Name
Range
Step
Default
Description
Active energy deadband 0.1…1000.0kWh 0.1kWh 2kWh
Determines the data reporting deadband settings for this
measurement.
Reactive
energy deadband
0.1…1000.0kVar 0.1kVar 2kVar
Determines the data reporting deadband settings for this
measurement.
Active power deadband
0.1…1000.0kW
0.1kW
2kW
Determines the data reporting deadband settings for this
measurement.
Reactive
power deadband
0.1…1000.0kVar 0.1kVar 2kVar
Determines the data reporting deadband settings for this
measurement.
Apparent
power deadband
0.1…1000.0kVA
0.1kVA
2kVA
Determines the data reporting deadband settings for this
measurement.
Power factor deadband
0.01…0.99
0.01
0.05
Determines the data reporting deadband settings for this
measurement.
Frequency deadband
0.01…1.00Hz
0.01Hz
0.1Hz
Determines the data reporting deadband settings for this
measurement.
Current deadband
0.01…50.00A
0.01A
5A
Determines the data reporting deadband settings for this
measurement.
Residual
current deadband
0.01…50.00A
0.01A
0.2A
Determines the data reporting deadband settings for this
measurement.
Voltage deadband
0.01…5000.00V
0.01V
200V
Determines the data reporting deadband settings for this
measurement.
Residual
voltage deadband
0.01…5000.00V
0.01V
200V
Determines the data reporting deadband settings for this
measurement.
Angle
measurement deadband 0.1…5.0deg
0.1deg
1deg
Determines the data reporting deadband settings for this
measurement.
Integration time
0…10 000ms
1ms
0ms
Defines the integration time of the protocol. If this
parameter is set to "0 ms", no integration time is in use.
Reconfigure GOOSE
0: -
1: Reconfigure
-
0: -
Reconfigures the GOOSE.
Enable GOOSE
subscriber
0: Disabled
1: Enabled
-
0:
Disabled Enabled and disables the GOOSE subscriber.
For more information on the IEC 61850 communication protocol support, please refer to the
conformance statement documents (
→
AQ-200 series
→
Resources).
6.1.5 GOOSE
Arcteq relays support both GOOSE publisher and GOOSE subscriber. GOOSE subscriber is enabled
with the "GOOSE subscriber enable" parameter at
Communication
→
Protocols
→
IEC 61850/
GOOSE. The GOOSE inputs are configured using either the local HMI or the AQtivate software.
There are up to 64 GOOSE inputs available for use. Each of the GOOSE inputs also has a
corresponding input quality signal which can also be used in internal logic. The quality is good, when
the input quality is low (that is, when the quality is marked as "0"). The value of the input quality can
increase as a result of a GOOSE time-out or a configuration error, for example. The status and quality
of the various logical input signals can be viewed at the
GOOSE IN status and GOOSE IN quality tabs
at
Control
→
Device I/O
→
Logical signals.
GOOSE input settings
The table below presents the different settings available for all 64 GOOSE inputs.