Figure. 5.5.5. - 146. Example of timers and pick-up parameters. No inrush current detected in the starting.
CLPU activates after current has been under ILow setting for time Tset. When current exceed the ILow
setting but not IHigh the CLPU signal is active until the Tmin time. If no inrush is noticed during the Tmin
time the CLPU signal is released.