HC997-999
– MOD. A
INTRODUCTION
Digital multifunction solenoid metering pump
ENGLISH
ADSP9000026
18/09/2015 Rev.1.5
22/100
1.0 INTRODUCTION
The HC997-999 mod. A pump is a metering solenoid pump that can work in constant or proportional by an external
signal. In the bottom of the enclosure there are located an ON/OFF switch and an internal terminal block to connect
the different signals (level probe input, water meter input, flow sensor input, 4÷20mA input and relay output). Once
the pumps is switched on the display show an user menu and is possible to read some information regarding the
functioning mode and the possibility to pause and prime the pump. Thanks to the digital technology with the
microcontroller and an LCD display the HC997-999 pump is easy to program and to save all the statistics.
1.1
D
ESIGN STANDARD
Our pumps are built according to the actual general directives endowed with CE mark in conformity with the
following European directives:
n°
2004/108/CE
“ e s.m.i.
n°
2006/95/CE
“DBT Low Voltage Directive” e s.m.i.
n°
2011/65/UE
,
2012/19/UE
“direttive RoHs e WEEE” e s.m.i.
1.2
T
ECHNICAL FEATURES
Power supply
: 230VAC ± 10%
– 50/60Hz
Consumption
: see table below
Fuse
: 1 A
– Delayed
Degree protection
: IP65
Weight
: 2,5 kg
Overall dimensions
: W 118 x H 205 x D 147 mm
1.3
H
YDRAULIC FEATURES
MODEL
Max flow rate @
Strokes
Volume
Consumption
Size
Head pump
Max pressure
Frequency (max) per stroke
(max)
tubing
connections
L/h
bar
per min.
ml / stroke
watt
mm
model
HC997 - 1
2
8
150
0,22
18
4x6
½" - PVDF
5
5
150
0,56
18
4x6
½" - PVDF
7
2
150
0,77
18
4x6
½" - PVDF
HC997 - 2
7
4
200
0,58
18
4x6
½" - PVDF
8
2
200
0,67
18
4x6
½" - PVDF
10
0
200
0,83
18
4x6
½" - PVDF
HC997 - 3
3
12
120
0,42
22
4x6
½" - PVDF
4
10
120
0,56
22
4x6
½" - PVDF
5
8
120
0,69
22
4x6
½" - PVDF
HC997 - 4
10
4
180
0,93
22
4x6
½" - PVDF
12
2
180
1,11
22
4x6
½" - PVDF
14
0
180
1,30
22
4x6
½" - PVDF
HC997 - 5
2
20
75
0,44
22
4x6
½" - PVDF
2,5
18
75
0,56
22
4x6
½" - PVDF
3
15
75
0,67
22
4x6
½" - PVDF
MODEL
Max flow rate @
Strokes
Volume
Consumption
Size
Head pump
Max pressure
Frequency (max) per stroke
(max)
tubing
connections
L/h
bar
per min.
ml / stroke
watt
mm
model
HC999 - 1
10
10
200
0,83
35
4x6
½"
– PP
12
8
200
1
35
4x6
½"
– PP
14
5
200
1,17
35
4x6
½"
– PP
HC999 - 2
4
20
100
0,67
35
4x6
½" - PP
4,5
18
100
0,75
35
4x6
½"
– PP
5
15
100
0,83
35
4x6
½"
– PP
HC999 - 3
20
5
150
2,22
35
4x6/6x9
½"
– PP
25
3
150
2,78
35
4x6/6x9
½"
– PP
35
1
150
3,89
35
4x6/6x9
½"
– PP
HC999 - 4
35
2
150
3,89
35
10X14
½"
– PVC
45
1
150
5
35
10X14
½"
– PVC
50
0,5
150
5,56
35
10X14
½"
– PVC