26
Standard Altitude Blower Speeds
CIRCULATOR EXERCISING
and FREEZE PROTECTION
CIRCULATOR EXERCISING
1. The control will automatically start the circulator output and
run for 10 seconds for each 72-hour period of inactivity.
FREEZE PROTECTION
1. This function automatically fires the boiler and starts the
HEAT circulator when the heat exchanger sensor detects a
temperature less than 40 °F. The circulator turns off when the
temperature rises above 45 °F.
Model
3TANDARD!LTITUDE
"LOWER3PEED(Z
Low
Fire
(b06)
Ignition
(Can't
Change -
Needs PC)
High Fire
In
CH Mode
(b05)
High Fire
In
DHW
Mode (b04)
WMB-155C N
39
60%
205
205
WMB-155C LP
40
60%
200
200
In USA Input rates are derated 4% for each 1000 ft.
above sea level, beyond 2000 ft. in accordance with
National Fuel Gas Code, ANSI Z223.1/NFPA 54 -latest
edition.
For elevations above 10,000 feet, please contact
Weil-McLain Technical Support for details.
Figure 78
34!.$!2$!LTITUDE"LOWER3PEEDS
FORBELOWINSTALLATIONS
)