Figure. 5.5.7. - 156. Different states of the system
Measured input values
Analog voltage measurement values are used for the function block. Function block utilizes always
peak-to-peak measurement from samples and the monitored magnitude is fundamental frequency
RMS values.
Table. 5.5.7. - 207. Analogic magnitudes used by the SYN function.
Signal
Description
Time base
U
1
RMS
Fundamental RMS measurement of voltage U
1
/V
5 ms
U
2
RMS
Fundamental RMS measurement of voltage U
2
/V
5 ms
U
3
RMS
Fundamental RMS measurement of voltage U
3
/V
5 ms
U
4
RMS
Fundamental RMS measurement of voltage U
4
/V
5 ms
Function blocking
In the blocking element the block signal is checked in the beginning of each program cycle. Blocking
signal is received from the blocking matrix for the function dedicated input. If the blocking signal is not
activated when the synchronization is ok, a SYN OK signal is generated.
If blocking signal is active when SYN OK activates a BLOCKED signal will be generated and the
function shall not process the situation further. If SYN OK function has been activated before blocking
signal it will reset.
From blocking of the function a HMI display event as well as time stamped blocking event with
information of the startup voltage values and fault type is issued.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
258