Operation
13
3.
During the time this display is present, press the "HOLD" key.
The next selection will appear, which is "CT: 2A DIRECT". If
this is the desired selection, do nothing; the new value will be
incorporated, and the unit will be ready for use.
4.
If another value is desired, press "HOLD" again while the CT
selection display is still present.
5.
This key sequence can be continued, as necessary, to scroll
through all of the choices, which are available.
A standard Model 918B is equipped to use the following current
transformers:
20A CLAMP-ON, Standard CT
Calibrated for the standard (Model 09111A) clamp-on 1000:1 20A
current transformer. Note: The calibration constants for this
configuration apply specifically to the 20A clamp-on CT supplied
with, and having the same serial number as the 918B. Use of other
CTs may result in reduced accuracy.
2A DIRECT, Accessory CT
Calibrated for the Arbiter Systems 09182A 100:1 2.0A plug-in
current transformer.
20A DIRECT, Accessory CT
Calibrated for the Arbiter Systems 09182B 1000:1 20A plug-in
current transformer.
1000A CLAMP, Accessory CT
Calibrated for the combination of an Arbiter Systems Model
09113A and Model 09182A. This combination provides clamp-on
measurement capability for currents of up to 1000A.
NOTE
When a Model 918B Phase Angle Multimeter is ordered and
shipped from the factory with additional current transformers, a