![Aquamatic Aquacell P2 Series Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/aquamatic/aquacell-p2-series/aquacell-p2-series_user-manual_2960285044.webp)
OP
ERA
TION
4.8
SYSSAM12
MAXIMUM SAMPLES
0100
Set maximum allowable number of samples
➔
See SYSSAM13
SYSSAM13
PRE PURGE
03 SEC
The time required, to expel the standing column of water
in the submerged sample Intake Hose prior to the sample
shot being collected
The PRE PURGE time should be long enough to ensure
that water is expelled from the Intake Hose followed by
bubbles emitted from the end of the Intake Hose for
approximately 2 seconds
➔
See SYSSAM14
SYSSAM14
POST PURGE
06 SEC
The time required, to expel the risen column of water from
the submerged sample Intake Hose. The POST PURGE
time should be long enough to ensure that water is
expelled from the Intake Hose followed by bubbles emitted
from the end of the Intake Hose for approximately 2
seconds
➔
See SYSSAM15
SYSSAM15
TIME OUT LIMIT
060 SEC
The period for which the Sampler will attempt to draw the
effluent up the Intake Hose can be varied to suit the
application. Maximum 199 seconds
➔
See SYSSAM16
SYSSAM16
SYSTEM SETTINGS
INSTALLED
Information screen only
➔
See SETPROG if Bottler not fitted
➔
See SYSBOT1 if Bottler is fitted
SYSBOT1
BOTTLER SETTINGS
> > > > > > >
Information screen only
➔
See SYSBOT2
SYSBOT2
BOTT LOCATIONS
24 [etc]
Set according to bottler format
➔
See SYSBOT3
SYSBOT3
RE-CYCLE
[NO]
YES
Bottler can either stop on last bottle or continue on to
Bottle 1 and repeat its cycle continuously
➔
See SYSBOT4
SYSBOT4
BOTTLER MODE
SINGLE
[GROUP]
In SINGLE mode each bottle is addressed individually
according to the program selected. In GROUP mode a
nominally identical sample is deposited into each bottle of
a group simultaneously* - Perhaps a bottle for each
interested party, or possibly a separate bottle for each
determinant (necessary where preservative dosing of the
sample is required for example)
➔
See SYSBOT7 if SINGLE
➔
See SYSBOT5 if GROUP
SYSBOT5
BOTTLES/GROUP
2
[
other group sizes
]
Select number of bottles to be addressed simultaneously*
(2, 3, 4, 6, 8, 12 or 24). This number must be a factor or
equal to the number of specified bottle locations
➔
See SYSBOT6
Содержание Aquacell P2 Series
Страница 1: ...AQUACELL PORTABLE WASTEWATER SAMPLERS USER GUIDE Sira MC 050059 Issue 20 2...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ...CONTENTS OF PACKAGE 1 2...
Страница 14: ...CONTENTS OF PACKAGE 1 8...
Страница 16: ...INTRODUCTION 2 2...
Страница 26: ...INSTALLATION 3 2...
Страница 36: ...INSTALLATION 3 12...
Страница 38: ...OPERATION 4 2...
Страница 56: ...OPERATION 4 20...
Страница 58: ...MAINTENANCE 5 2...
Страница 70: ...TECHNICAL SPECIFICATION 6 2...
Страница 77: ......