Figure. 7.2 - 145. Application example and its connections.
7.3 Two-phase, three-wire ARON input connection
This chapter presents the two-phase, three-wire ARON input connection for any AQ-200 series IED
with a current transformer. The example is for applications with protection CTs for just two phases. The
connection is suitable for both motor and feeder applications.
Figure. 7.3 - 146. ARON connection.
A
AQ
Q-S215
-S215
Instruction manual
Version: 2.04
244