3.1 

Display screen 

 

REG-6S-100 

and

  REG-12S-100

  devices  are  equipped  with  a  3  digits  x  7  segments  LCD  screen.  The 

screen has also a set of icons, which provide information about the regulator status. The main indications 
are: 

cosφ value, reactive power sign ( 

  for lagging or inductive PF and  

 for leading or capacitive 

PF), connected stages and measurement of different parameters (see section 3.2)  
 

Icons  

Screen and LED 

Icons Indications 

  :      Lagging  or  inductive 

power indication 
 

    :  Leading  or  capacitive 

power indication 

The 

 LED (red) is ON 

in normal working conditions  

The 

  LED    shows 

that the reading of current or 
max.  current  has  to  be 
multiplied by 10

 

 

 

 

 

 

In normal working conditions, RUN 
LED  (red)  is  ON  and   

  cursor 

points  to  the  parameter  being 
displayed (Left column list)   

In SET-UP mode, the RUN LED  is 
OFF,  the    cursor  is  blinking  and 
pointing  to  the  parameter  being 
configured (Right column list). 

Symbols  indicating  the  stages 
which  are  connected  (only  in  RUN 
mode) 

3.2 

Measured parameters 

When  the  instrument  is  in  normal  RUN  mode,  the  following  parameters  can  be  displayed:  cos

,  mains 

current,  THD  of  both  mains  current  and  mains  voltage.  The  instrument  can  also  display  the  maximum 
values of mains current and voltage since the last parameters clear. The parameter being displayed can 
be selected with the navigation keys and is indicated by the   cursor. 

 

3.3 

Errors and ERROR messages 

In case that the regulator detects a possible error, the front screen shows an error code. The possible 
error codes are listed and explained in table 3-1. 
 

 Table 3-1: Possible errors and messages displayed on the screen 

ERROR 

message 

Description 

 

Load  current  below  the  threshold  current,  or  current  transformer  (CT)  not 
connected. The threshold is 0,1 A at the secondary side of CT 

 

Overcompensation.  The  regulator  detects  that  some  stages  should  be 
disconnected but all the stages are already disconnected.  

 

Under-compensation.  The  regulator  detects  that  some  stages  should  be 
connected and all the stages are already connected. 

 

Overcurrent.  The  measured  current  exceeds  the  rated  current  by  a  +  20%. 
(Rated current is considered to be the CT primary rated current)  

 

Overvoltage. The measured voltage exceeds the rated voltage by a +15%. 

 

3.4 

Alarm relay 

In  case  that  the  number  of  stages  configured  in  a 

REG-6S-100

  or 

REG-12S-100

,  is  less  than  6  or  12 

respectively,  the  relay  number  6  or  12  is  automatically  configured  as  alarm  relay.  The  relay  remains 
connected  in  absence  of  alarm  (positive  safety)  and  disconnects  in  case  that  one  or  more  of  the  errors 
listed in section 3.2 occur. Notice that the absence of supply voltage will always be detected as an alarm 
condition. The alarm relay  has a delay  of 10 s in case of Over-compensation  and Under-compensation, 
but the operation is instantaneous (delay < 1 s) in case of Over-voltage and Over-current. 

 

Содержание REG-12S-100

Страница 1: ...Power factor regulators REG 6S 100 REG 12S 100 Instructions Manual M982282AP 03 13A ...

Страница 2: ...8 4 INSTALLATION AND START UP 9 4 1 TECHNICAL CHARACTERISTICS 9 4 2 DEVICE INSTALLATION 10 4 2 1 Mechanical Installation 10 4 2 2 Connections 10 4 2 3 Cabling cross sections and protections 11 4 2 4 Schematics 11 5 CONFIGURABLE PARAMETERS 12 5 1 TARGET COSΦ 12 5 2 SMALLER AVAILABLE CAPACITOR STEP 12 5 3 C K PARAMETER CALCULATION 13 5 4 STAGE S CONFIGURATION OF PF CORRECTION EQUIPMENT CONFIGURATION...

Страница 3: ...uipment make sure that the earth terminals have been properly connected A defective earth connection may cause a wrong operation of equipment and involves a danger of electric shock to the user or system operator Maintenance must be performed taking the necessary precautions to avoid electrocution and electric shock Ensure that the unit has been disconnected and wait the necessary time to ensure t...

Страница 4: ...CP program control the switching of capacitor stages in order to minimize the number of switching operations to reach the required PF compensation Moreover the program assigns the capacitor stages to be connected or disconnected using a FIFO criterion FIFO First IN first OUT that way the times of use of all stages are equalized 1 3 3 Stages and steps We must distinguish between these two terms In ...

Страница 5: ... stage are equal twice four times etc 2 GENERAL CHARACTERISTICS The power factor regulators of types REG 6S 100 and 2S 100 measure the cos φ sometimes called Displacement Power Factor DPF in a supply network and control the connection and disconnection of power capacitors in order to regulate such parameter The difference between the two types is the number of output relays which determines the nu...

Страница 6: ...itive Fig 2 1 Power signs in four quadrants measurements 3 FRONT PANEL SCREEN AND KEYBOARD The PF regulator s front panel shows the following items Fig 3 1 Front cover and screen NOTE The set up procedure the description of different parameters and the different control modes are described in detail in the SET UP section section 6 Front Screen Configurable Parameters Measured Parameters Navigation...

Страница 7: ...ted with the navigation keys and is indicated by the cursor 3 3 Errors and ERROR messages In case that the regulator detects a possible error the front screen shows an error code The possible error codes are listed and explained in table 3 1 Table 3 1 Possible errors and messages displayed on the screen ERROR message Description Load current below the threshold current or current transformer CT no...

Страница 8: ... connecting new steps in a sequential mode respecting the adjusted connection times ton Manual disconnection of capacitor stages If this key is pushed for more than 1s the regulator starts disconnecting steps in a sequential mode respecting the adjusted disconnection times toff 3 5 2 Key functions in SET UP status Long Push 1 s This is to initiate or exit the set up mode Exiting the set up mode wi...

Страница 9: ...urement circuit Terminals A B External Current Transformer CT Current ratio In 5 To be placed preferably in phase L1 Cables for the current measurement circuit CT secondary side Minimum cross section 2 5 mm 2 If cable length between regulator and CT must exceed 25 m increase the cross section by 1mm 2 every 10 m or use a CT with a higher primary rated current Current margin 0 05 to 5 A maximum ove...

Страница 10: ... sensing of the installation A current transformer CT must be installed externally to perform this function Usually the current ratio of the CT is In 5 A where In must be at least 1 5 times the maximum expected load current The CT must be installed at the incoming supply line point of coupling of the user so that it measures the total current of all the loads including also the compensation capaci...

Страница 11: ...TERMINALS V P1 P2 Fig 4 2 Connection schematic for REG 6S 100 Nº Terminals functions A Current input S1 B Current input S2 COM Relays common 1 Relay Output 1 2 Relay Output 2 3 Relay Output 3 4 Relay Output 4 5 Relay Output 5 6 Relay Output 6 C Supply Measure Input 0V D Supply Measure Input Rated voltage depending on type See device label REG 12S 100 COM 7 8 9 10 11 12 COM 0 1 2 3 4 5 6 A B S1 S2 ...

Страница 12: ...erent values of smaller capacitor step kvar For conditions other than those given in table 5 1 the paragraph 5 13 shows a simple calculation to obtain the C K value See also foot NOTE Table 5 1 C K factor according to smaller capacitor power and CT ratio CT ratio Ip Is Smaller capacitor power in kvar at 400 V 2 5 5 00 7 5 10 0 12 5 15 0 20 0 25 0 30 0 37 5 40 0 50 0 60 0 75 0 80 0 150 5 0 12 0 24 ...

Страница 13: ...ge the powers of the rest of stages can be given in terms of multiples of the smaller step Then we could state the configuration configuration program of PF equipment as Program 1 1 1 All the stages have the same power in kvar Program 1 2 2 The second stage and successive have a power double than the 1st step The available programs of REG 6S 100 and REG 12S 100 regulators are listed in table 5 2 T...

Страница 14: ...alue between 0 7 and 1 Table 5 3 Phase shift options in REG 6S 100 and REG 12S 100 Screen U I phase shift at cos 1 V measured in phases CT placed in phase T1 30º L3 L2 L3 T2 270º L3 L2 L1 T3 150º L3 L2 L2 T4 210º L3 L2 L3 P1 P2 or S1 S2 reversed T5 90º L3 L2 L1 P1 P2 or S1 S2 reversed T6 330º L3 L2 L2 P1 P2 or S1 S2 reversed 5 8 Programming the CT rated current primary The set up of this parameter...

Страница 15: ...een C K Program Delay times Nr of stages CT phase CT primary current 5 1 5 12 5 13 5 14 5 15 5 16 5 17 5 18 IMPORTANT While the device is in set up mode if there isn t any key pushing for more than 3 minutes the device returns automatically to normal RUN mode and none of the previously edited parameters are changed nor saved To exit the set up menu changing the edited parameters push the key for m...

Страница 16: ...will sequentially connect the different steps following the normal program and respecting the delay time ton set in the set up procedure long Manual disconnection of capacitor stages Keep the key pushed during more than 1s and the regulator will sequentially disconnect the different steps following the normal program and respecting the delay time toff set in the set up procedure Displaying the num...

Страница 17: ...d Alarm relay if exists disconnects see paragraph 3 3 Although the regulation may be wrong the device tries to regulate the PF normally Overvoltage The measured voltage is 15 above rated voltage Possible causes Connection to a wrong supply voltage Alarm relay if exists disconnects see paragraph 3 3 Although the regulation may be wrong the device tries to regulate the PF normally 8 MAINTENANCE REG ...

Отзывы: