Aqua-Swirl

®

  

Stormwater Treatment System

 

 

Inspection and Maintenance Manual 

 
 

 

 
 
 
 

AquaShield

TM

, Inc.  

2733 Kanasita Drive 

Suite 111 

Chattanooga, TN  37343 

Toll free (888) 344-9044 

Phone: (423) 870-8888 

Fax: (423) 826-2112 

Email: [email protected] 

www.aquashieldinc.com

  

 
 
 

November 2016 

 

Содержание Aqua-Swirl

Страница 1: ...Stormwater Treatment System Inspection and Maintenance Manual AquaShieldTM Inc 2733 Kanasita Drive Suite 111 Chattanooga TN 37343 Toll free 888 344 9044 Phone 423 870 8888 Fax 423 826 2112 Email info...

Страница 2: ...ype hydrodynamic separator designed and supplied by AquaShieldTM Inc AquaShieldTM Aqua Swirl technology removes pollutants including suspended solids debris floatables and free floating oil from storm...

Страница 3: ...ate to the center of the chamber where velocities are the lowest The treated flow then exits the Aqua Swirl behind the arched outer baffle The top of the baffle is sealed across the treatment channel...

Страница 4: ...formance of any stormwater treatment structure including manufactured or land based systems depends on a consistent maintenance plan Inspection and maintenance functions are simple and easy for the Aq...

Страница 5: ...n Procedure To inspect the Aqua Swirl a hook is typically needed to remove the manhole cover AquaShieldTM provides a customized manhole cover with our distinctive logo to make it easy for maintenance...

Страница 6: ...Cleanout Procedure Cleaning the Aqua Swirl is simple and quick Free floating oil and floatable debris can be observed and removed directly through the 30 inch service access riser provided A vacuum t...

Страница 7: ...tasks Disposal of Recovered Materials AquaShieldTM recommends that all maintenance activities be performed in accordance with appropriate health and safety practices for the tasks and equipment being...

Страница 8: ...oil due to the dark body of the surrounding structure Oil may appear darker than water in the system and is usually accompanied by oil stained debris e g Styrofoam etc The depth of oil can be measure...

Страница 9: ...the presence of known contaminants may necessitate that appropriate actions be taken to clean and dispose of materials captured and retained by the Aqua Swirl All cleaning activities should be perfor...

Страница 10: ...IV Bypass Structures Bypass structures should be inspected whenever the Aqua Swirl is inspected Maintenance should be performed on bypass structures as needed MAINTENANCE COMPANY INFORMATION Company...

Страница 11: ...ogging Yes No Describe Other Observations NOTES Additional Comments and or Actions To Be Taken Time Frame ATTACHMENTS Attach site plan showing Aqua Swirl location Attach detail drawing showing Aqua Sw...

Страница 12: ...as needed X X X X Clean System X The Aqua Swirl should be cleaned once a year regardless of whether it has reached full pollutant storage capacity Second and Subsequent Years Post Construction Month...