
42
d IX E L
Installing and Operating Instructions
1592020530
1592020530 XR30CX RTC GB r1.0 28.05.2008.doc
XR30CX
2/5
1.
Push the
n
key for more than 3 seconds
2.
e
LED switches ON and the following messages are displayed:
Hur
(hour);
Min
(Minute);
dAY
(day)
3.
To exit push
n
key or wait 5 seconds
6.2
HOW TO SEE THE SETPOINT
1.
Push and immediately release the
SET
key: the display will show
the Set point value;
2.
Push and immediately release the
SET
key or wait for 5 seconds to
display the probe value again.
6.3
HOW TO CHANGE THE SETPOINT
1.
Push the
SET
key for more than 2 seconds to change the Set point value;
2.
The value of the set point will be displayed and the “
°C” or “°F”
LED starts blinking;
3.
To change the Set value push the
o
or
n
arrows within 10s.
4.
To memorise the new set point value push the
SET
key again or wait 10s.
6.4
HOW TO START A MANUAL DEFROST
Push the
DEF
key for more than 2 seconds and a manual defrost will
start.
6.5
HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
1.
Enter the Programming mode by pressing the
Set
+
n
keys for 3s (the “
°C” or “°F”
LED
starts blinking).
2.
Select the required parameter. Press the “
SET
” key to display its value
3.
Use “
UP
” or “
DOWN
” to change its value.
4.
Press “
SET
” to store the new value and move to the following parameter.
To exit
: Press
SET + UP
or wait 15s without pressing a key.
NOTE
: the set value is stored even when the procedure is exited by waiting the time-out to
expire.
6.6
THE HIDDEN MENU
The hidden menu Includes all the parameters of the instrument.
6.6.1 HOW TO ENTER THE HIDDEN MENU
1.
Enter the Programming mode by pressing the
Set
+
n
keys for 3s (the “
°C” or “°F”
LED
starts blinking).
2.
Released the keys, then push again the Set+
n
keys for more than 7s. The Pr2 label will
be displayed immediately followed from the HY parameter.
NOW YOU ARE IN THE HIDDEN MENU.
3.
Select the required parameter.
4.
Press the “
SET
” key to display its value
5.
Use
o
or
n
to change its value.
6.
Press “
SET
” to store the new value and move to the following parameter.
To exit
: Press
SET +
o
or wait 15s without pressing a key.
NOTE1:
if none parameter is present in Pr1, after 3s the “noP” message is displayed. Keep
the keys pushed till the Pr2 message is displayed.
NOTE2
: the set value is stored even when the procedure is exited by waiting the time-out to
expire.
6.6.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO
THE FIRST LEVEL AND VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST
LEVEL” (user level) by pressing
“SET +
n
”
.
In HIDDEN MENU when a parameter is present in First Level the decimal point is on.
6.7
HOW TO LOCK THE KEYBOARD
1.
Keep pressed for more than 3 s the
UP
+
DOWN
keys.
2.
The “POF” message will be displayed and the keyboard will be locked. At this point it will
be possible only to see the set point or the MAX o Min temperature stored
3.
If a key is pressed more than 3s the “POF” message will be displayed.
6.8
TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the
o
and
n
keys, till the
“Pon”
message will be
displayed.
6.9
THE CONTINUOUS CYCLE
When defrost is not in progress, it can be activated by holding the “
o
” key pressed for about
3 seconds. The compressor operates to maintain the “
ccS
” set point for the time set through
the “
CCt
” parameter. The cycle can be terminated before the end of the set time using the
same activation key “
o
” for 3 seconds.
6.10
THE ON/OFF FUNCTION
With “
onF = oFF
”, pushing the
ON/OFF
key, the instrument is switched off. The
“OFF”
message is displayed. In this configuration, the regulation is disabled.
To switch the instrument on, push again the ON/OFF key.
WARNING: Loads connected to the normally closed contacts of the relays are always
supplied and under voltage, even if the instrument is in stand by mode.
7.
PARAMETERS
rtc Real time clock menu:
to set the time and date and defrost start time.
REGULATION
Hy Differential
: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor
Cut IN is Set Point + differential (Hy). Compressor Cut OUT is when the temperature
reaches the set point.
LS Minimum set point:
(- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point.
US Maximum set point:
(SET÷110°C/ SET÷230°F). Set the maximum value for set point.
Ot Thermostat probe calibration
: (-12.0÷12.0°C; -120÷120°F) allows to adjust possible
offset of the thermostat probe.
P3P Third probe presence (P3): n
= not present:, the terminal operates as digital input.;
y=
present:, the terminal operates as third probe.
O3 Third probe calibration (P3):
(-12.0÷12.0°C; -120÷120°F). allows to adjust possible
offset of the third probe.
P4P Fourth probe presence
: (n = Not present; y = present).
o4 Fourth
probe
calibration
: (-12.0 12.0°C) allows to adjust possible offset of the fourth
probe.
OdS Outputs activation delay at start up:
(0÷255min) This function is enabled at the initial
start up of the instrument and inhibits any output activation for the period of time set in
the parameter.
AC Anti-short cycle delay
: (0÷50 min) minimum interval between the compressor stop and
the following restart.
CCt Compressor ON time during continuous cycle:
(0.0÷24.0h; res. 10min) Allows to set
the length of the continuous cycle: compressor stays on without interruption for the CCt
time. Can be used, for instance, when the room is filled with new products.
CCS Set point for continuous cycle:
(-50÷150°C) it sets the set point used during the
continuous cycle.
COn Compressor ON time with faulty probe:
(0÷255 min) time during which the
compressor is active in case of faulty thermostat probe. With COn=0 compressor is always
OFF.
COF Compressor OFF time with faulty probe:
(0÷255 min) time during which the
compressor is OFF in case of faulty thermostat probe. With COF=0 compressor is always
active.
CH Type
of
action:
CL = cooling; Ht = heating.
DISPLAY
CF Temperature measurement unit: °C=
Celsius;
°F
=Fahrenheit. WARNING: When the
measurement unit is changed the SET point and the values of the parameters Hy, LS,
US, Ot, ALU and ALL have to be checked and modified if necessary).
rES Resolution (for °C)
: (in = 1°C; dE = 0.1 °C) allows decimal point display.
dLy Display delay:
(0 ÷20.0m; risul. 10s) when the temperature increases, the display is
updated of 1 °C/1°F after this time.
DEFROST
EdF Defrost mode:
rtc
=
Real Time Clock mode
. Defrost time follows
Ld1÷Ld6
parameters on workdays
and
Sd1÷Sd6
on holidays.
in
=
interval mode
. The defrost starts when the time “
Idf
” is expired.
IdF Interval between defrost cycles
: (0÷120h) Determines the time interval between the
beginning of two defrost cycles.
MdF (Maximum) length for defrost
: (0÷255min) When
P2P = n
, (not evaporator probe:
timed defrost) it sets the defrost duration, when
P2P = y
(defrost end based on
temperature) it sets the maximum length for defrost.
dFd Temperature displayed during defrost
: (
rt
= real temperature;
it
= temperature at
defrost start;
SEt
= set point;
dEF
= “dEF” label)
dAd MAX display delay after defrost
: (0÷255min). Sets the maximum time between the end
of defrost and the restarting of the real room temperature display.
ALARMS
ALC Temperature alarms configuration:
(Ab; rE)
Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. rE =
temperature alarms are referred to the set point. Temperature alarm is enabled when the
temperature exceeds the “SET+ALU” or “SET-ALL” values.
ALU MAXIMUM temperature alarm
: (SET÷110°C; SET÷230°F) when this temperature is
reached the alarm is enabled, after the “ALd” delay time.
ALL Minimum temperature alarm
: (-50.0 ÷ SET°C; -58÷230°F when this temperature is
reached the alarm is enabled, after the “ALd” delay time.
AFH Differential for temperature alarm recovery:
(0,1÷25,5°C; 1÷45°F) Intervention
differential for recovery of temperature alarm.
ALd Temperature alarm delay
: (0÷255 min) time interval between the detection of an alarm
condition and alarm signalling.
dAO Exclusion of temperature alarm at startup
: (from 0.0 min to 23.5h) time interval
between the detection of the temperature alarm condition after instrument power on and
alarm signalling.
CONDENSER TEMPERATURE ALARM (detected by the fourth probe)
AP2 Probe selection for temperature alarm of condenser: nP
= no probe;
P1
=thermostat
probe;
P2 =
evaporator probe;
P3
=configurable probe;
P4
= Probe on Hot Key plug.
AL2 Low temperature alarm of condenser
: (-55÷150°C) when this temperature is reached
the LA2 alarm is signalled, possibly after the Ad2 delay.
Au2 High temperature alarm of condenser
: (-55÷150°C) when this temperature is reached
the HA2 alarm is signalled, possibly after the Ad2 delay.
AH2 Differential for temperature condenser alarm recovery
: (0,1÷25,5°C; 1÷45°F)
Ad2 Condenser temperature alarm delay
: (0÷255 min) time interval between the detection
of the condenser alarm condition and alarm signalling.
dA2 Condenser temperature alarm exclusion at start up
: (from 0.0 min to 23.5h, res.
10min)
Содержание SF SERIES
Страница 1: ...Service Manual SF MODELS...
Страница 2: ...o SF 150 500 i i 2 HC HC 5b 5c 5d 5e 5f...
Страница 30: ...30 5c Compressor data SF150...
Страница 31: ...31...
Страница 32: ...32 5c Compressor data SF500...
Страница 33: ...33...
Страница 47: ...47...