Ceiling mounted air filtration units
10
10.3 Electrical connection for DCT-1000 sequencer
The MAXITOP dust collector is equipped with 115V solenoids which activate the cleaning valves.
These solenoids are grouped in a NEMA 4 ½ panel installed behind the cabinet, above the air tanks.
A differential control panel (DCP) may also be included on the electronic panel. Wiring for these
solenoids is factory assembled. The DCT-1000 activates the solenoids in sequence in response to
either cartridge pressure drop or a continuous bases. Figure 2 represents a typical connection with
a starter to a DCT-1000 sequencer card. The electronic panel is activated in parallel with the fan
startup. This operation will regulate the pulsation required as per the status of the filters.
10.4 DCT-1000 board specifications (figure 2)
3 PHASE
ELECTRICAL
INLET
FUSES
STARTER
BLOWER MOTOR
TO HIGH/LOW
PRESSURE TAPS
ELECTRICAL CONNEXIONS
10.4.1
Typical connection for DCT-1000 sequencer figure 2
Figure 2
DCT-1000 controller:
Number of connectors:
6, 10 & 22
Extendable to 255 connections by using
extension card DCT-1122 & DCT-1110
Power:
85-270 VAC, 50-60 Hz.
Consumption:
5 W.
Power to solenoids:
3A max per
connection.
Fuses:
3 A @ 250 VAC.
Temperature range:
-40 to 140°F (-40 to
60°C).
Shutter time:
10 msec to 600 msec.
Shutter time accuracy:
±10 msec.
Down time:
1 second to 255 seconds
Down time accuracy:
±1% of setting
Weight:
1 lb, 3.0 oz (538.6 g).
Approval agency:
UL, cUL.
DCP pressure module:
Pressure range:
10» w.c. ou 20» w.c.
Temperature range:
-40 to 140°F (-40 to 60°C)
High pressure:
10 psig (68.95 kPa).
High pressure (differential):
10 psig (68.95 kPa)
Accuracy:
±1.5% F.S. @ 73°F (22.8°C).
Outlet signal:
4-20 mA.
Weight:
5.5 oz (155.9 g).