements VK Icn 2 RCT 2RL Rrp Rrn 34...

Страница 301: ...or X R 40 and if 15In VK 48 In RCT 2RL for X R 40 15In If 40In and 40 X R 120 If 15In Where VK Required CT knee point voltage volts In Rated secondary current amps RCT Resistance of current transforme...

Страница 302: ...P12x EN AP A96 Application Guide Page 80 80 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 303: ...Communications P12x EN CT A96 MiCOM P120 P121 P122 P123 MODBUS DATABASE COURIER DATABASE IEC 60870 5 103 DNP 3 0 DATABASE MiCOM P120 P121 P122 P123 VERSION V11...

Страница 304: ......

Страница 305: ...Communications P12x EN CT A96 MiCOM P120 P121 P122 P123 MODBUS DATABASE MiCOM P120 P121 P122 P123 VERSION V11 A...

Страница 306: ......

Страница 307: ...MiCOM P120 P121 P122 AND P123 RELAY DATABASE ORGANISATION 7 3 1 Description of the application mapping 7 3 1 1 Settings 7 3 1 2 Disturbance records P122 P123 7 3 1 3 Event records P122 P123 8 3 1 4 Fa...

Страница 308: ...s 44 3 19 Pages 3Dh 45 4 DESCRIPTION OF THE MAPPING FORMAT MiCOM P122 AND P123 47 4 1 Disturbance record additional information 58 4 1 1 MODBUS request definition used for disturbance record 58 4 1 2...

Страница 309: ...scribes the characteristics of the MODBUS K Bus COURIER and IEC 60870 5 103 communication protocol of MiCOM P120 P121 P122 and P123 relays 1 2 Glossary Ir Is It currents measured on the concerned phas...

Страница 310: ...0 19200 38400 Transmission mode of the configured characters by operator dialog Mode 1 start 8 bits 1 stop total 10 bits 1 start 8 bits even parity 1 stop total 11 bits 1 start 8 bits odd parity 1 sto...

Страница 311: ...e received from MiCOM P120 P121 P122 and P123 relays Frame transmitted by the master query Slave number Function code Information CRC16 1 byte 1 byte n bytes 2 bytes 0 FFh 1 10h Slave number The slave...

Страница 312: ...good but the MiCOM relay can not process the query it sends an exception response Warning frame sent by the MiCOM relay response Slave number Function code Warning code CRC16 1 byte 1 byte 1 byte 2 by...

Страница 313: ...select the record number to be uploaded The answer following this request contain the following information 1 Numbers of samples pre and post time 2 Phase CT ratio 3 Earth CT ratio 4 Internal phase a...

Страница 314: ...event set the bit 13 of control word 400 h 3 1 4 Fault records P122 P123 Page 37h Page dedicated to upload fault record Used addresses 3700h FAULT 1 3701h FAULT 2 3718h FAULT 25 Page 3Eh Request to up...

Страница 315: ...ternal earth ratio F1 P122 P123 0009 General start info 0 1 1 F1 P120 to P123 000A to 000B Reserved P120 to P123 000C LED Status 0 255 F73 P120 to P123 000D Real Active Setting Group after taking into...

Страница 316: ...information I2 0 to FFFF 1 F16 P122 P123 0023 Output information broken conductor CB failure CB alarm 0 to FFFF 1 F38 P122 P123 0024 tI memorisation 0 to FFFF 1 F17 P122 P123 0025 Memorised flag for...

Страница 317: ...phase A 0 to 600 000 1 A 10 0 F18 P122 P123 003E Max RMS value phase B 0 to 600 000 1 A 10 0 F18 P122 P123 0040 Max RMS value phase C 0 to 600 000 1 A 10 0 F18 P122 P123 0042 Average RMS value Phase A...

Страница 318: ...ing Demand Average sliding time window RMS IA 0 to 600 000 1 A 10 0 F18 P122 P123 0063 Average sliding time window RMS IB 0 to 600 000 1 A 10 0 F18 P122 P123 0065 Average sliding time window RMS IC 0...

Страница 319: ...label L3 C T VTA F25 C P121 P122 P123 0108 Earth label N G E VTA F25 N P120 to P123 0109 Fault display 1 4 1 F26 1 P120 to P123 010A User reference characters 1 and 2 32 127 1 F10 AL P120 to P123 010B...

Страница 320: ...d P120 to P123 012E Fail safe and inversion relays 1 F60 0 P120 to P123 012F Rotation phase sequence 0 to 1 1 F51 0 P121 P122 P123 0130 Communication Speed 0 to 7 1 F4 6 19200 bds P120 to P123 0131 Pa...

Страница 321: ...ion Max I2 0 to 31 1 F14 0 P122 P123 014B to 014F Reserved P120 to P123 0150 LEDs allocation Led 5 1 F19 4 P120 to P123 0151 Led 6 1 F19 16 P120 to P123 0152 Led 7 1 F19 32 P120 to P123 0153 Led 8 1 F...

Страница 322: ...0 P122 P123 0169 Thermal overload alarm 0 31 1 F14 0 P122 P123 016A Thermal overload trip 0 31 1 F14 0 P122 P123 016B CB close 0 31 1 F14 0 P121 P122 P123 016C tAUX1 0 31 1 F14 0 P120 to P123 016D tA...

Страница 323: ...123 0184 Broken conductor detection 0 1 1 F24 0 P122 P123 0185 tBC 0 to 14400 1 F1 0 P122 P123 0186 Cold load start 0 1 1 F24 0 P122 P123 0187 Cold load start thresholds 0 to 255 1 F33 0 P122 P123 018...

Страница 324: ...123 019F Tripping time 10 to 500 5 1 100 s F1 10 P122 P123 01A0 Closing time 10 to 500 5 1 100 s F1 10 P122 P123 01A1 Closing time threshold validation 0 1 1 F24 0 P122 P123 01A2 Trip circuit supervis...

Страница 325: ...0 1 1 100s F1 0 P123 01B5 to 01BF Reserved P120 to P123 01C0 to 01F5 Reserved P123 01F6 Remote trip 0 31 1 F14 0 P123 01F7 Remote close 0 31 1 F14 0 P123 01F8 SOFT function 0 1 1 F52 0 P123 01F9 SOFT...

Страница 326: ...lue 25 to 3200 1 1 1000 F1 25 P122 P123 0209 I tRESET value 0 to 60000 1 1 100 s F1 4 P122 P123 020A to 020F Reserved 0 P120 to P123 0210 I 0 1 1 F24 0 P121 P122 P123 0211 I Threshold 50 to 4000 5 In...

Страница 327: ...00 to 10000 5 1 1000 F1 100 P120 to P123 0236 tIE value 0 to 15000 1 1 100 s F1 4 P120 to P123 0237 IE reset type 0 1 1 F27 0 P122 P123 0238 IE RTMS value 25 to 3200 1 1 1000 F1 25 P122 P123 0239 IE t...

Страница 328: ...IE value 0 to 15000 1 1 100 s F1 1 P120 to P123 0253 Ith 0 1 1 F24 0 P122 P123 0254 Ith Threshold 10 to 320 5 1 100 F1 8 P122 P123 0255 Ith k value 100 to 150 1 1 100 F1 105 P122 P123 0256 Ith trip th...

Страница 329: ...to 0276 Reserved P120 to P123 0277 Dead time 1 0 to 30000 1 1 100 s F1 1 P123 0278 Dead time 2 0 to 30000 1 1 100 s F1 1 P123 0279 027A Dead time 3 0 to 60000 1 1 100 s F18 1 P123 027B 027C Dead time...

Страница 330: ...04 operand 0 38 1 F72 0 050A Equation A 05 operator 0 3 1 F71 0 050B Equation A 05 operand 0 38 1 F72 0 050C Equation A 06 operator 0 3 1 F71 0 050D Equation A 06 operand 0 38 1 F72 0 050E Equation A...

Страница 331: ...and 0 38 1 F72 0 0544 Equation C 02 operator 0 3 1 F71 0 0545 Equation C 02 operand 0 38 1 F72 0 0546 Equation C 03 operator 0 3 1 F71 0 0547 Equation C 03 operand 0 38 1 F72 0 0548 Equation C 04 oper...

Страница 332: ...and 0 38 1 F72 0 0584 Equation E 02 operator 0 3 1 F71 0 0585 Equation E 02 operand 0 38 1 F72 0 0586 Equation E 03 operator 0 3 1 F71 0 0587 Equation E 03 operand 0 38 1 F72 0 0588 Equation E 04 oper...

Страница 333: ...and 0 38 1 F72 0 05C4 Equation G 02 operator 0 3 1 F71 0 05C5 Equation G 02 operand 0 38 1 F72 0 05C6 Equation G 03 operator 0 3 1 F71 0 05C7 Equation G 03 operand 0 38 1 F72 0 05C8 Equation G 04 oper...

Страница 334: ...72 0 05F0 Equation H 08 operator 0 3 1 F71 0 05F1 Equation H 08 operand 0 38 1 F72 0 05F2 Equation H 09 operator 0 3 1 F71 0 05F3 Equation H 09 operand 0 38 1 F72 0 05F4 Equation H 10 operator 0 3 1 F...

Страница 335: ...on Inrush harmonic 2 ratio 100 350 1 0 1 F1 200 P122 P123 0633 Automation tInrush_reset 0 200 10 10mS F1 0 P122 P123 0634 to 06FF free 0634 to 063F Free for automation 0 0640 Equation tempos Equation...

Страница 336: ...falling tempo 0 60000 1 10 ms F1 0 0650 Equation A assignation to outputs 1 F14 0 0651 Equation B assignation to outputs 1 F14 0 0652 Equation C assignation to outputs 1 F14 0 0653 Equation D assigna...

Страница 337: ...t is Timer Address hex Nb bytes Mask hex Values range Unit Year 0800 2 FFFF 1994 2093 Years Month 1 Hi FF 1 12 Months Day 0801 1 Lo FF 1 31 Days Hour 1 Hi FF 0 23 Hours Minute 0802 1 Lo FF 0 59 Minute...

Страница 338: ...o 025Fh 0300h to 035Fh PAGE 04h PAGE 05h 0400h to 0403h 0500h to 052Ah P122 P123 PAGE 01h PAGE 02h PAGE 03h 0100h to 01BFh 0200h to 028Ah 0300h to 038Ah PAGE 04h PAGE 05h 0400h to 0403h 0500h to 052Ch...

Страница 339: ...g of 1 bit function 05 WARNING THE BITS NUMBER MUST NOT BE HIGHER THAN 16 P121 P122 P123 PAGE 04h 4000h to 4002h Description of accessible addresses in writing of n bits function 15 WARNING THE BITS N...

Страница 340: ...5FAh 250 disturbance data words 1600h to 16FAh 250 disturbance data words 1700h to 17FAh 250 disturbance data words 1800h to 18FAh 250 disturbance data words 1900h to 19FAh 250 disturbance data words...

Страница 341: ...ratio mapping address 0008 3277 2 0 002 to 1 Ion range Line earth current value primary value earth sampled value e g word 10 or 14 earth primary CT earth internal CT ratio mapping address 0008 32700...

Страница 342: ...cond n 6 Disturbance record starting condition 1 tripping command RL1 2 instantaneous 3 remote command 4 logic input n 7 Frequency at the post time beginning n 8 0 Optional n 9 0 Optional 3 14 Page 35...

Страница 343: ...13 IE F16 018h 023 14 IE F16 019h 023 15 Thermal overload alarm F37 020h 023 16 Thermal overload threshold F37 020h 023 17 tI F17 014h 023 18 tI F17 015h 023 19 tI F17 016h 023 20 tIE F16 017h 023 21...

Страница 344: ...Front panel single alarm acknowl 52 Front panel all alarms acknowledge 53 Remote single alarm acknowledge 54 Remote all alarms acknowledge 55 Major material alarm F45 00Fh 022 56 Minor material alarm...

Страница 345: ...F16 018h 025 87 t Reset I2 F16 022h 025 88 TRIP Breaker Failure F13 013h 021 89 t BF Ext Breaker Failure F38 023h 025 90 Manual Close input F20 bis 02Ah 020 91 t SOTF F54 070h 025 92 TRIP t SOTF F13...

Страница 346: ...tEquation G TRIP F13 114 tEquation H TRIP F13 NOTA The double arrow means the event is generated on event occurrence and on event disappearance On event occurrence the corresponding bit of the associa...

Страница 347: ...ault date number of seconds since 01 01 94 PRIVATE FORMAT 4 5 Fault date milli seconds IEC FORMAT 2 to 5 Fault date see format of time synchronisation address 0800h 6 Fault date season 0 winter 1 summ...

Страница 348: ...7 tIE trip 08 tIE trip 09 tI trip 10 Broken conductor trip 11 t Aux 1 trip 12 t Aux 2 trip 13 tI2 trip 14 tI2 trip 15 t Aux 3 trip 16 t Aux 4 trip 17 Breaker Failure Trip 18 SOTF Word n 10 Fault value...

Страница 349: ...mary value earth sampled value e g word 10 or 14 earth primary CT ratio earth internal CT ratio mapping address 0008 32700 3 17 Page 3Eh Most older Fault record value data Access in word reading funct...

Страница 350: ...6 Earth primary CT ratio Word n 7 Earth secondary CT ratio Word n 8 Phase internal CT ratio Word n 9 Earth internal CT ratio Word n 10 Mapping last page number Word n 11 Number of words in the mapping...

Страница 351: ...ious disturbance record date millisecond Word n 14 Disturbance record starting origin 1 trip relay RL1 2 instantaneous threshold 3 remote command 4 logic input Word n 15 Acknowledge Word n 16 Number o...

Страница 352: ...ASE Page 46 248 MiCOM P120 P121 P122 P123 Words n 33 34 Previous disturbance record date millisecond Word n 35 Disturbance record starting origin 1 trip relay RL1 2 instantaneous threshold 3 remote co...

Страница 353: ...EC Rectifier curve F3 Unsigned integer RXIDG curve type 0 curve 1 K 0 3 1 curve 2 K 0 4 2 curve 3 K 0 5 3 curve 4 K 0 6 4 curve 5 K 0 7 5 curve 6 K 0 8 6 curve 7 K 0 9 7 curve 8 K 1 0 F4 Unsigned inte...

Страница 354: ...ree F7 Unsigned integer Latching configuration bit 0 SOFT bit 1 to 15 Reserved F8 Unsigned integer Latching configuration bit 0 I latching bit 1 I bit 2 I bit 3 IE bit 4 IE bit 5 IE bit 6 I bit 7 tIth...

Страница 355: ...it 9 Maintenance mode bit 10 Recloser counter reset bit 11 Recloser reset bit 12 Local manual acknowledge bit 13 Oldest event acknowledge bit 14 Oldest fault acknowledge bit 15 Hardware RAM alarm ackn...

Страница 356: ...1 allocation selective scheme logic 2 bit 12 allocation change of setting group bit 13 allocation recloser locked bit 14 allocation thermal state reset bit 15 allocation trip circuit supervision F15bi...

Страница 357: ...Broken conductor trip bit 15 CB failure F19 Unsigned integer LEDs allocation 2 3 bit 0 Logic input 1 bit 1 Logic input 2 bit 2 Logic input 3 bit 3 Logic input 4 bit 4 Logic input 5 bit 5 Recloser run...

Страница 358: ...External 4 bit 5 Manual Close SOFT TOR bit 6 Local Mode bit 7 Synchronisation F21 Unsigned integer software version 10 Version 1 A 11 Version 1 B 20 Version 2 A F22 Unsigned integer internal logic da...

Страница 359: ...esholds bit 0 tI bit 1 tI bit 2 tI bit 3 tIE bit 4 tIE bit 5 tIE bit 6 Thermal overload trip bit 7 tI2 bit 8 tI2 bit 9 to 15 reserved F34 Reserved F35 0 No disturbance record uploaded 1 Disturbance re...

Страница 360: ...rd in maintenance mode bit 0 RL1 trip bit 1 RL2 bit 2 RL3 bit 3 RL0 watch dog bit 4 RL4 bit 5 RL5 bit 6 RL6 bit 7 RL7 bit 8 RL8 F40 Unsigned integer selective scheme logic configuration bit 0 tI bit 1...

Страница 361: ...Rolling Demands Data average avlues and timers bit 5 Reset of maximum values of the averages in sub period bit 6 LEDs reset bit 7 Internal reset of non latched tripping LED bit 8 communication Order 1...

Страница 362: ...ay normally de energized bit x 1 relay normally energized bit 0 Fail safe logic output number RL1 tripping bit 1 Fail safe logic output number RL2 bit 2 Inversion logic output number RL3 bit 3 Inversi...

Страница 363: ...Ie 12 Tripping Ie 13 Start I2 14 Tripping I2 15 Start I2 16 Tripping I2 17 Start I2 18 Tripping I2 19 Thermal alarm Ith 20 Thermal tripping Ith 21 Start I 22 Tripping I 23 Tripping BRK 24 Tripping 79...

Страница 364: ...de EVT_NOK OF No record available NOTA If there is less than 5 records available the answer will contains zero in the non used words 4 1 3 Service requests This request must be send before uploading t...

Страница 365: ...t record acknowledgement on event retrieval a Automatic event record acknowledgement on event retrieval The bit12 of the remote order frame format F9 mapping address 0400h shall be set to 0 On event r...

Страница 366: ...e bit12 of the remote order frame format F9 mapping address 0400h shall be set to 0 On fault retrieval this fault record is acknowledged b Non automatic fault record acknowledgement on fault retrieval...

Страница 367: ...Communications P12x EN CT A96 MiCOM P120 P121 P122 P123 COURIER DATABASE MiCOM P120 P121 P122 P123 VERSION V11 A...

Страница 368: ......

Страница 369: ...nit status word 5 1 4 5 Control status word 5 1 4 6 Logic input status word 5 1 4 7 Output relay status word 5 1 4 8 Control information 6 1 4 9 Protection Indication 6 1 4 10 Measurement control 8 1...

Страница 370: ...P12x EN CT A96 Communications COURIER DATABASE Page 2 248 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 371: ...facility and his user friendliness 1 1 1 K Bus transmission layer The communication port is supported on the reception levels and the voltage transmission RS485 with galvanic isolation assured by a t...

Страница 372: ...for each change 1 4 Systems integration data 1 4 1 Address of the relay The relays can have any address between 1 and 254 included The address 255 corresponds to the global address to which all relay...

Страница 373: ...ion of the unit elements checked through the relay This functionality is not supported on MiCOM P120 P121 P122 and P123 relays 1 4 5 Control status word The Control status word is located in the cell...

Страница 374: ...t 9 Default settings Bit 10 to 15 Reserved 1 4 9 Protection Indication The protection indications gives the status of different protection elements in the relay The fault indications are generated wit...

Страница 375: ...Trip operation number 8 SA 2n 9 Trip circuit Supervision 10 Close operating time 11 Successful autoreclose 12 Locked autorecloser 13 Autorecloser configuration fail 14 I2 15 tI2 The following table pr...

Страница 376: ...es received with an error detection The principal unit can be re initialised in order to resent an order as often as wanted if he is not receiving any response or if he receives a response with an err...

Страница 377: ...If all events have been extracted then the event bit will reset if there are more events still to be extracted the next event can be accessed using the Send Event command as before 1 5 2 Event types...

Страница 378: ...w fault occurs 1 6 Disturbance record extraction P120 P122 P123 only The stored disturbance records within the relay are accessible via the Courier interface Select Record Number Row 01 This cell can...

Страница 379: ...123 13 IE 0023 P120 P122 P123 14 IE 0023 P120 P122 P123 15 TH ALARM 0023 P122 P123 16 TH OVERLOAD 0023 P122 P123 17 tI 0023 P122 P123 18 tI 0023 P122 P123 19 tI 0023 P122 P123 20 tIE 0023 P120 P122 P1...

Страница 380: ...FRONT 0 P120 P122 P123 52 ACK ALAR FRONT 0 P120 P122 P123 53 ACK 1 ALARM COM 0 P120 P122 P123 54 ACK ALAR COM 0 P120 P122 P123 55 Hard Maj Alarm 0022 P120 P122 P123 56 Hard min Alarm 0022 P120 P122 P...

Страница 381: ...TF 0021 P123 93 LOCAL MODE 0020 P123 94 Reserved 95 LOCKED AUTORECLOSER 0024 P123 96 AUTORECLOS IN PROGRESS 0025 P123 97 TIME SYNCHRO P122 P123 98 INRUSH BLOCKING 00XX P122 P123 99 t Equation A 0026 P...

Страница 382: ...e and another is generated on event disappearance When the cell reference is equal to zero only the event on edging edge is generated Twelve bits are available in the string of characters to describe...

Страница 383: ...escription ASCII Text 6 bytes P120 Setting 32 127 1 05 Plant Reference ASCII Text 4 bytes Pref Setting 32 127 1 06 Model Number ASCII Text 16 bytes Model Number Data 07 Firmware Number ASCII Text 16 b...

Страница 384: ...12 1F Unused reserved 20 Logic Input Status Binary flag 3 bits 0 log input 1 1 log input 2 Data 21 Relay Output Status Binary flag 5 bits 0 relay 1 trip 1 relay 2 2 relay 3 3 relay 4 4 watchdog relay...

Страница 385: ...VIEW RECORDS 01 Record number Unsigned Integer 2 bytes 5 Setting 1 5 1 02 Occur date Unsigned Integer 2 bytes 03 Active set group Unsigned Integer 2 bytes 04 Phase in fault ASCII Text 05 Fault Id ASCI...

Страница 386: ...es 2102 1 Setting 0 3 1 05 Curve Type I Indexed String 0 1 2 3 4 5 6 7 8 9 10 STI CEI SI CEI VI CEI EI CEI LTI CEI STI CO2 MI ANSI LTI CO8 VI ANSI EI ANSI RC CEI 2104 1 Setting 0 10 1 07 TMS I Courier...

Страница 387: ...s 2121 1 Setting 0 150 0 0 01 60 00 AUTOMATISM 01 Trip Configuration Binary 16 bits 0 t I 1 t I 2 t I 6 to 15 reserved Setting 0 65535 1 02 Latched Configuration Binary 16 bits 0 Latch I 1 Latch I 2...

Страница 388: ...GENERAL TRIP Binary 3 bits 000 Setting 0 7 1 02 I Binary 3 bits 000 Setting 0 7 1 03 tI Binary 3 bits 000 Setting 0 7 1 04 I Binary 3 bits 000 Setting 0 7 1 05 t I Binary 3 bits 000 Setting 0 7 1 06...

Страница 389: ...2 Stopped Trigerred Running Setting 1 2 1 02 Recorder Source Indexed String 0 Samples Data 20 Pretemps Courier floating point number 0 1 secondes Setting 0 1 3 0 0 1 21 Postemps Courier floating point...

Страница 390: ...2 Time Base Courier floating point number Data 13 NOT IMPLEMENTED reserved 14 Upload Timer Repeated group of Integers Data 15 1F NOT IMPLEMENTED reserved 20 Upload Channel 0 Repeated group of Integers...

Страница 391: ...n Magnitude Courier floating point number 12 34 A Data BF 00 COMM SYSTEM DATA 01 Dist Record Cntrl Ref Menu Cell 2 0x7000 Data 02 Dist Record Extract Ref Menu Cell 2 0x8000 Data 03 Setting Transfert S...

Страница 392: ...04 Description ASCII Text 6 bytes P121 Setting 32 127 1 05 Plant Reference ASCII Text 4 bytes Pref Setting 32 127 1 06 Model Number ASCII Text 16 bytes Model Number Data 07 Firmware Number ASCII Text...

Страница 393: ...re Reference ASCII Text 16 characters Data 12 1F Unused reserved 20 Logic Input Status Binary flag 3 bits 0 log input 1 1 log input 2 2 log input 3 Data 21 Relay Output Status Binary flag 5 bits 0 rel...

Страница 394: ...Pseudo Logic Input Status group 2 Binary flag 3 bits 0 Reserved 1 t Aux 1 2 t Aux 2 Data 26 Pseudo Logic Input Status group 4 Binary flag 8 bits 0 t Equation A 1 t Equation B 2 t Equation C 3 t Equat...

Страница 395: ...flag 4 bits 0 relay 1 trip 1 relay 2 2 relay 3 3 relay 4 Setting 0 15 1 0D 00 GENERAL SETTING 01 Phase rotation sense Indexed string 0 Direct A B C 1 Inverse A B C Setting 0 A B C 1 A B C 0E 00 CT RA...

Страница 396: ...CEI VI CEI EI CEI LTI CEI STI CO2 MI ANSI LTI CO8 VI ANSI EI ANSI RC CEI 2004 1 Setting 0 10 1 06 TMS I Courier floating point number 0 025 2004 1 Setting 0 025 1 5 0 001 07 K I Courier floating poin...

Страница 397: ...6 K I Courier floating point number 0 1 2013 2 Setting 0 1 10 0 0 005 17 Tempo I Courier floating point number 0 01 s 2013 0 Setting 0 150 0 01 1B 1F Reserved 20 Stage 3 Overcurrent Sub Heading 21 Max...

Страница 398: ...LTI CO8 VI ANSI EI ANSI RC CEI 2104 1 Setting 0 10 1 07 TMS IE Courier floating point number 0 025 2104 1 Setting 0 025 1 5 0 001 08 K IE Courier floating point number 0 1 2104 2 Setting 0 1 10 0 0 00...

Страница 399: ...Setting 0 10 1 16 TMS IE Courier floating point number 0 025 2113 1 Setting 0 025 1 5 0 001 17 K IE Courier floating point number 0 1 2113 2 Setting 0 1 10 0 0 005 18 Tempo IE Courier floating point n...

Страница 400: ...rved 7 reserved 8 reserved 9 t Aux1 10 t Aux2 Setting 0 2047 1 02 Latched Configuration Binary 11 bits 0 Latch I 1 Latch I 2 Latch I 3 Latch IE 4 Latch IE 5 Latch IE 6 reserved 7 reserved 8 reserved 9...

Страница 401: ...Equation F 8 Trip Equation G 9 Trip Equation H Setting 0 4095 1 61 00 TS SETTINGS 06 Timer aux 1 Courier floating point number 0 Setting 0 200 0 0 01 07 Timer aux 2 Courier floating point number 0 Se...

Страница 402: ...bits 000 Setting 0 7 1 09 t IE Binary 3 bits 000 Setting 0 7 1 0A IE Binary 3 bits 000 Setting 0 7 1 0B t IE Binary 3 bits 000 Setting 0 7 1 0C IE Binary 3 bits 000 Setting 0 7 1 0D t IE Binary 3 bit...

Страница 403: ...Setting 0 7 1 35 t Equation F Binary 3 bits 000 Setting 0 7 1 36 t Equation G Binary 3 bits 000 Setting 0 7 1 37 t Equation H Binary 3 bits 000 Setting 0 7 1 63 00 LEDS SETTINGS 01 Led 5 1 3 Binary 1...

Страница 404: ...16 bits 0 I 1 t I 2 I 3 t I 4 I 5 t I 6 IE 7 t IE 8 IE 9 t IE 10 IE 11 t IE 12 to 15 Reserved Setting 0 65535 1 04 Led 8 1 3 Binary 16 bits 0 I 1 t I 2 I 3 t I 4 I 5 t I 6 IE 7 t IE 8 IE 9 t IE 10 IE...

Страница 405: ...0 0 Input 1 1 Input 2 2 Reserved 3 Reserved 4 Reserved 5 Reserved 6 Reserved 7 t Aux1 8 t Aux2 Setting 0 511 1 07 Led 7 2 3 Binary 9 bits 0 0 Input 1 1 Input 2 2 Reserved 3 Reserved 4 Reserved 5 Rese...

Страница 406: ...G 7 Equation H Setting 0 255 1 0A Led 6 3 3 Binary 8 bits 0 0 Equation A 1 Equation B 2 Equation C 3 Equation D 4 Equation E 5 Equation F 6 Equation G 7 Equation H Setting 0 255 1 0B Led 7 3 3 Binary...

Страница 407: ...Alarms tAux Binary 2 bits 0 0 Alarm tAux1 1 Alarm tAux2 Setting 0 3 1 6C 00 BOOLEAN EQUATIONS 1 2 10 EQUATION A 11 Operator 00 Indexed String 0 1 Space NOT Setting 0 1 1 12 Operand 00 Indexed String 0...

Страница 408: ...tep 14 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie t Aux1 t Aux2 Setting 0 26 1 15 Operator 02 Indexed String 0 1 2 3 OR OR NOT AND AND...

Страница 409: ...efault Depend Cell Type Min Max Step 17 Operator 03 Indexed String 0 1 2 3 OR OR NOT AND AND NOT Setting 0 3 1 18 Operand 03 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie...

Страница 410: ...tep 1A Operand 04 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie t Aux1 t Aux2 Setting 0 26 1 1B Operator 05 Indexed String 0 1 2 3 OR OR NOT AND AND...

Страница 411: ...efault Depend Cell Type Min Max Step 1D Operator 06 Indexed String 0 1 2 3 OR OR NOT AND AND NOT Setting 0 3 1 1E Operand 06 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie...

Страница 412: ...tep 20 Operand 07 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie t Aux1 t Aux2 Setting 0 26 1 21 Operator 08 Indexed String 0 1 2 3 OR OR NOT AND AND...

Страница 413: ...efault Depend Cell Type Min Max Step 23 Operator 09 Indexed String 0 1 2 3 OR OR NOT AND AND NOT Setting 0 3 1 24 Operand 09 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie...

Страница 414: ...tep 26 Operand 10 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie t Aux1 t Aux2 Setting 0 26 1 27 Operator 11 Indexed String 0 1 2 3 OR OR NOT AND AND...

Страница 415: ...efault Depend Cell Type Min Max Step 29 Operator 12 Indexed String 0 1 2 3 OR OR NOT AND AND NOT Setting 0 3 1 2A Operand 12 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie...

Страница 416: ...tep 2C Operand 13 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie t Aux1 t Aux2 Setting 0 26 1 2D Operator 14 Indexed String 0 1 2 3 OR OR NOT AND AND...

Страница 417: ...Row Menu Text Data Type Ind Values default Depend Cell Type Min Max Step 2F Operator 15 Indexed String 0 1 2 3 OR OR NOT AND AND NOT Setting 0 3 1 30 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10...

Страница 418: ...efault Depend Cell Type Min Max Step 6C 40 EQUATION B 41 Operator 00 Indexed String 0 1 Space NOT Setting 0 1 1 42 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I I...

Страница 419: ...tep 60 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie t Aux1 t Aux2 Setting 0 26 1 6C 70 EQUATION C 71 Operator 00 Indexed String 0 1 Space...

Страница 420: ...efault Depend Cell Type Min Max Step 73 Operator 01 Indexed String 0 1 2 3 OR OR NOT AND AND NOT Setting 0 3 1 90 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie...

Страница 421: ...tep A2 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie t Aux1 t Aux2 Setting 0 26 1 A3 Operator 01 Indexed String 0 1 2 3 OR OR NOT AND AND...

Страница 422: ...Cell Type Min Max Step 6D 00 BOOLEAN EQUATIONS 2 2 10 EQUATION E 11 Operator 00 Indexed String 0 1 Space NOT Setting 0 1 1 12 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I...

Страница 423: ...tep 30 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie t Aux1 t Aux2 Setting 0 26 1 6E 40 EQUATION F 41 Operator 00 Indexed String 0 1 Space...

Страница 424: ...Row Menu Text Data Type Ind Values default Depend Cell Type Min Max Step 43 Operator 01 Indexed String 0 1 2 3 OR OR NOT AND AND NOT Setting 0 3 1 60 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10...

Страница 425: ...efault Depend Cell Type Min Max Step 6E 70 EQUATION G 71 Operator 00 Indexed String 0 1 Space NOT Setting 0 1 1 72 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I I...

Страница 426: ...tep 90 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie t Aux1 t Aux2 Setting 0 26 1 6E A0 EQUATION H A1 Operator 00 Indexed String 0 1 Space...

Страница 427: ...Row Menu Text Data Type Ind Values default Depend Cell Type Min Max Step A3 Operator 01 Indexed String 0 1 2 3 OR OR NOT AND AND NOT Setting 0 3 1 C0 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10...

Страница 428: ...C operation delay Courier floating point number 0 Setting 0 600 0 0 01 s 06 Equation C reset delay Courier floating point number 0 Setting 0 600 0 0 01 s 07 Equation D operation delay Courier floating...

Страница 429: ...elay Courier floating point number 0 Setting 0 600 0 0 01 s 10 Equation H reset delay Courier floating point number 0 Setting 0 600 0 0 01 s BF 00 COMM SYSTEM DATA 01 NOT IMPLEMENTED Data 02 NOT IMPLE...

Страница 430: ...h Setting 0 3 1 02 Password ASCII Password 4 bytes AAAA Setting 32 127 1 03 Fnlinks NOT IMPLEMENTED 04 Description ASCII Text 6 bytes P123 Setting 32 127 1 05 Plant Reference ASCII Text 4 bytes Pref S...

Страница 431: ...12 1F Unused reserved 20 Logic Input Status Binary flag 5 bits 3 bits 0 log input 1 1 log input 2 2 log input 3 3 log input 4 4 log input 5 Data 21 Relay Output Status Binary flag 9 bits 7 bits 0 rela...

Страница 432: ...I 3 IE 4 IE 5 IE 6 t I 7 t I 8 t I 9 t IE 10 t IE 11 t IE 12 Thermal Alarm 13 Therm Overload 14 t I 15 I Data 24 Pseudo Logic Input Status group 2 Binary flag 16 bits 0 Broken Conductor 1 t Aux 1 2 t...

Страница 433: ...us group 3 Binary flag 16 bits 0 t Aux 3 1 t Aux 4 2 t Reset I 3 t Reset I 4 t Reset IE 5 t Reset IE 6 t Reset I2 7 t BF 8 t SOTF 9 Final Trip 10 Autoreclos in progress 11 15 reserved Data 26 Pseudo L...

Страница 434: ...State Reset 7 RMS aver max Reset 8 Dist Rec Trig 9 Maintenance Start 10 Recloser timer Reset 11 Recloser Reset 12 Reserved 13 Reserved 14 Reserved 15 SRAM def ack Setting 0 65535 1 02 Remote control...

Страница 435: ...igned Integer 2 bytes 5 Setting 1 5 1 02 Occur date Unsigned Integer 2 bytes 03 Active set group Unsigned Integer 2 bytes 04 Phase in fault ASCII Text 05 Fault Id ASCII Text 06 Magnitude Courier float...

Страница 436: ...er floating point number Data 04 I0 RMS Courier floating point number Data 05 Idirect Courier floating point number Data 06 IINV Courier floating point number Data 07 Ratio Idir Iinv Courier floating...

Страница 437: ...t number Data 11 IN Fn Rst Courier floating point number Data 20 RST Sub period average Peaks 21 IA RMS Sub period average Peak Courier floating point number Data 22 IB RMS Sub period average Peak Cou...

Страница 438: ...CYCLE 3 NUMBER Unsigned Integer 2 bytes Data 05 CYCLE 4 NUMBER Unsigned Integer 2 bytes Data 06 DEFINITIVE TRIP NUMBER Unsigned Integer 2 bytes Data 07 RECLOSE ORDER NUMBER Unsigned Integer 2 bytes D...

Страница 439: ...Setting 1 255 1 0D 00 GENERAL SETTING 01 Phase Rotation sense Indexed String 0 Direct A B C 1 Inverse A C B Setting 0 A B C 1 A C B 0E 00 CT RATIOS 01 Phase CT Primary Unsigned Integer 2 bytes 1000 S...

Страница 440: ...reshold I Courier floating point number 0 1 In 2002 1 Setting 0 1 25 0 0 1 04 Temporisation Type I Indexed String 0 1 2 0 definite time 1 inverse time 2 RI curve 2002 1 Setting 0 2 1 05 Curve type I I...

Страница 441: ...or 2004 0 or 2004 2 or 2004 1 2005 5 2005 9 Setting 0 600 0 0 01 0C 0F Reserved 10 Stage 2 Overcurrent Sub Heading 11 Max I Binary 1 bit 0 Disabled Enabled Setting 0 1 1 12 Threshold I Courier floatin...

Страница 442: ...erse time 2013 1 2014 5 2014 9 Setting 0 1 19 RTMS I Courier floating point number 0 025 2018 1 Setting 0 025 3 2 0 001 1A T RESET I Courier floating point number 0 04 2018 0 or 2013 0 or 2013 2 or 20...

Страница 443: ...En if great sensitivity 2102 1 Setting 0 01 2 0 0 005 or 0 1 25 0 0 01 if normal sensitivity or 0 002 1 0 0 001 if great sensitivity 04 Tempo Type IE Indexed String 0 1 2 3 0 definite time 1 inverse t...

Страница 444: ...5 5 2105 9 Setting 0 1 0B RTMS IE Courier floating point number 0 025 210A 1 Setting 0 025 3 2 0 001 0C T RESET IE Courier floating point number 0 04 210A 0 or 2104 0 or 2104 2 or 2104 3 or 2104 1 210...

Страница 445: ...EI VI CEI EI CEI LTI CEI STI CO2 MI ANSI LTI CO8 VI ANSI EI ANSI RC CEI 2113 1 Setting 0 10 1 15 Curve Type 2 RXIDG IE Indexed String 0 1 2 3 4 5 6 7 K 0 3 K 0 4 K 0 5 K 0 6 K 0 7 K 0 8 K 0 9 K 1 0 21...

Страница 446: ...ing point number 0 01 IEn or 0 50 IEn if normal sensitivity or 0 002 IEn if great sensitivity 2121 1 Setting 0 01 8 0 0 005 or 0 50 40 0 0 01 if normal sensitivity or 0 002 1 0 0 001 if great sensitiv...

Страница 447: ...r 0 01 s 2301 1 Setting 0 150 0 0 01 04 Inhib I by 52a Binary 1 bit 0 Disabled Enabled 2301 1 Setting 0 1 1 24 00 NEGATIVE CURRENT 01 Iinv Binary 1 bit 0 Disabled Enabled Setting 0 1 1 02 Threshold Ii...

Страница 448: ...1 1 11 Threshold Iinv Courier floating point number 0 1 In 2410 1 Setting 0 1 40 0 0 01 In 12 Tempo Iinv Courier floating point number 0 01 s 2410 1 Setting 0 150 0 1 0 25 00 AUTORECLOSER 01 Autoreclo...

Страница 449: ...es tI configuration Unsigned Integer 2 bytes 0x1111 2501 1 Setting 0 2 1 on each 4 bit group 10 Cycles tI configuration Unsigned Integer 2 bytes 0x1111 2501 1 Setting 0 2 1 on each 4 bit group 11 Cycl...

Страница 450: ...empo Type I Indexed String 0 1 2 0 definite time 1 inverse time 2 RI curve 4002 1 Setting 0 2 1 05 Curve Type I Indexed String 0 1 2 3 4 5 6 7 8 9 10 STI CEI SI CEI VI CEI EI CEI LTI CEI STI CO2 MI AN...

Страница 451: ...Stage 2 Overcurrent Sub Heading 11 Max I Binary 1 bit 0 Disabled Enabled Setting 0 1 1 12 Threshold I Courier floating point number 0 50 In 4011 1 Setting 0 5 40 0 0 05 13 Tempo Type I Indexed String...

Страница 452: ...ng 0 1 19 RTMS I Courier floating point number 0 025 4018 1 Setting 0 025 3 2 0 001 1A T RESET I Courier floating point number 0 04 4018 0 or 4013 0 or 4013 2 or 4013 1 4014 5 4014 9 Setting 0 600 0 0...

Страница 453: ...if great sensitivity 4102 1 Setting 0 01 2 0 0 005 or 0 1 25 0 0 01if normal sensitivity or 0 002 1 0 0 001 if great sensitivity 04 Temporisation Type IE Indexed String 0 1 2 3 0 definite time 1 inver...

Страница 454: ...4105 5 4105 9 Setting 0 1 0B RTMS IE Courier floating point number 0 025 4109 1 Setting 0 025 3 2 0 001 0C T RESET IE Courier floating point number 0 04 4109 0 or 4104 0 or 4104 2 or 4104 3 or 4104 1...

Страница 455: ...SI CEI VI CEI EI CEI LTI CEI STI CO2 MI ANSI LTI CO8 VI ANSI EI ANSI RC CEI 4113 1 Setting 0 10 1 15 Curve Type 2 RXIDG IE Indexed String 0 1 2 3 4 5 6 7 K 0 3 K 0 4 K 0 5 K 0 6 K 0 7 K 0 8 K 0 9 K 1...

Страница 456: ...ating point number IEn or 0 50 IEn if normal sensitivity or 0 002 IEn if great sensitivity 4121 1 Setting 0 01 8 0 0 005 or 0 50 40 0 0 01 if normal sensitivity or 0 002 1 0 0 001 if great sensitivity...

Страница 457: ...t number 0 01 s 4301 1 Setting 0 150 0 0 01 04 Inhib I by 52a Binary 1 bit 0 Disabled Enabled 4301 1 Setting 0 1 1 44 00 NEGATIVE CURRENT 01 Iinv Binary 1 bit 0 Disabled Enabled Setting 0 1 1 02 Thres...

Страница 458: ...g 0 1 1 11 Threshold Iinv Courier floating point number 0 1 In 4410 1 Setting 0 1 40 0 0 01 In 12 Tempo Iinv Courier floating point number 0 01 s 4410 1 Setting 0 150 0 1 0 45 00 AUTORECLOSER 01 Autor...

Страница 459: ...es tI configuration Unsigned Integer 2 bytes 0x1111 4501 1 Setting 0 2 1 on each 4 bit group 10 Cycles tI configuration Unsigned Integer 2 bytes 0x1111 4501 1 Setting 0 2 1 on each 4 bit group 11 Cycl...

Страница 460: ...I 2 t I 3 t IE 4 t IE 5 t IE 6 t I 7 t Therm 8 Broken Conductor 9 t Aux1 10 t Aux2 11 t I2 12 t I2 13 t Aux3 14 t Aux4 15 Breaker Fail Setting 0 65535 1 02 Latch Configuration Binary 15 bits 0 0 Latc...

Страница 461: ...cking t Therm 8 Blocking Broken Conductor 9 Blocking t Aux1 10 Blocking t Aux2 11 Blocking t I2 12 Blocking t I2 13 Blocking t Aux3 14 Blocking t Aux4 15 reserved Setting 0 65535 1 04 Blocking 2 Confi...

Страница 462: ...I 3 Desens t IE 4 Desens t IE 5 Desens t IE 6 Desens t Therm 7 Desens t I2 8 Desens t I2 6008 1 Setting 0 511 1 0A of cold load start Unsigned Integer 2 bytes 50 6008 1 Setting 20 500 1 0B Cold load...

Страница 463: ...Setting 0 150 0 0 01 s 15 Trip Configuration 2 2 Binary 10 bits 0 0 Trip SOTF 1 Control TRIP 2 Trip Equation A 3 Trip Equation B 4 Trip Equation C 5 Trip Equation D 6 Trip Equation E 7 Trip Equation...

Страница 464: ...P121 P122 P123 Col Row Menu Text Data Type Ind Values default Depend Cell Type Min Max Step 23 Inrush blocking selection Binary 13 bits 0 t I 1 t I 2 t I 3 t IE 4 t IE 5 t IE 6 Reserved 7 Reserved 8 R...

Страница 465: ...ling edge Setting 0 31 1 09 TS voltage Indexed String 0 DC 1 AC Setting 0 1 1 0A Timer aux 3 Courier floating point number 0 Setting 0 200 0 0 01 0B Timer aux 4 Courier floating point number 0 Setting...

Страница 466: ...8 Disturbance start 9 Cold load start 10 Log Selectivity 1 11 Log Selectivity 2 12 Change of group 13 Recloser locked 14 Thermal reset 15 Trip circuit supervision Setting 0 65535 1 12 Logical input 3...

Страница 467: ...8 Disturbance start 9 Cold load start 10 Log Selectivity 1 11 Log Selectivity 2 12 Change of group 13 Recloser locked 14 Thermal reset 15 Trip circuit supervision Setting 0 65535 1 14 Logical input 5...

Страница 468: ...nary 8 bits 0 1 2 3 4 5 6 7 0 external CB failure 1 Leds reset 2 Maintenance mode 3 External input 3 4 External input 4 5 Manual Close 6 Local Mode 7 Synchronisation Setting 0 255 1 17 Logical input 3...

Страница 469: ...Row Menu Text Data Type Ind Values default Depend Cell Type Min Max Step 19 Logical input 5 allocation 2 2 Binary 8 bits 0 1 2 3 4 5 6 7 0 external CB failure 1 Leds reset 2 Maintenance mode 3 Externa...

Страница 470: ...ary 7 bits 5 bits 0000000 00000 Setting 0 127 1 or 0 31 1 0B t IE Binary 7 bits 5 bits 0000000 00000 Setting 0 127 1 or 0 31 1 0C IE Binary 7 bits 5 bits 0000000 00000 Setting 0 127 1 or 0 31 1 0D t I...

Страница 471: ...000000 Setting 0 127 1 20 tCOMM1 Binary 7 bits 5 bits 0000000 00000 Setting 0 127 1 or 0 31 1 21 tCOMM2 Binary 7 bits 5 bits 0000000 00000 Setting 0 127 1 or 0 31 1 22 tCOMM3 Binary 7 bits 5 bits 0000...

Страница 472: ...ation C Binary 7 bits 5 bits 0000000 00000 Setting 0 127 1 or 0 31 1 33 Equation D Binary 7 bits 5 bits 0000000 00000 Setting 0 127 1 or 0 31 1 34 Equation E Binary 7 bits 5 bits 0000000 00000 Setting...

Страница 473: ...ETTINGS 01 Led 5 1 3 Binary 16 bits 4 0 I 1 t I 2 I 3 t I 4 I 5 t I 6 IE 7 t IE 8 IE 9 t IE 10 IE 11 t IE 12 Thermal Overload 13 t I2 14 Broken Conductor 15 Breaker Failure Setting 0 65535 1 02 Led 6...

Страница 474: ...Led 7 1 3 Binary 16 bits 32 0 I 1 t I 2 I 3 t I 4 I 5 t I 6 IE 7 t IE 8 IE 9 t IE 10 IE 11 t IE 12 Thermal Overload 13 t I2 14 Broken Conductor 15 Breaker Failure Setting 0 65535 1 04 Led 8 1 3 Binar...

Страница 475: ...d Autorecloser 6 Autorecloser in progress 7 t Aux1 8 t Aux2 9 t I2 10 SOTF Setting 0 2047 1 06 Led 6 2 3 Binary 11 bits 0 0 Input 1 1 Input 2 2 Input 3 3 Input 4 4 Input 5 5 Locked Autorecloser 6 Auto...

Страница 476: ...t Aux1 8 t Aux2 9 t I2 10 SOTF Setting 0 2047 1 09 Led 5 3 3 Binary 8 bits 0 0 Equation A 1 Equation B 2 Equation C 3 Equation D 4 Equation E 5 Equation F 6 Equation G 7 Equation H Setting 0 255 1 0A...

Страница 477: ...2 2 Alarm tAux3 3 Alarm tAux4 Setting 0 15 1 or 0 7 1 69 00 SW SUPERVISION 01 Trip circuit supervision Binary 1 bit 0 Disabled Enabled Setting 0 1 1 02 Trip circuit time Courier floating point number...

Страница 478: ...tting 0 1 5 0 0 05 s 6A 00 COMM ORDER LATCH TIMES 01 t COMM1 Courier floating point number 0 1 s 6220 0 Setting 0 1 600 0 0 05 s 02 t COMM2 Courier floating point number 0 1 s 6221 0 Setting 0 1 600 0...

Страница 479: ...OOLEAN EQUATIONS 1 2 10 EQUATION A Sub Heading 11 Operator 00 Indexed String 0 1 Space NOT Setting 0 1 1 12 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 2...

Страница 480: ...ring 0 1 2 3 OR OR NOT AND AND NOT Setting 0 3 1 14 Operand 01 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t...

Страница 481: ...in Max Step 16 Operand 02 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 482: ...in Max Step 18 Operand 03 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 483: ...in Max Step 1A Operand 04 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 484: ...in Max Step 1C Operand 05 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 485: ...in Max Step 1E Operand 06 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 486: ...in Max Step 20 Operand 07 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 487: ...in Max Step 22 Operand 08 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 488: ...in Max Step 24 Operand 09 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 489: ...in Max Step 26 Operand 10 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 490: ...in Max Step 28 Operand 11 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 491: ...in Max Step 2A Operand 12 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 492: ...in Max Step 2C Operand 13 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 493: ...in Max Step 2E Operand 14 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 494: ...Ind Values default Depend Cell Type Min Max Step 30 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t...

Страница 495: ...Operator 00 Indexed String 0 1 Space NOT Setting 0 1 1 42 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t I...

Страница 496: ...Step 60 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Trip I t I...

Страница 497: ...in Max Step 72 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 498: ...Ind Values default Depend Cell Type Min Max Step 90 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t...

Страница 499: ...Operator 00 Indexed String 0 1 Space NOT Setting 0 1 1 A2 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t I...

Страница 500: ...Ind Values default Depend Cell Type Min Max Step C0 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t...

Страница 501: ...OOLEAN EQUATIONS 2 2 10 EQUATION E Sub Heading 11 Operator 00 Indexed String 0 1 Space NOT Setting 0 1 1 12 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 2...

Страница 502: ...in Max Step 13 Operator 01 Indexed String 0 1 2 3 OR OR NOT AND AND NOT Setting 0 3 1 30 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t...

Страница 503: ...Operator 00 Indexed String 0 1 Space NOT Setting 0 1 1 42 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t I...

Страница 504: ...Step 60 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Trip I t I...

Страница 505: ...in Max Step 72 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 506: ...Step 90 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Trip I t I...

Страница 507: ...in Max Step A2 Operand 00 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t I2 I2 t I2 Thermal Alarm Thermal Tri...

Страница 508: ...Ind Values default Depend Cell Type Min Max Step C0 Operand 15 Indexed String 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NULL I t I I t I I t I Ie t Ie Ie t Ie Ie t Ie I2 t...

Страница 509: ...C operation delay Courier floating point number 0 Setting 0 600 0 0 01 s 06 Equation C reset delay Courier floating point number 0 Setting 0 600 0 0 01 s 07 Equation D operation delay Courier floatin...

Страница 510: ...s 70 00 RECORDER CONTROL 01 Start Trigger recorder Indexed String 0 1 2 Stopped Trigerred Running Setting 1 2 1 02 Recorder Source Indexed String 0 Samples Data 20 Pretemps Courier floating point numb...

Страница 511: ...3 4 11111 Ia Ib Ic I0 Inputs Outputs Data 04 Channel Types Binary Flag 0 digital 1 analogue 01111 Data 05 Channel Offsets Repeated group of Courier numbers Upload Offsets Data 06 Scaling Factors Repe...

Страница 512: ...Bin flags Data 90 00 AUTOMAT FLT 01 Record number Unsigned Integer 2 bytes Setting automatic 02 Occur fault date Unsigned Integer 2 bytes Data 03 Active set group Unsigned Integer 2 bytes 1 Data 04 P...

Страница 513: ...Text Data Type Ind Values default Depend Cell Type Min Max Step BF 00 COMM SYSTEM DATA 01 Dist Record Cntrl Ref Menu Cell 2 0x7000 Data 02 Dist Record Extract Ref Menu Cell 2 0x8000 Data 03 Setting Tr...

Страница 514: ...P12x EN CT A96 Communications COURIER DATABASE Page 146 248 MiCOM P120 P121 P122 P123...

Страница 515: ...Communications P12x EN CT A96 MiCOM P120 P121 P122 P123 IEC 60870 5 103 MiCOM P120 P121 P122 P123 VERSION V11 A...

Страница 516: ......

Страница 517: ...events 4 1 5 General interrogation 4 1 6 Cyclic measurements 4 1 7 Commands 4 1 8 Disturbance records P120 P122 P123 only 4 1 9 Blocking of monitor direction 4 2 APPENDIX 1 5 2 1 Spontaneous messages...

Страница 518: ...P12x EN CT A96 Communications IIEC 60870 5 103 Page 2 248 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 519: ...tialise the communications The relay will respond to either of the two reset commands Reset CU or Reset FCB the difference being that the Reset CU will clear any unsent messages in the relay s transmi...

Страница 520: ...e events 1 5 General interrogation The GI request can be used to read the status of the relay the function numbers information numbers and common address offsets that will be returned during the GI cy...

Страница 521: ...events only generated on rising edge will be tagged with a Two types of ASDU can be generated for events ASDU 1 time tagged message or ASDU 2 time tagged message with relative time The following list...

Страница 522: ...23 Auxiliary input 4 FUN 160 INF 30 TYP 1 COT 1 ADDR P123 Logical input 1 FUN 168 INF 160 TYP 1 COT 1 ADDR P120 to P123 with private option inactive FUN 160 INF 161 TYP 1 COT 1 ADDR Logical input 2 FU...

Страница 523: ...INF 181 TYP 1 COT 1 ADDR Logical output 7 FUN 168 INF 182 TYP 1 COT 1 ADDR P122 P123 with private option inactive FUN 160 INF 182 TYP 1 COT 1 ADDR Logical output 8 FUN 168 INF 183 TYP 1 COT 1 ADDR P1...

Страница 524: ...98 TYP 2 COT 1 ADDR Start pick up N FUN 160 INF 67 TYP 2 COT 1 ADDR P120 to P123 Start pick up I FUN 168 INF 100 TYP 2 COT 1 ADDR P122 P123 with private option inactive FUN 160 INF 73 TYP 2 COT 1 ADD...

Страница 525: ...ith private option inactive FUN 160 INF 94 TYP 2 COT 1 ADDR 1 Trip IN FUN 160 INF 92 TYP 2 COT 1 ADDR P120 to P123 Trip IN FUN 160 INF 93 TYP 2 COT 1 ADDR P120 to P123 Trip IN FUN 168 INF 22 TYP 2 COT...

Страница 526: ...p Equation E private option active FUN 168 INF 196 TYP 2 COT 1 ADDR P121 P122 P123 Trip Equation F private option active FUN 168 INF 197 TYP 2 COT 1 ADDR P121 P122 P123 Trip Equation G private option...

Страница 527: ...data they are systematically sent to the master station during a General Interrogation The list of processed data following a General Interrogation is given below it is a sub assembly of the spontaneo...

Страница 528: ...DR Logical output 1 FUN 168 INF 176 TYP 1 COT 9 ADDR P120 to P123 with private option inactive FUN 160 INF 176 TYP 1 COT 9 ADDR Logical output 2 FUN 168 INF 177 TYP 1 COT 9 ADDR P120 to P123 with priv...

Страница 529: ...lity Trip Circuit Supervision FUN 160 INF 36 TYP 1 COT 9 ADDR P122 P123 Fault Indications in monitor direction Availability Start pick up N FUN 160 INF 67 TYP 2 COT 9 ADDR P120 to P123 General Start p...

Страница 530: ...rs of the GI cycle generated by the GI command If a data has just changed before extracted by the GI the new state is sent to the master station When an event is generated during the GI cycle the even...

Страница 531: ...P123 with private option inactive FUN 160 INF 142 TYP 1 COT 20 ADDR Close TC FUN 168 INF 2 TYP 20 COT 20 ADDR P120 to P123 with private option inactive FUN 160 INF 143 TYP 1 COT 20 ADDR After executin...

Страница 532: ...messages The measurands values are stored in lower levels of communication before polling by master station Several of the fields in the ASDU 9 FUN 160 INF 148 are unused in the P122 P123 relay Volta...

Страница 533: ...ollowing Number of analog channels transmitted 1 which is Channel 1 IN current Earth Identifiers of tags 8 transmitted in ASDU 29 logical informations Tag number 1 IN FUN 160 INF 67 Tag number 2 Gener...

Страница 534: ...or P122 Tag number 1 IN FUN 160 INF 67 Tag number 2 General start FUN 160 INF 84 Tag number 3 CB Failure FUN 160 INF 85 Tag number 4 General Trip FUN 160 INF 68 Tag number 5 tI FUN 160 INF 90 Tag numb...

Страница 535: ...og input 3 FUN 168 INF 162 with private option inactive FUN 160 INF 163 For a P123 there are 15 identifiers of tags so the two following tags in addition to the precedents Tag number 14 Log input 4 FU...

Страница 536: ...P12x EN CT A96 Communications IEC 60870 5 103 Page 20 248 MiCOM P120 P121 P122 P123...

Страница 537: ...Communications P12x EN CT A96 MiCOM P120 P121 P122 P123 DNP 3 0 DATABASE MiCOM P120 P121 P122 P123 VERSION V11 A...

Страница 538: ......

Страница 539: ...1 248 CONTENTS 1 INTRODUCTION 3 1 1 Purpose of this document 3 1 2 DNP V3 00 device Profile 3 1 3 Implementation Table 6 1 4 Point List 8 1 4 1 Binary Input Points 8 1 4 2 Binary Output Status Points...

Страница 540: ...P12x EN CT A96 Communications DNP 3 0 Database Page 2 248 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 541: ...and a description of configuration methods and user interface in Sections DNP V3 00 DEVICE PROFILE DOCUMENT ALSO SEE THE IMPLEMENTATION TABLE IN SECTION 1 3 BEGINNING ON PAGE 6 Vendor Name AREVA T D A...

Страница 542: ...s Configurable DIRECT OPERATE Never Always Sometimes Configurable DIRECT OPERATE NO ACK Never Always Sometimes Configurable Count 1 Never Always Sometimes Configurable Pulse On Never Always Sometimes...

Страница 543: ...BLE IN SECTION 1 3 BEGINNING ON PAGE 6 Default Counter Object Variation No Counters Reported Configurable Default Object 20 Default Variation 5 Point by point list attached Counters Roll Over at No Co...

Страница 544: ...d qty 129 response 17 28 index 10 0 Binary Output Status Variation 0 is used to request default variation 1 read 00 01 start stop 06 no range or all 07 08 limited qty 17 28 index 10 2 default see note...

Страница 545: ...hout Time 1 read 06 no range or all 07 08 limited qty 129 response 17 28 index 32 2 16 Bit Analog Change Event without Time 1 read 06 no range or all 07 08 limited qty 129 response 17 28 index 32 only...

Страница 546: ...elay 3 0 2 3 3 3 3 Output relay 4 0 2 4 4 4 4 Output relay 0 watch dog 0 2 5 5 Output relay 5 0 2 6 6 Output relay 6 0 2 7 Output relay 7 0 2 8 Output relay 8 0 2 5 5 7 9 Opto isolator 1 0 2 6 6 8 10...

Страница 547: ...ote order 0 1 20 26 47 54 Tripping order by remote order 0 1 48 55 Thermal Resetting by communication 0 1 49 56 Shifting to maintenance mode 0 1 21 27 50 57 Major material Alarms 0 1 22 28 51 58 Minor...

Страница 548: ...ame Description init val Change Event Class 1 2 3 or none 78 86 taux3 alarm if latched by Trip 0 3 87 taux4 0 1 88 taux4 alarm if latched by Trip 0 3 89 Final trip autorecloser 0 1 39 79 90 t Equation...

Страница 549: ...e Pulse On 3 3 3 3 Remote control Triping 0 Unpaired Pulse On Paired Trip Pulse On 4 4 4 4 Remote control Closing 0 Unpaired Pulse On Paired Close Pulse On 5 5 Change of Active Group 0 Unpaired Pulse...

Страница 550: ...ange Event Object Number not supported Request Function Codes supported 1 read Static Variation reported when variation 0 requested 9 32 Bit Frozen Binary without Flag Change Event Variation reported...

Страница 551: ...ey are included in one of classes 1 2 or 3 Analog Inputs Static Steady State Object Number 30 Change Event Object Number 32 Request Function Codes supported 1 read Static Variation reported when varia...

Страница 552: ...esent ation of 32767 see above Valid Range Change Event Dead band Initial Change Event Class 1 2 3 or none 18 18 Fault origin 0 32767 0 to 17 P122 18 P123 F2 each new fault 2 19 19 Fault magnitude 0 4...

Страница 553: ...Commissioning and Maintenance P12x EN CM A96 MiCOM P120 P121 P122 P123 COMMISSIONING AND MAINTENANCE GUIDE...

Страница 554: ......

Страница 555: ...4 3 PRODUCT VERIFICATION TESTS 5 3 1 Allocation of terminals 5 3 2 Electrostatic discharge ESD 5 3 3 Visual inspection 5 3 4 Earthing 5 3 5 Current transformers CT s 5 3 5 1 Use of a Core CT for eart...

Страница 556: ...22 P123 5 MAINTENANCE 15 5 1 Equipment failure 15 5 1 1 Minor fault 15 5 1 2 Major fault 15 5 2 Method of repair 16 5 2 1 Replacing the active part 16 5 2 2 Replacing the complete relay 16 5 3 Problem...

Страница 557: ...he settings applied to the relay using the appropriate setting software MiCOM S1 preferred method Via the front panel user interface REMINDER It is not possible to download a new setting software as l...

Страница 558: ...n 1 ms Three phase injection test set 3 currents 0 to 50 A timer precision 1 ms 2 1 2 Additional commissioning test equipment 1 multimeter precision 1 1 connecting terminal to measure the currents exc...

Страница 559: ...hases and earth CT s between the terminals indicated on the wiring diagram are closed 3 4 Earthing Check if the earth connection of the case situated above the rear terminal block is used to connect t...

Страница 560: ...ent can be read on the MiCOM P120 P121 P122 and P123 and produce false readings P121 with CT core Busbar 2 Busbar 1 Earthing 1 Earthing 2 Circuit Breaker 1 Circuit Breaker 2 Electrical line P0042ENa F...

Страница 561: ...is energised one of the characters on the bottom line of the menu display will change to the value show in the following table to indicate the new state of the inputs Input MiCOM P12x models OP PARAME...

Страница 562: ...RL 5 P122 P123 00010000 RL 6 P122 P123 00100000 RL 7 P123 01000000 RL 8 P123 10000000 3 9 RS 485 rear communication This test should only be performed where the relay is to be accessed from a remote...

Страница 563: ...arry forward the settings on the commissioning test sheets 4 2 Measurements The MiCOM P120 P121 P122 and P123 relays measure phase and earth currents P120 only one phase or earth as a True RMS value u...

Страница 564: ...44 45 46 To carry out injection for the 1 Amp phase inputs perform the same test on the 1 Amp inputs terminals 49 50 51 52 53 54 MiCOM P121 33 34 Case earth 29 RS 485 communication port 31 32 30 Watch...

Страница 565: ...rease the injection current up to the value of the I threshold If the time delay tI is long inject 0 95 x I threshold and check that there is no tripping Then inject 1 1 x I threshold and check the tr...

Страница 566: ...nal tripping time less than 40ms STI AREVA 1 78 1 56 2 00 0 518 0 492 0 544 SI 10 03 8 78 11 28 2 971 2 822 3 119 VI 13 5 11 81 15 19 1 5 1 425 1 575 EI 26 67 23 33 30 00 0 808 0 7676 0 8484 LTI AREVA...

Страница 567: ...42 1 76 1 67 1 85 RXIDG with k 0 6 4 17 3 65 4 69 2 00 1 90 2 10 RXIDG with k 0 7 4 38 3 83 4 93 2 21 2 10 2 32 RXIDG with k 0 8 4 56 3 99 5 13 2 39 2 27 2 51 RXIDG with k 0 9 4 72 4 13 5 31 2 55 2 4...

Страница 568: ...I threshold I injected 2 x I threshold Apply a current onto one of the phases and measure the time delay tI by pre setting the current above the I threshold I injected 10 x I threshold 4 4 Final check...

Страница 569: ...nly when relay boots and on any setting change 5 1 1 Minor fault Regarded by the MiCOM P120 P121 P122 and P123 relays as a minor fault is a communication failure If the communication is in fault MiCOM...

Страница 570: ...notches on the front panel of the MiCOM relay The reinstall the repaired or replacement relay follow the above instruction in reverse ensuring that no modification has been done on the scheme wiring...

Страница 571: ...e of this chapter 5 3 Problem solving 5 3 1 Password lost or not accepted Problem Password lost or not accepted Cause MiCOM P120 P121 P122 and P123 relays are supplied with the password set to AAAA Th...

Страница 572: ...er responds Problem No response from MiCOM P120 P121 P122 and P123 relays when asked by the supervision software without any communication fault message Cause Mainly this type of problem is linked to...

Страница 573: ...Connection Diagrams P12x EN CO A96 MiCOM P120 P121 P122 P123 CONNECTION DIAGRAMS...

Страница 574: ......

Страница 575: ...current input is connected to the sommation of the three phase CTs C A B S1 S2 S2 P2 P1 P2 37 S1 P1 5 A 5 A 5 A 5 A 1 A 1 A 48 47 46 45 44 43 42 41 56 55 54 52 53 1 A 1 A 50 51 49 input Programmable P...

Страница 576: ...nput is connected to the sommation of the three phase CTs Alternative Connection to 2 phases CTs a core balanced CT P123 only P123 only input Programmable input Programmable input Programmable input P...

Страница 577: ...ble 29 30 31 32 shield P0253ENa Case earth connection 1 Connect a cable green yellow wire on the case earth connection of each product with screw 2 The communication cable shield must be connected to...

Страница 578: ...th EARTH 1 Connect a cable green yellow wire on the case earth connection of each product with screw 2 The communication cable shield must be connected to the pin number 29 of each product 3 The pin n...

Страница 579: ...Commissioning Test Record Sheets P12x EN RS A96 MiCOM P120 P121 P122 P123 COMMISSIONING TEST RECORD SHEETS...

Страница 580: ......

Страница 581: ...record sheets 10 2 2 1 OP PARAMETERS Menu 10 2 2 2 CONFIGURATION Menu 10 2 2 3 COMMUNICATION Menu 11 2 2 4 PROTECTION Menu 12 2 2 5 AUTOMAT CTRL Menu 13 2 3 MiCOM P122 commissioning setting record sh...

Страница 582: ...P12x EN RS A96 Commissioning Test Record Sheets Page 2 60 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 583: ...TINGS ON THE EQUIPMENT RATING LABEL 1 1 Relay identification Commissioning date Engineer Substation Circuit Network nominal frequency MiCOM Overcurrent relay model P120 P121 P122 P123 Serial number Ra...

Страница 584: ...Phase A current _______________ A A Phase B current _______________ A A Phase C current _______________ A A EARTH CT INPUT Earth current _______________ A A Phase protection test Theoretical value Rel...

Страница 585: ...A Ie drop threshold _______________A Time delay Time delay at 2 x Ie ______________ ms ms Time delay at 10 x Ie ______________ ms ms Ie threshold _______________ A Ie threshold _______________A Ie dro...

Страница 586: ...E Gnd CT Secondary Secondary CT ratio 1 A 5 A 2 1 2 3 LEDs 5 to 8 configuration Functions LED 5 LED 6 LED 7 LED 8 Ie I YES NO YES NO YES NO YES NO tIe tI YES NO YES NO YES NO YES NO Ie I YES NO YES NO...

Страница 587: ...0 bds 9 600 bds 19 200 bds 38 400 bds Relay Address 2 1 3 4 COMMUNICATION Menu DNP3 Communication YES NO Baud Rate 300 bds 600 bds 1 200 bds 2 400 bds 4 800 bds 9 600 bds 19 200 bds 38 400 bds Parity...

Страница 588: ...ES NO Trip tIe YES NO Trip tIe YES NO 2 1 5 2 Latch Function allocation Latch tIe YES NO Latch tIe YES NO Latch tIe YES NO 2 1 5 3 Blocking logic allocation Block tIe YES NO Block tIe YES NO Block tIe...

Страница 589: ...ing Test Record Sheets P12x EN RS A96 MiCOM P120 P121 P122 P123 Page 9 60 2 1 5 5 Inputs allocation Input 1 None Unlatch 52a 52b CB FLT Aux 1 Aux2 Blk log Input 2 None Unlatch 52a 52b CB FLT Aux 1 Aux...

Страница 590: ...atio Line CT Secondary Secondary phase CT ratio 1 A 5 A E Gnd CT Primary Primary earth CT ratio E Gnd CT Secondary Secondary earth CT ratio 1 A 5 A 2 2 2 3 LEDs 5 to 8 configuration Functions LED 5 LE...

Страница 591: ...bits 7 8 Stop bits 1 2 Relay Address 2 2 3 2 COMMUNICATION Menu Courier Communication YES NO Relay Address 2 2 3 3 COMMUNICATION Menu IEC 60870 5 103 Communication YES NO Baud Rate 300 bds 600 bds 1...

Страница 592: ...Delay Type IDMT DMT RI 2 2 4 1 1 1 51 I DMT tI ms 2 2 4 1 1 2 51 I IDMT Idmt IEC SI IEC STI IEC VI IEC EI IEC LTI CO2 IEEE MI CO8 IEEE VI IEEE EI Tms 2 2 4 1 1 3 51 I RI K 2 2 4 1 2 51 I I YES NO I I...

Страница 593: ...2 2 4 2 1 3 51N Ie RI K 2 2 4 2 2 51N Ie Ie YES NO Ie Ien tIe ms 2 2 4 2 3 51N Ie Ie YES NO Ie Ien tIe ms 2 2 5 AUTOMAT CTRL Menu 2 2 5 1 Trip Command allocation Trip tI YES NO Trip tI YES NO Trip tI...

Страница 594: ...nctions RL 2 RL 3 RL 4 Trip YES NO YES NO YES NO I YES NO YES NO YES NO tI YES NO YES NO YES NO I YES NO YES NO YES NO tI YES NO YES NO YES NO I YES NO YES NO YES NO tI YES NO YES NO YES NO Ie YES NO...

Страница 595: ...d Reference Software version Frequency 50 Hz 60 Hz 2 3 2 CONFIGURATION Menu 2 3 2 1 Display Phase A Text A L1 R Phase B Text B L2 S Phase C Text C L3 T E Gnd Text N E G 2 3 2 2 CT Ratio Line CT Primar...

Страница 596: ...e YES NO YES NO YES NO YES NO Ie YES NO YES NO YES NO YES NO tIe YES NO YES NO YES NO YES NO Thermal Trip YES NO YES NO YES NO YES NO Brkn Cond YES NO YES NO YES NO YES NO CB Fail YES NO YES NO YES NO...

Страница 597: ...A B C A C B 2 3 3 COMMUNICATION Menu 2 3 3 1 COMMUNICATION Menu MODBUS Communication YES NO Baud Rate 300 bds 600 bds 1 200 bds 2 400 bds 4 800 bds 9 600 bds 19 200 bds 38 400 bds Parity Odd Even None...

Страница 598: ...ty Odd Even None Data bits 7 8 Stop bits 1 2 Relay Address 2 3 4 PROTECTION G1 Menu 2 3 4 1 Phase Overcurrent 50 51 2 3 4 1 1 50 51 I I YES NO I In Delay Type IDMT DMT RI 2 3 4 1 1 1 51 I DMT tI ms t...

Страница 599: ...IDMT DMT RI 2 3 4 1 2 1 51 I DMT tI ms t Reset ms 2 3 4 1 2 2 51 I IDMT Idmt IEC SI IEC STI IEC VI IEC EI IEC LTI CO2 IEEE MI CO8 IEEE VI IEEE EI IEEE RC Tms 2 3 4 1 2 3 51 I DMT reset time t Reset m...

Страница 600: ...3 4 2 1 1 51N Ie DMT tIe ms t Reset ms 2 3 4 2 1 2 51N Ie IDMT Idmt IEC SI IEC STI IEC VI IEC EI IEC LTI CO2 IEEE MI CO8 IEEE VI IEEE EI IEEE RC Tms 2 3 4 2 1 3 51N Ie DMT reset time t Reset ms 2 3 4...

Страница 601: ...IEEE VI IEEE EI IEEE RC Tms 2 3 4 2 2 3 51N Ie DMT reset time t Reset ms 2 3 4 2 2 4 51N Ie IDMT reset time Rtms 2 3 4 2 2 5 51N Ie RI K t Reset ms 2 3 4 2 2 6 51N Ie RXIDG K t Reset ms 2 3 4 2 3 51N...

Страница 602: ...NO I2 In Delay Type IDMT DMT RI 2 3 4 5 1 46 I2 DMT tI ms 2 3 4 5 2 46 I2 DMT Idmt IEC SI IEC STI IEC VI IEC EI IEC LTI CO2 IEEE MI CO8 IEEE VI IEEE EI Tms 2 3 4 5 3 46 I2 DMT reset time t Reset ms 2...

Страница 603: ...Delay Type IDMT DMT RI 2 3 5 1 1 1 51 I DMT tI ms t Reset ms 2 3 5 1 1 2 51 I IDMT Idmt IEC SI IEC STI IEC VI IEC EI IEC LTI CO2 IEEE MI CO8 IEEE VI IEEE EI IEEE RC Tms 2 3 5 1 1 3 51 I DMT reset tim...

Страница 604: ...2 IEEE MI CO8 IEEE VI IEEE EI IEEE RC Tms 2 3 5 1 2 3 51 I DMT reset time t Reset ms 2 3 5 1 2 4 51 I IDMT reset time Rtms 2 3 5 1 2 5 51 I RI K t Reset ms 2 3 5 1 3 51 I I YES NO I Sample YES NO I In...

Страница 605: ...51N Ie DMT reset time t Reset ms 2 3 5 2 1 4 51N Ie IDMT reset time Rtms 2 3 5 2 1 5 51N Ie RI K t Reset ms 2 3 5 2 1 6 51N Ie RXIDG K t Reset ms 2 3 5 2 2 51N Ie Ie YES NO Ie Ien Delay Type IDMT DMT...

Страница 606: ...K t Reset ms 2 3 5 2 2 6 51N Ie RXIDG K t Reset ms 2 3 5 2 3 51N Ie Ie YES NO Ie Sample YES NO Ie Ien tIe ms 2 3 5 3 49 THERMAL OVERLOAD Therm OL YES NO I In Te mn k Trip Alarm YES NO Alarm 2 3 5 4 37...

Страница 607: ...5 5 4 46 I2 IDMT reset time Rtms 2 3 5 5 5 46 I2 RI K t Reset ms 2 3 5 6 46 Negative phase sequence overcurrent I2 I2 YES NO I2 In tI2 ms 2 3 6 AUTOMAT CTRL Menu 2 3 6 1 TRIP Command allocation Trip t...

Страница 608: ...S NO Latch tI2 YES NO Latch Thermal YES NO Latch Brkn Cond YES NO Latch tAux1 YES NO Latch tAux2 YES NO Latch tAux3 YES NO 2 3 6 3 Blocking Logic 1 function allocation Block 1 tI YES NO Block 1 tI YES...

Страница 609: ...I YES NO Block 2 tI2 YES NO Block 2 tI2 YES NO Block 2 Thermal YES NO Block 2 Brkn Cond YES NO Block 2 tAux1 YES NO Block 2 tAux2 YES NO Block 2 tAux3 YES NO 2 3 6 5 SELECTIVE SCHEME LOGIC1 function a...

Страница 610: ...NO YES NO tIe YES NO YES NO YES NO Ie YES NO YES NO YES NO tIe YES NO YES NO YES NO tI YES NO YES NO YES NO tI2 YES NO YES NO YES NO tI2 YES NO YES NO YES NO Therm Alarm YES NO YES NO YES NO Therm Tri...

Страница 611: ...ES NO YES NO Ie YES NO YES NO tIe YES NO YES NO Ie YES NO YES NO tIe YES NO YES NO tI YES NO YES NO tI2 YES NO YES NO tI2 YES NO YES NO Therm Alarm YES NO YES NO Therm Trip YES NO YES NO CB Alarm YES...

Страница 612: ...Aux3 Strt tBF Input 2 None Unlatch 52a 52b CB FLT Aux1 Aux2 Blk Log 1 Blk Log 2 Strt Dist Cold L PU Log Sel 1 Log Sel 2 Change Set Reset Trip Circ Rst Led Maint M Aux3 Strt tBF Input 3 None Unlatch 52...

Страница 613: ...e YES NO tI2 YES NO tI2 YES NO t Therm YES NO Level tCL ms 2 3 6 11 CIRCUIT BREAKER FAILURE CB Fail YES NO I In tBF ms Block I YES NO Block Ie YES NO 2 3 6 12 CIRCUIT BREAKER SUPERVISION TC Supervisio...

Страница 614: ...Sheets Page 34 60 MiCOM P120 P121 P122 P123 2 3 7 RECORDS Menu 2 3 7 1 DISTURBANCE RECORD Pre Time ms Post Time ms Disturb Rec Trig ON INST ON TRIP 2 3 7 2 TIME PEAK VALUE Time Window mn 2 3 7 3 ROLL...

Страница 615: ...d Reference Software version Frequency 50 Hz 60 Hz 2 4 2 CONFIGURATION Menu 2 4 2 1 Display Phase A Text A L1 R Phase B Text B L2 S Phase C Text C L3 T E Gnd Text N E G 2 4 2 2 CT Ratio Line CT Primar...

Страница 616: ...ES NO YES NO tIe YES NO YES NO YES NO YES NO Therm Trip YES NO YES NO YES NO YES NO Brkn Cond YES NO YES NO YES NO YES NO CB Fail YES NO YES NO YES NO YES NO tI2 YES NO YES NO YES NO YES NO tI2 YES NO...

Страница 617: ...C 2 4 2 7 Relays maintenance Maintenance Mode YES NO 8 7 6 5 W 4 3 2 1 Relays CMD 2 4 2 8 Phase rotation configuration Phase rotation A B C A C B 2 4 3 COMMUNICATION Menu 2 4 3 1 COMMUNICATION Menu MO...

Страница 618: ...4 COMMUNICATION Menu DNP3 Communication YES NO Baud Rate 300 bds 600 bds 1 200 bds 2 400 bds 4 800 bds 9 600 bds 19 200 bds 38 400 bds Parity Odd Even None Data bits 7 8 Stop bits 1 2 Relay Address 2...

Страница 619: ...I RI K t Reset ms 2 4 4 1 2 51 I I YES NO I In Delay Type IDMT DMT RI 2 4 4 1 2 1 51 I DMT tI ms t Reset ms 2 4 4 1 2 2 51 I IDMT Idmt IEC SI IEC STI IEC VI IEC EI IEC LTI CO2 IEEE MI CO8 IEEE VI IEEE...

Страница 620: ...DMT tIe ms t Reset ms 2 4 4 2 1 2 51N Ie IDMT Idmt IEC SI IEC STI IEC VI IEC EI IEC LTI CO2 IEEE MI CO8 IEEE VI IEEE EI INTERLOCK Ie YES NO Tms 2 4 4 2 1 3 51N Ie DMT reset time t Reset ms 2 4 4 2 1...

Страница 621: ...IEEE VI IEEE EI Tms 2 4 4 2 2 3 51N Ie DMT reset time t Reset ms 2 4 4 2 2 4 51N Ie IDMT reset time Rtms 2 4 4 2 2 5 51N Ie RI K t Reset ms 2 4 4 2 2 6 51N Ie RXIDG K t Reset ms 2 4 4 2 3 51N Ie Ie Y...

Страница 622: ...NO I2 In Delay Trip IDMT DMT RI 2 4 4 5 1 46 I2 DMT tI2 ms 2 4 4 5 2 46 I2 IDMT Idmt IEC SI IEC STI IEC VI IEC EI IEC LTI CO2 IEEE MI CO8 IEEE VI IEEE EI Tms 2 4 4 5 3 46 I2 DMT reset time t Reset ms...

Страница 623: ...xt CB Fail Time ms Ext Block YES NO Aux 1 I YES NO Aux 2 Ie YES NO Dead Time tD1 ms Dead Time tD2 ms Dead Time tD3 ms Dead Time tD4 ms Reclaim Time tR ms Inhib Time tI ms Phase Cycles E Gnd Cycles CYC...

Страница 624: ...Delay Type IDMT DMT RI 2 4 5 1 1 1 51 I DMT tI ms t Reset ms 2 4 5 1 1 2 51 I IDMT Idmt IEC SI IEC STI IEC VI IEC EI IEC LTI CO2 IEEE MI CO8 IEEE VI IEEE EI IEEE RC Tms 2 4 5 1 1 3 51 I DMT reset tim...

Страница 625: ...2 IEEE MI CO8 IEEE VI IEEE EI IEEE RC Tms 2 4 5 1 2 3 51 I DMT reset time t Reset ms 2 4 5 1 2 4 51 I IDMT reset time Rtms 2 4 5 1 2 5 51 I RI K t Reset ms 2 4 5 1 3 51 I I YES NO I Sample YES NO I In...

Страница 626: ...TERLOCK Ie YES NO Tms 2 4 5 2 1 3 51N Ie DMT reset time t Reset ms 2 4 5 2 1 4 51N Ie IDMT reset time Rtms 2 4 5 2 1 5 51N Ie RI K t Reset ms 2 4 5 2 1 6 51N Ie RXIDG K t Reset ms 2 4 5 2 2 51N Ie Ie...

Страница 627: ...5 2 2 5 51N Ie RI K t Reset ms 2 4 5 2 2 6 51N Ie RXIDG K t Reset ms 2 4 5 2 3 51N Ie Ie YES NO Ie Sample YES NO Ie Ien tIe ms 2 4 5 3 49 THERMAL OVERLOAD 49 Therm OL YES NO I In Te mn k Trip 49 Alar...

Страница 628: ...s 2 4 5 5 4 46 I2 IDMT reset time Rtms 2 4 5 5 5 46 I2 RI K t Reset ms 2 4 5 6 46 Negative phase sequence overcurrent I2 I2 YES NO I2 In tI2 ms 2 4 5 7 79 AUTORECLOSER 79 Autoreclose YES NO Ext CB Fai...

Страница 629: ...3 2 1 CYCLES tAux 2 4 3 2 1 2 4 6 AUTOMAT CTRL Menu 2 4 6 1 TRIP Command allocation Trip tI YES NO Trip tI YES NO Trip tI YES NO Trip tIe YES NO Trip tIe YES NO Trip tIe YES NO Trip tI YES NO Trip tI...

Страница 630: ...NO Latch Brkn Cond YES NO Latch tAux1 YES NO Latch tAux2 YES NO Latch tAux3 YES NO Latch tAux4 YES NO Latch SOTF YES NO Latch CB FAIL YES NO 2 4 6 3 Blocking Logic 1 function allocation Block 1 tI YE...

Страница 631: ...lock 2 tI2 YES NO Block 2 tI2 YES NO Block 2 Thermal YES NO Block 2 Brkn Cond YES NO Block 2 tAux1 YES NO Block 2 tAux2 YES NO Block 2 tAux3 YES NO Block 2 tAux4 YES NO 2 4 6 5 Selective Scheme Logic1...

Страница 632: ...O tIe YES NO YES NO YES NO Ie YES NO YES NO YES NO tIe YES NO YES NO YES NO Ie YES NO YES NO YES NO tIe YES NO YES NO YES NO tI YES NO YES NO YES NO tI2 YES NO YES NO YES NO tI2 YES NO YES NO YES NO T...

Страница 633: ...Functions RL 2 RL 3 RL 4 Order COM 1 YES NO YES NO YES NO Order COM 2 YES NO YES NO YES NO Order COM 3 YES NO YES NO YES NO Order COM 4 YES NO YES NO YES NO Active Group YES NO YES NO YES NO SOTF YES...

Страница 634: ...S NO tIe YES NO YES NO YES NO YES NO Ie YES NO YES NO YES NO YES NO tIe YES NO YES NO YES NO YES NO tI YES NO YES NO YES NO YES NO tI2 YES NO YES NO YES NO YES NO tI2 YES NO YES NO YES NO YES NO Therm...

Страница 635: ...rder COM 1 YES NO YES NO YES NO YES NO Order COM 2 YES NO YES NO YES NO YES NO Order COM 3 YES NO YES NO YES NO YES NO Order COM 4 YES NO YES NO YES NO YES NO Active Group YES NO YES NO YES NO YES NO...

Страница 636: ...2 None Unlatch 52a 52b CB FLT Aux 1 Aux 2 Blk Log 1 Blk Log 2 Strt Dist Cold L PU Log Sel 1 Log Sel 2 Change Set Reset Block 79 Trip Circ Rst Led Maint M Aux 3 Aux 4 Strt tBF Input 3 None Unlatch 52a...

Страница 637: ...Change Set Reset Block 79 Trip Circ Rst Led Maint M Aux 3 Aux 4 Strt tBF 2 4 6 8 2 tAux Aux 1 Time tAux 1 ms Aux 2 Time tAux 2 ms Aux 3 Time tAux 3 ms Aux 4 Time tAux 4 ms 2 4 6 9 BROKEN CONDUCTOR Br...

Страница 638: ...tBF ms I In Block I YES NO Block Ie YES NO 2 4 6 12 CIRCUIT BREAKER SUPERVISION TC Supervision YES NO t SUP s CB Open S vision YES NO CB Open Time ms CB Close S vision YES NO CB Close Time ms CB Open...

Страница 639: ...RS A96 MiCOM P120 P121 P122 P123 Page 59 60 2 4 7 RECORDING Menu 2 4 7 1 DISTURBANCE RECORD Pre time ms Post time ms Disturb Rec Trig ON INST ON TRIP 2 4 7 2 TIME PEAK VALUE Time Window mn 2 4 7 3 ROL...

Страница 640: ...P12x EN RS A96 Commissioning Test Record Sheets Page 60 60 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 641: ...Hardware Software Version P12x EN VC A96 History and Compatibility MiCOM P120 P121 P122 P123 HARDWARE SOFTWARE VERSION P120 P121 P122 P123 HISTORY AND COMPATIBILITY V11...

Страница 642: ......

Страница 643: ...Hardware Software Version P12x EN VC A96 History and Compatibility MiCOM P120 P121 P122 P123 Page 1 26 CONTENTS 1 INTRODUCTION 3 2 MiCOM P120 4 3 MiCOM P121 7 4 MiCOM P122 11 5 MiCOM P123 18...

Страница 644: ...P12x EN VC A96 Hardware Software Version History and Compatibility Page 2 26 MiCOM P120 P121 P122 P123 BLANK PAGE...

Страница 645: ...0MHz new RAM 2Mb new flash memory 20Mb to replace BBRAM EEPROM front face battery lead free design Hardware watchdog wide range power supply 48 250 Vac dc wide range digital input 48 250 Vac or Vdc AN...

Страница 646: ...n password is active V2 0 V3 C 22 08 00 VDEW improvements V2 0 HARD V 3 HARD V 4 V4 A 15 03 01 Integration of DNP3 protocol Management of alternative logic input Latching of the auxiliary output relay...

Страница 647: ...rd threshold delay Ie whose limitation test was done on 1st threshold delay Ie V2 07 Two versions HARD 3 or HARD 4 HARD 2 V6 D 12 03 06 Software changes implemented in this version Added EA Approval o...

Страница 648: ...be configured as Fail safe Possibility to have contact outputs inverted to trip on drop of signals Time Synchronization through a digital Input TMS step to 0 001 of the TMS as well as the RTMS That w...

Страница 649: ...n of password in order to acknowledge the alarms Auto acknowledgement of the instantaneous Modbus time out of 200 ms Display of the letter P in the menu N and N 1 when password is active V2 0 HARD V 3...

Страница 650: ...U 77 for setting in conformity with the standard cf P127 V2 09 Two versions HARD 3 or HARD 4 HARD 2 V6 B 18 07 03 Improvement of the reading of the alarm EEPROM DATA FAULT when much access EEPROM is d...

Страница 651: ...pressing Clear Button Software improvement done in this version None V2 12 Two versions HARD 3 or HARD 4 HARD 2 06H 14 04 05 Software changes implemented in this version Watchdog behaviour when couri...

Страница 652: ...Trip order to output relays or to logic equations RL1 RL2 can be configured as Fail safe Possibility to have contact outputs inverted to trip on drop of signals TMS step to 0 001 of the TMS as well as...

Страница 653: ...ibility with previous hardware V2 J 30 08 99 MODBUS improvement Correction of al encountered problem answer to a synchronisation telegram creation of a 2 seconds time out HARD V 2 HARD V 3 HARD V 4 V3...

Страница 654: ...ctifier curve LABORELLEC curves Selection of the Setting group by level or by edge CB fail detection possibility to inhibit the starting signals Instanteneous record Rolling demand Peak value demand I...

Страница 655: ...protection functions in IEC870 5 103 communication V2 07 Two versions HARD 3 or HARD 4 HARD 2 V6 A 18 06 03 Add periodic self test of EEPROM data calibration every 24 hours with safeguard of the resul...

Страница 656: ...ation of release addition of manual logical input closed order of manual closing Addition of function LOCAL REMOTE by wiring addition of logical input LOCAL MODE mode switch over local for inhibition...

Страница 657: ...ved SOFT TOR function Improved Breaker Fail alarm processing Fixed checksum verification test in Front panel MODBUS communication V2 10 Two versions HARD 3 or HARD 4 HARD 2 V6 F 08 10 04 Software chan...

Страница 658: ...fier curve selection coherency between P12x and MICOM S1 Correction of Start In event in IEC103 communication when going down General trip correction in disturbance records Utilisation of nominal netw...

Страница 659: ...equations RL1 RL2 can be configured as Fail safe Possibility to have contact outputs inverted to trip on drop of signals Time Synchronization through a digital Input TMS step to 0 001 of the TMS as we...

Страница 660: ...ibility with previous hardware V2 J 30 08 99 MODBUS improvement Correction of al encountered problem answer to a synchronisation telegram creation of a 2 seconds time out HARD V 2 HARD V 3 HARD V 4 V3...

Страница 661: ...to 150 sec Tripping curves rectifier curve LABORELLEC curves Selection of the Setting group by level or by edge CB fail detection possibility to inhibit the starting signals Instantaneous record Roll...

Страница 662: ...unctions in IEC870 5 103 communication V2 07 Two versions HARD 3 or HARD 4 HARD 2 V6 A 18 06 03 Add periodic self test of EEPROM data calibration every 24 hours with safeguard of the results in safegu...

Страница 663: ...ng temporization of release addition of manual logical input closed order of manual closing Addition of function LOCAL REMOTE by wiring addition of logical input LOCAL MODE mode switch over local for...

Страница 664: ...ront panel Software improvement done in this version Modification to fix upload program for FPGA of new CPU board index E or higher This problem affects all Px2x products equiped with this CPU board M...

Страница 665: ...used and must be set to zero as soon as the circuit breaker is done supervision of the 52a information Also it should be kept at zero until the end of inhibits time see also below connection with the...

Страница 666: ...assignable to LED to Trip order to output relays or to logic equations RL1 RL2 can be configured as Fail safe Possibility to have contact outputs inverted to trip on drop of signals Time Synchronizat...

Страница 667: ......

Страница 668: ...AREVA T D s Automation Information Systems Business www areva td com T D Worldwide Contact Centre online 24 hours a day 44 0 1785 25 00 70 http www areva td com contactcentre Publication P12X EN T A96...