2. CONFIGURATION OF THE NETWORK

Possible measure number

Type of measure

200

Status logic input 1

201

Status logic input 2

202

Logical result «or» between logic input 1 

and logic input 2

203

Logical result «and» between logic input 

1 and logic input 2

4) Then transfer the programming of all the instruments of the bus.

Important  :

From the version 2.02 of the TPIs, it is possible to transfer the programming of 

the TPIs directly from the master.

For this purpose, connect yourself on the master and click on «communication 

with the devices» and then «communication through the master» and then «send 

the configuration of all devices».

Then transfer the programming of the master.

5) Then validate the bus. For this purpose connect yourself on the master, click on 

«validate network».

This will record the configuration of the bus in order to point out any error (loss of 

a module for example).

The network must always be validated after adding / removing an instrument and 

after the modification of all the links between instruments.

First start by launching the configuration software SlimSet.

The purpose is to define your network using the software.

1) Connect a USB cable on the first instrument of the bus (the most on the left 

or the most on the right).

Click on «communication with the devices» and then on «add the connected 

device to the architecture».

The instrument will be recognized, and the software will request its position 

within the architecture. Enter it, and do the same for all the instruments of the 

bus.

2) Then choose the instrument which will be the master (TPIs or TPIvM) and 

programme it as master if it is a TPIs (the orange led becomes active).

Important:

From the version 2.02 of the TPIs it is possible to access the configuration of 

the instruments of the bus directly from the master.

In this case first connect the instrument defined as master (TPIs or TPIvM), 

programme it as master if it is a TPIs and click on «communication through the 

master» and then «add or remove some devices».

The software will then take up all the instruments present on the bus and read 

their configuration one by one.

For each instrument detected, the SlimSet will request its position on the archi-

tecture. This position can be determined by a specific blinking of the green led 

of the concerned instrument (morse code blinking: twice on, once off).

3) Then programme each of the instruments, as well as the links between ins-

truments:

for each of the outputs of the output modules (TPIs 4R, TPIs 2A/4A ...) you 

must define the converter associated with this output, as well as the measure 

associated with this output.

Содержание TPIs 2T

Страница 1: ...IQUES INSTRUMENTATIONS AUTOMATISME Route de Brindas Parc d activité d Arbora N 2 69510 Soucieu en Jarrest FRANCE Tél 04 72 31 31 30 Fax 04 72 31 31 31 Tel Intern 33 4 72 31 31 30 Fax Intern 33 4 72 31 31 31 http www ardetem com e mail info ardetem com MODULE OF 2 LOGIC INPUTS TPIs 2T User handbook version 02 02 Software SlimSet ...

Страница 2: ...p1 Summary UE conformity declaration p2 1 INTRODUCTION p3 1 1 General features p3 1 2 Features of the inputs p3 2 CONFIGURATION OF THE NETWORK p4 3 DIMENSIONS MOUNTING p5 4 CONNECTINGS p7 ...

Страница 3: ...Before any installation or maintenance work make sure the power supply of the instrument is cut This symbole indicates that the module is protected by a double or reinforced isolation The person who has designed the system electrical installation including the instrument is sole responsable for the safety and must make sure it has been designed according to the current safety standards This applia...

Страница 4: ...ture 25 C to 70 C Storage temperature 40 C to 85 C Power supply 16 8 to 31 2 Vdc Max power draw 0 7W Max internal dissipation 0 5W Galvanic partition 2 5kV 50Hz 1mn between supply logic inputs µUSB logic inputs not insulated from each other Listed Installation in ATEX IECEx area 2 Installation in division 2 cFMus Compliance with standards Directive EMC 2004 108 CE EN 61326 1 Directive LV 2014 35 U...

Страница 5: ...bus the most on the left or the most on the right Click on communication with the devices and then on add the connected device to the architecture The instrument will be recognized and the software will request its position within the architecture Enter it and do the same for all the instruments of the bus 2 Then choose the instrument which will be the master TPIs or TPIvM and programme it as mast...

Страница 6: ...2 5mm2 14 AWG Protection case terminals IP20 Mounting in switchbox latching on symmetrical DIN rail with footing for the distribution of the 24Vdc power supply and the communication signals Instructions for assembling on 35mm DIN rail according to EN 60715 Assembling of the footings on the rail BEWARE The polarization tongue is at the bottom Assembling of the footings before mounting on DIN rail M...

Страница 7: ...mum de type IP54 Le câble USB ne doit être inséré ou retiré que si l appareil a été mis hors ten sion ou si la zone est sûre Le convertisseur ne doit être déconnecté de son embase rail DIN que si l alimentation du rail a été mise hors tension ou si la zone est sûre L installation doit être réalisée selon le Canadian Electrical Code Partie 1 pour le Canada et le National Electrical Code NFPA 70 pou...

Страница 8: ...p7 4 CONNECTINGS TPIs 2T 8 7 6 5 A B C D E communication 24VDC 30 1 2 3 4 contact 2 0V 5V logic 2 namur 2 contact 1 0V 5V logic 1 namur 1 NPN 1 NPN 2 PNP 1 PNP 2 LED master LED voltage presence ...

Отзывы: