background image

AquaBreak Series  

Page 

5

 of 

18

 

AquaTech-Pressmain Instruction Manual\AquaBreak 

0.2.7

 

If the equipment were to be stored or taken out of service for a period of time (e.g. 1 week or more), 
then we would recommend draining the equipment of all water/liquid (with due regard to any local 
regulations) to prevent frost damage to components. When restarting is required we would 
recommend commissioning by our authorised service agent. 

0.2.8

 

Ensure the base/foundation/plinth/wall to which the equipment is to be attached has sufficient mass 
compared to the equipment, in order to avoid noise/vibration transmission. E.g. the mass of the base 
should be at least five times the mass of the equipment. 

0.2.9

 

Ensure the electrical supply is the correct voltage, current, frequency and type for the equipment 
supplied and that suitable circuit protection equipment is installed in the supply. Incorrect electrical 
installation could be an electric shock/burns/fire hazard. 

0.2.10

 

When accessing the control panel to make electrical connections adopt anti‐static procedures e.g. 
wear anti‐static earthed wristband, to avoid risk of damaging the controller. 

0.2.11

 

All products that are packaged to include Pressure vessel(s)/Hydraulic Accumulator(s)/Expansion 
Vessel(s) are classed as “Assemblies” under the Pressure Equipment Directive (PED). Where units are 
despatched with “Loose” vessel(s) for assembly on site it is absolutely essential that they be installed 
as detailed in the instructions using the fittings provided where appropriate. Failure to observe this 
will nullify compliance with the PED and may present a safety hazard. Your warranty may also be 
affected. 

0.2.12

 

Where Hydraulic Accumulator(s)/Expansion Vessel(s) are supplied as a loose item, they must be 
installed/connected correctly before operating the equipment, otherwise serious damage from over‐
pressure/pump overheating could occur. 

0.2.13

 

Do not operate this equipment/pumpset prior to commissioning (section 2.2) This could cause 
irreparable damage to equipment/pumpset/pipework/system components. 

0.2.14

 

Isolate the equipment/pumpset before pressure testing system. Excess pressure could irreparably 
damage the pressure transducer, pressure switches (where fitted) and the diaphragms of pressure 
vessel/hydraulic accumulators. 

0.2.15

 

It is the installers’ responsibility to ensure subsequent pipework etc can accept the pressures 
generated by the equipment/pumpset and to install an overpressure safety device into the system 
with due respect to the suction pressure present on the pumpset, the pump closed valve pressure 
stated on the pump, the maximum working pressure stated on any of the attached pressure vessels 
and any other device connected to the system e.g. boilers, calorifiers etc. 

0.2.16

 

When chlorination of the system is carried out,

 

ensure that any residual chlorine is removed by 

thorough flushing as detailed in the HSE approved code of practice L8, to avoid damaging the 
equipment/pumpset. The normal level of chlorination is up to 2 parts per million (ppm), but shock 
dosing for sterilization purposes, at 25‐50 ppm for 24‐48 hours is acceptable as long as all chlorine is 
removed once the process is complete. Chlorination beyond these limits could seriously damage 
pumpset components and WILL NOT be covered by the warranty. 

0.2.17

 

The installer/user is responsible for the installation of the correct earthing and protection according to 
valid national and local standards. All operations must be carried out by a suitably qualified person. 

0.2.18

 

The equipment is only suitable for earth referenced supplies and must be permanently earthed to 
avoid electric shock hazard. 

0.2.19

 

The equipment must be permanently earthed with appropriate sized Earthing. 

0.2.20

 

We recommend the use of a 30mA RCD to provide electrical safety. 

0.2.21

 

Never perform high voltage resistance tests on control panels, variable speed drives/motors without 
first disconnecting the panel/drive/motor from the circuit being tested as this will damage the built in 
electronic components. 

0.2.22

 

Metal parts (e.g. heat sinks) may reach temperatures of 90 degrees centigrade. 

0.2.23

 

Where “Expansion vessels” are used on Domestic hot water systems (DHWS) or LTHW heating system 
pressurisation units, the temperature of the fluid returning to the vessels should not exceed 70 
degrees Centigrade as this could damage the vessel diaphragm. Where the temperature exceeds 70C 
an intermediate cooling vessel should be fitted. 

0.2.24

 

Where “Expansion vessels” are used on Domestic hot water systems (DHWS) or LTHW heating system 
pressurisation units, the glycol content in the water must not exceed 50%. 

0.2.25

 

Drain cocks/valves and air bleed screws must not be left open as this could cause flooding. 

Содержание AquaBreak AB5

Страница 1: ...BREAKTANK PUMPSET FOR BACKFLOW PROTECTION TO FLUID CATEGORY 5 ISSUE 3 18 07 2017 Head Office AGM House London Rd Copford Colchester Essex CO6 1GT UK Tel 01206 215121 Email aftersales agm plc co uk Man...

Страница 2: ...NANCE 6 1 INSTALLATION INSTRUCTIONS 7 1 1 ADDITIONAL WARNINGS 7 1 2 ADDITIONAL CAUTIONS 7 1 3 PROCEDURE 7 1 3 1 OFF LOADING AT SITE 7 1 3 2 LOCATION 8 1 3 3 FIXING 8 1 3 4 PIPEWORK 9 1 3 5 FLOW THROUG...

Страница 3: ...ions PSSR and the Owner User should be made aware of their responsibility for this see section 3 Servicing Failure to install operate use maintain the equipment as recommended below could cause damage...

Страница 4: ...it will contain under worst case fault conditions E g fully saturated pressure vessel with no air charge break tank full to overflowing etc Failure to observe this could cause serious mechanical dama...

Страница 5: ...accumulators 0 2 15 It is the installers responsibility to ensure subsequent pipework etc can accept the pressures generated by the equipment pumpset and to install an overpressure safety device into...

Страница 6: ...nning causing pump seal damage and water leakage 0 3 8 Do no attempt to start pumps without liquid in volutes pumps must be fully primed see 1 2 2 mechanical seals must have a film of liquid between f...

Страница 7: ...pplied as loose item is installed in the breaktank overflow warning pipe see fig 1 3 1 2 4 Mains water pressure to unit should be between 1 0 and 3 0Bar Ensure a pressure reducing valve set at a maxim...

Страница 8: ...a minimum distance of 500mm all round There must be sufficient room to fully open panel door lift and withdraw pumps withdraw diaphragms from vessels Any Hydraulic Accumulator supplied should be loca...

Страница 9: ...it an extra non return valve to the discharge as it may interfere with the correct operation of the non return valve already fitted as standard in the pumpset 1 3 4 5 Connect site pipework to mains wa...

Страница 10: ...ure to the correct level see section 2 4 dependent on the application required for the vessel Refer to the Operating parameters at the back of this manual or contact Aquatech Pressmain for advice 1 3...

Страница 11: ...eak Tank Stop Start Filling Solenoid Probes B3 B2 B1 B2 B3 B1 Level Control Relay set to FS filling short delay medium sensitivity 75k range 5k 150k Solenoid Valve n c min com max SV1 LR1 A1 A1 14 14...

Страница 12: ...authorised AquaTech Pressmain agent This Assurance does not apply to those items not supplied by us or to defects arising from parts not made or approved by AquaTech Pressmain The individual manufactu...

Страница 13: ...ss of all mechanical and electrical connections to ensure they have not loosened during transit 2 2 5 with the pumpset switched off IS1 and the motor circuit breaker switched off CB1 close the dischar...

Страница 14: ...all or floor mounted 2 3 3 1 For normal operation all pumpset inlet and discharge valves should be left open all hydraulic accumulator expansion vessel isolating valves should be left open and drain c...

Страница 15: ...onds and switch power on again to reset control relay No water pump does run Pump air locked Vent prime pump to remove all air Check pump suction strainer inlet filter Reduced intermittent flow Pump p...

Страница 16: ...any build up of debris Fig 2 1 Pump inlet filter suction strainer Mains water inlet strainer The mains water inlet strainer should be regularly checked to remove any build up of debris Fig 2 2 Mains w...

Страница 17: ...s Its specialist fields are Pressure booster equipment and sealed systems for heating and chilled water distribution systems Regular servicing of any plant for essential services is vital because wear...

Страница 18: ...ter Essex CO6 1GT UK Telephone 01206 215121 OPERATING PARAMETERS SERIAL No MODEL AB5 THE SERIAL MODEL NUMBERS MUST BE QUOTED WHEN REQUESTING ASSISTANCE ELECTRICAL DATA Supply 230 volts 1 Ph 50 Hz Full...

Отзывы: