OPTIMA PS1 PELLET STOVE
10
10
RESIDENTIAL & MOBILE HOME INSTALLATION
MINMUM CLEARANCES TO COMBUSTIBLE MATERIALS
SIDEWALL
A - 229 mm / 9”
BACKWALL
B - 76 mm / 3”
CORNER
C - 26 mm / 1”
MAXIMUM ALCOVE DEPTH: 915 mm / 36” with minimum back wall clearance or front of
stove door recessed a maximum of 178mm / 7” into alcove.
MINIMUM ALCOVE CEILING HEIGHT:1220 mm / 48” OR MINIMUM 381 mm / 15”
CLEARANCE FROM TOP OF STOVE TO CEILING.
CLEARANCE TO VENT PIPE MUST ALSO BE OBSERVED. PLEASE SEE VENT
MANUFACTURES’ INSTRUCTIONS FOR VENT PIPE CLEANRANCE TO COMBUSTIBLES.
NOTE—Even though the pellet stove is safe to install to the minimum clearances listed
above, additional clearances should be considered for the ease of fueling, operating
and maintenance.
The floor pad (ember pad) must be of non-
combustible material and must extend 6" (153mm)
in front of the door opening and 6" (153mm) to the
sides and rear of the unit.
If the listed stove clearance is less than the
required floor pad, use the stove listing. Contact
your local Authority Having Jurisdiction and/or the
CSA B365 in Canada or NFPA 211 in USA for
more details.
Hearth pad should also extend beneath the
horizontal or vertical vent.
(229mm)
(229mm)
(76mm)
(76mm)
(76mm)
(26mm)
(26mm)
(51mm)
(51mm)
(153mm)
(153mm)
(153mm)
(902mm)
(813mm)