Heat Pump Won’t Shut Off
PLEASE NOTE
When heat pump is set to "
OFF
", the display will show either the water temperature or
FLO
.
1. Confirm the heat pump has reached the desired temperature set on the thermostat. The heat pump will continue to
run until the set temperature is reached.
2. If the heat pump is using an external controller, it may not be set correctly.
l
See "Operating Heat Pump (With an External Controller)" on page 1.
Heat Pump Is Running, Not Heating
1. If the heat pump is using an external controller, confirm it is set correctly.
l
See "Operating Heat Pump (With an External Controller)"
l
If the heat pump is still not running correctly with this device, contact the installer of the external controller
device or the device’s manufacturer for further assistance.
2. Confirm heat pump mode is set to
HEA
operating mode.
3. Confirm thermostat is set to the desired water temperature.
4. Confirm valves are correctly positioned to heat the correct body of water (either the pool or the spa). If heating a
spa that overflows into a pool, confirm the spa is isolated when being heated (not flowing into the pool).
5. Confirm heat pump is transferring heat into the water.
l
Measure the temperature of air discharge coming out of the heat pump fan. If discharge air is between 8° to
10° colder than the outside ambient air, the heat pump is moving heat into the water.
6. If an error code is displayed, diagnose and correct cause of code. See "Fault Codes" on page 31.
7. Confirm that filter pump has a sufficient run-time. The heat pump will not run (or heat the water) without water
flow. Heat Pump equipment will generally be set to run 24 hours a day in commercial applications.
8. If heating a spa, deactivate air blower or venturi (if equipped) to allow for quicker heating times. For pools,
deactivate water features, such as slides, waterfalls, or fountains to allow water to retain heat. Use of a liquid pool
blanket product can also compensate for excessive heat loss.
l
See Available Accessories on page 28 for more information on liquid blankets.
Heat Pump Is Running, Not Cooling (Reversing Models)
1. If the heat pump is using an external controller, confirm the heat pump is programmed properly to allow for
cooling.
See "Operating Heat Pump (With an External Controller)" on page 1.
2. Confirm the heat pump mode is set to
COO
operating mode.
3. Confirm the thermostat is set below the current water temperature.
4. Confirm valves are correctly positioned to cool the correct body of water (either the pool or the spa). If cooling a
spa that overflows into a pool, confirm the spa is isolated when being cooled (not flowing into the pool).
5. If an error code is displayed, determine and correct the condition causing the code. See "Fault Codes" on page
31.
6. Confirm heat pump is transferring heat out of the water.
l
Measure the temperature of air discharge coming out of heat pump's fan. If the air is between 8° to 10° warmer
than the outside ambient air, the heat pump is moving heat out of the water.
7. Confirm that filter pump has a sufficient run-time. The heat pump will not run (or cool the water) without water
flow. Heat Pump equipment will generally be set to run 24 hours a day in commercial applications.