Page 4

Important information

Safety information

This product must be installed by a competent person in accordance with all relevant current Water Supply Regulations.

ALL PRODUCTS REQUIRING AN ELECTRICAL CONNECTI0N MUST BE INSTALLED BY A QUALIFIED PERSON
FOLLOWING THE LATEST REVISION OF BS 7671 (WIRING REGULATIONS) AND CERTIFIED TO CURRENT BUILDING
REGULATIONS.

This system should be installed so that other taps or appliances operated elsewhere within the premises do not
significantly affect the flow.

The Digital Bath must not be used with a hot water supply temperature of over 65ºC.

The processor is supplied factory pre-set at maximum temperature of 45ºC. The maximum temperature is fully
adjustable to suit site conditions. If adjusted, we recommend the outlet temperature is set to a MAXIMUM of 46ºC.

THE DIGITAL PROCESSOR MUST BE INSTALLED IN AN ACCESSIBLE LOCATION FOR SERVICING AND MAINTENANCE.

The Digital processor must not be installed in situations where either the ambient temperature is likely to exceed 40ºC
or where freezing may occur.

The control must not be installed in situations where the ambient temperature is likely to fall below 5ºC or rise above
40ºC.

We do not recommend the use of HiQu Digital in steam therapy facilities.

This appliance must be earthed.

Cables which are chased into the wall must be protected by a suitably sized conduit or sheathing to allow for
removal in the event of service and maintenance purposes. Ensure that the conduit is run to avoid the controller
fixing holes.

Surface mounted cables must also be protected by a suitable approved conduit, even in a loft, where there may be
a risk of damage from vermin.

The power lead must only be replaced by the manufacturer or his accredited agent.

The user control is supplied from a safety low voltage source.

This product is suitable for domestic use only.

HiQu Digital is supplied complete with a 5 year guarantee.

This product is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities or lack of experience and knowledge, unless they have been given initial supervision or instruction
concerning the use of the product by a person responsible for their safety.

Children should be supervised to ensure they do not play with the product.

Installation of Digital pumped processor (for gravity stored systems)

The HiQu Digital pumped bath system is designed to operate up to maximum static pressure of 100kPa
((1 bar)(10 metres head)(14.5psi)).

Under no circumstances must the pumped processor be connected directly to the water main or in line with
another booster pump.

The minimum actual capacity of the cold water storage cistern should be not less than 225 litres (50 gallons).
The capacity of the hot water cylinder must be capable of meeting anticipated demand.

Содержание HiQu

Страница 1: ...HiQu Digital Bath installation instructions Page 1 HiQu Digital Bath Installation guide...

Страница 2: ...HiQu Digital Bath installation instructions Page 2 HiQu Digital Digital Bath HiQu Digital Bath...

Страница 3: ...Components HP Combi Literature not shown Literature not shown Components Gravity Pumped HiQu Digital Bath installation instructions Page 3...

Страница 4: ...rthed Cables which are chased into the wall must be protected by a suitably sized conduit or sheathing to allow for removal in the event of service and maintenance purposes Ensure that the conduit is...

Страница 5: ...n ended 2 5 bar pump should be used The minimum actual capacity of the cold water storage cistern should be not less than 225 litres 50 gallons The capacity of the hot water cylinder must be capable o...

Страница 6: ...t is essential that the written in structions overleaf are read and understood and that you have all the necessary components shown overleaf before com mencing installation The HiQu Digital Bath syste...

Страница 7: ...indicate direction of flow Compression fittings should not be used on the inlet and outlet spigots and may affect warranty if fitted Choose the position for your Digital processor as close to the bath...

Страница 8: ...y pipes 5 The maximum hot water inlet temperature must be no more than 65 C Attach the supply pipes to the Digital processor ensuring that the cold and hot feeds are fitted into the appropriately mark...

Страница 9: ...set aside 8 Place the bath control back plate onto the finished wall surface in the desired location and mark the fixing and data cable entry points 9 Connect the data cable to the rear of the control...

Страница 10: ...BEFORE ANY ELECTRICAL ADJUSTMENT IS ATTEMPTED THE ELECTRICITY SUPPLY MUST BE TURNED OFF AT THE MAINS SWITCH ELECTRICAL INSTALLATION MAY ONLY BE CARRIED OUT BY A QUALIFIED PERSON Connect the outlet pi...

Страница 11: ...recommend protecting surface mounted cables in suitable ap proved conduit to avoid the risk of damage from vermin The data cable and power lead should also be clipped in place with P clips or similar...

Страница 12: ...N BOILER SYSTEMS For Standard Digital processors installed on combi boiler systems for op timum performance we recommend setting the flow rate to the COMBI mode 18 N B The ECO flow rate mode should no...

Страница 13: ...t bladed screwdriver using the MAX TEMP ADJUSTMENT control as indicated When the temperature has been set to the desired position carefully replace the Digi tal processor lid and secure the fixing han...

Страница 14: ...purposes The company reserves the right to alter change or modify the product specifications without prior warning Registered Trademark Aqualisa Products Limited The Waste Electrical and Electronic E...

Отзывы: