 5. MAINTENANCE AND  INSPECTION 

 

 

 

 

5.1  Maintenance

 

Check the water supply device and the release often. You should avoid the condition of no water or 
air entering into system, as this will influence unit's performance and reliability. You should clear the 
pool/spa filter regularly to avoid damage to the unit as a result of the dirty of clogged filter.

 

The area around the unit should be dry, clean and well ventilated. Clean the side heating 
exchanger regularly to maintain good heat exchange as conserve energy .

 

The operation pressure of the refrigerant system should only be serviced by a certified 
technician .

 

Check the power supply and cable connection often,.Should the unit begin to operate 
abnormally, switch it off and contact the qualified technician.

 

 

Discharge all water in the water pump and water system ,so that freezing of the water in the 

pump or water system does not occur. You should discharge the water at the bottom of water 
pump if the unit will not be used for an extended period of time. You should check the unit 
thoroughly  and fill the system with water fully before using it for the first time after a 
prolonged period of no usage.

 

5.2  Trouble Shooting Guide

 

 

 

Malfunction

 

 

Display

 

 

Canse

 

 

Solution

 

 

Water inlet temp. Sensor failure

 

 

P01

 

 

The water inlet temp. Sensor is 

open or shortcircuit

 

 

Check or change thewater 

inlet  temp. Sensor

 

 

Water outlet  temp. Sensor failure

 

 

P02

 

 

The water outlet temp. sensor is 

open or shortcircuit

 

 

Check or change thewater 

outlet  temp. 

S

ensor

 

 

Ambient temp. Sensor failure

 

 

P04

 

 

The ambient temp. sensor is 

open or shortcircuit

 

 

Check or change the 

ambient temp. 

S

ensor

 

 

Pipe temp. Sensor failure

 

 

P05

 

 

The pipe temp. sensor is 

open or short circuit

 

 

Check or change thepipe temp. 

S

ensor

 

 

Evaporator temp.Sensor failure

 

 

P07

 

 

The evaporator temp. Sensor is 

open or shortcircuit

 

 

Check or change the 

evaporator temp. Sensor

 

 

High pressure protect

 

 

E01

 

 

The exhaust pressure ishigh , 

high pressure switch action

 

 

Check high pressure switch 
and cooling return circuit

 

 

Low pressure protect

 

 

E02

 

The suction pressure islow, 
Low pressure switch action

 

 

Check low pressure switchand 
cooling return circuit

 

 

Flow switch failure

 

 

E03

 

 

No water or litterwater in 
water system

 

Check the flow volume,water 
pump is failure ornot

 

Temp. istoo much different 

between water-inlet and outlet

 

 

E06

 

 

Water flow volume not enough,

 

Water system pressure difference is small

 

 

Check the flow volume,water 
system is jammed ornot

 

 

Antifreezing  under  cooling mode

 

 

E07

 

 

Water flow volume not enough

 

 

Check the flow volume,water 
system is jammed ornot

 

 

The primary anti-freezing 

protection start.

 

 

E19

 

 

Ambient temperature is toolow

 

 

 

The second anti-freezing 

protection start

 

 

E29

 

 

Ambient temperature is toolow

 

 

 

Communication failure

 

 

E08

Communication failure between remote 

wire controller andmain board

 

 

Check the wire connection between 

remote wire controller andmain board

 

Содержание PASRW010

Страница 1: ...www aquaworldwoodpools co uk ...

Страница 2: ... Installation of System 7 3 2 Swimming Pool Heat Pumps Location 8 3 3 How Close to Your Pool 8 3 4 Swimming Pool Heat Pumps Plumbing 9 3 5 Swimming Pool Heat Pumps Electrical Wiring 10 3 6 Initial Start up of the Unit 10 4 Usage and Operation 11 4 1 Function of the controller 11 4 2 Usage of the controller 12 4 3 Parameter table 17 5 Maintenance and Inspection 18 5 1 Maintenance 18 5 2 Trouble Sho...

Страница 3: ... according to the recommended time and frequency as stated in this manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperature constant For split type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has fol...

Страница 4: ...Supply 230V 50Hz 230V 50Hz 230V 50Hz Compressor Quantity 1 1 1 Compressor rotary rotary rotary Fan Number 1 1 1 Fan Power Input W 90 90 90 Fan Rotate Speed RPM 850 850 850 Fan Direction horizontal horizontal horizontal Noise dB A 50 49 51 Water Connection mm 50 50 50 Water Flow Volume m3 h 1 5 2 3 3 Water Pressure Drop max kPa 2 2 4 1 8 Unit Net Dimensions L W H mm See the drawing of the units Uni...

Страница 5: ...upply 230V 50Hz Compressor Quantity 1 Compressor rotary Fan Number 1 Fan Power Input W 120 Fan Rotate Speed RPM 850 Fan Direction horizontal Noise dB A 54 Water Connection mm 50 Water Flow Volume m3 h 4 5 Water Pressure Drop max kPa 2 7 Unit Net Dimensions L W H mm See the drawing of the units Unit Ship Dimensions L W H mm See package lable Net Weight kg See nameplate Shipping Weight kg See packag...

Страница 6: ...4 2 SPECIFICATION 2 2 The dimensions for Swimming Pool Heat Pump Unit PASRW010 Water outlet 50 Water inlet 50 ...

Страница 7: ...5 2 SPECIFICATION 2 2 The dimensions for Swimming Pool Heat Pump Unit PASRW015 Water outlet 50 Water inlet 50 ...

Страница 8: ...6 2 SPECIFICATION 2 2 The dimensions for Swimming Pool Heat Pump Unit PASRW020 PASRW030 Water outlet 50 Water inlet 50 ...

Страница 9: ...up the electric box cover Pull on the electric box cover Attention 1 Please be careful when handle with the electric box cover in case of damage 2 During installation to buckle matched with the clamping groove of the electric box cover so that it can cover the electric box cover ...

Страница 10: ... these steps when using for the first time 1 Open valve and charge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary that the water in pipe is higher than the pool surface The schematic diagram is for reference only Please check the water inlet outlet label on the heat pump while plumbing installation Chlorin...

Страница 11: ...k air inlet These locations deny the unit of a continuous source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 3 How Close To Your Pool Normally the pool heat pump is installed within 7 5 metres of the pool The longer the distance from the pool the greater the heat loss from the piping For the most part the piping is buried Therefore the heat loss is minimal for...

Страница 12: ...ting at the unit inlet and outlet to allow easy draining of unit for winterizing and to provide easier access should servicing be required To pool PVC COUPLER RECOMMENDED Provided From pump CONDENSATION DRAIN BARB FTG Condensation Since the Heat pump cools down the air about 4 water may condense on the fins of the horseshoe shaped evaporator If the relative humidity is very high this could be as m...

Страница 13: ...d 3 6 Initial startup of the Unit NOTE In order for the unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger Start up Procedure After installation is completed you should follow these steps 1 Turn on your filter pump Check for water leaks and verify flow to and from the pool 2 Turn on the electrical power supply to the unit then press the key O...

Страница 14: ...o turn on off the unit MODE Mode Press this key to change the working mode CLOCK Timer Press this key to set system time Choose key Press this key to choose the Celsius degree or Fahrenheit degree TIMER ON TIMER ON Press this key to set timer on TIMER OFF TIMER OFF Press this key to set timer off Up Press this key to select the upward option or increase the parameter value Down Press this key to s...

Страница 15: ... switch You can choose unit mode In the unit on or off state you can choose cooling heating or automatic mode by pressing MODE button Attention if the unit is only for heating cooling the mode switching operation is invalid Cooling temp Heating temp 4 2 3 Temperature selection Choose display type of unit temperature when the unit is on press mode button and choose Celsius degree or Fahrenheit degr...

Страница 16: ...the main interface press or and the current mode target temperature flashes then press to increase the temp value or press to decrease it Press MODE can save setting parameter and back to the main interface Press can not save setting parameter but back to the main interface Attention If there is no operation for 5s system would remember parameter setting and back to the main interface Running inte...

Страница 17: ... time minute start to flashing press to increase value or press to decrease value and press CLOCK to save setting Press can not save setting parameter and back to main interface Attention If there is no operation for 5s system will remember parameter setting and back to the main interface Hours Minute Press CLOCK AUTO AUTO Press CLOCK Press AUTO or AUTO Press CLOCK Press AUTO or AUTO Press CLOCK A...

Страница 18: ...N and time hour bit flashing Press or to change the hours value Press TIME ON to save hours At the same time minutes bit flashing Press or to change the minute value Press TIME ON to save and exit At this time TIME ON LED light is on The time off setting is to press TIME OFF the other operation is the same as timer on For example Hour Munite AUTO Press TIME ON AUTO AUTO Press TIME ON AUTO AUTO Pre...

Страница 19: ...light turn off press TIME Off to enter timer off setting interface then press to cancel the timer off at this timer the timer off light turn off On Off 4 2 7 Keyboard lock To avoid mis operations please lock the controller after parameter setting At the main interface pressing for 5 seconds when hearing one sound the keyboard is locked When the keyboard is locked pressing for 5 seconds when hearin...

Страница 20: ...n occurs You can refer to the malfunction table to find out the failure cause and solution For example Water inlet temp Sensor failure 4 3 Parameter table Code Meaning Default Remarks r01 Set point of cooling target temp 27 Ajustable r02 Set point of heating target temp 27 Ajustable r03 Set point of auto mode target temp 27 Ajustable AUTO ...

Страница 21: ...ater inlet temp Sensor Water outlet temp Sensor failure P02 The water outlet temp sensor is open or shortcircuit Check or change thewater outlet temp Sensor Ambient temp Sensor failure P04 The ambient temp sensor is open or shortcircuit Check or change the ambient temp Sensor Pipe temp Sensor failure P05 The pipe temp sensor is open or short circuit Check or change thepipe temp Sensor Evaporator t...

Страница 22: ...itch 11 DI04 GND High pressure switch 12 DI05 GND No use 13 DI06 GND No use 14 AI01 GND Suction temp input 15 AI02 GND Water in temp input 16 AI03 GND Water out temp input 17 AI04 GND Coil Temp input 18 AI05 GND Ambient temp input 19 AI06 GND Ajustable fan speed Exhaust temperature 20 CN1 Primary transformer 21 CN2 Secondary transformer 22 CN6 No use 23 CN19 No use 24 5V CN16 GND No use OUT1 OUT2 ...

Страница 23: ...its useful life must be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs This product is compliant with directive 2002 95 EC RoHs concerning restrictions for the use of harmful substances in electric and electronic devices 7 The unit CANNOT ...

Страница 24: ...0A 30mA less than 0 1 sec 186 224A 2 95mm2 95mm2 280A 30mA less than 0 1 sec 2 Three phase unit Nameplate maximum current Phase line Earth line MCB Creepage protector Signal line No more than 10A 3 1 5mm2 1 5mm2 20A 30mA less than 0 1 sec n 0 5mm2 10 16A 3 2 5mm2 2 5mm2 32A 30mA less than 0 1 sec 16 25A 3 4mm2 4mm2 40A 30mA less than 0 1 sec 25 32A 3 6mm2 6mm2 40A 30mA less than 0 1 sec 32 40A 3 1...

Страница 25: ...Code 20160606 0006 ...

Отзывы: