APS REG-12S-100 Скачать руководство пользователя страница 10

M982282AP-03-13A                                                                                   

REG-6S-100

 / 

REG-12S-100

 

 

- 10 - 

4.2 

DEVICE INSTALLATION 

4.2.1 

Mechanical Installation  

Mechanically, the device is intended to be mounted attached  to the front door of the cabinet. The fitting 
hole must be according to DIN 43 700, (dimensions 138

+1

x138

+1

mm). 

4.2.2 

Connections  

Before connecting the supply to the device check the following items: 

 

The installation  and maintenance  of the device must be carried  out by specialised and dully 
trained staff, according to National Electric Codes and Rules and International Standards 

All the connections must be at the inner part of a protection cabinet. 

Notice that when the device is connected to supply, the 

voltage at certain terminals can be 

hazardous  and  cause  electric  shock 

in  case  of  contact.  Opening  the  electrical  cabinet  or 

removing  certain  covers  can  compromise  the  user  safety  and  should  only  be  done  by 
qualified and authorized staff. 

The 

REG-6S-100  and REG-12S-100

 devices are used together  with capacitor  banks, which 

can remain charged after supply disconnection. In order to avoid shock hazard, wait during 5 
minutes after supply disconnection before any manipulation inside the equipment cabinet.

 

REG-6S-100 and REG-12S-100

 

devices require current sensing of the installation. A current transformer 

(CT) must be installed externally to perform this function.  Usually the current ratio of the CT is 

I

n

 / 5  A

where 

In

 must be at least 1,5 times the maximum expected load current. 

The CT must be installed at the incoming supply line (point of coupling of the user), so that it measures 
the total current of all the loads, including also the compensation capacitor bank (see fig. 4.1) 

The CT should be installed preferably in phase L1, while the voltage measuring terminals of 

REG-6S-100 

and REG-12S-100

 

should  be connected  to phases L2 and L3 (see schematic

s in figs. 4.2 and 4.3). It’s 

important  to  respect  the  connection  senses  of  P1-P2  and  S1-S2  shown  in  the  above  mentioned  figs, 
otherwise  the  phase  difference  will  have  to  be  corrected  by  adjusting  the  device  according  to  set-up 
procedure indicated in paragraph 5.17. 

 

RIGHT CONNECTION 

WRONG CONNECTIONS 

LOAD

CAPACITORS

TC

S1

S2

P1

P2

 

The  CT  measures  the  whole 
current of loads + capacitor bank.  
In  case  of  malfunction  check  that 
the CT is not shortcircuited

 

TC

S1

S2

P1

P2

LOAD

CAPACITORS

 

If  CT  is  placed  in  this  position, 
NONE 

of 

the 

CAPACITOR 

STAGES WILL CONNECT. 

The equipment does not regulate 
properly.

 

TC

S1

S2

P1

P2

LOAD

CAPACITORS

 

If  CT  is  placed  in  this  position 
ALL  THE  CAPACITOR  STAGES 
WILL CONNECT. 

WARNING!  This  situation  may 
cause 

overcompensation, 

resonance and overcurrent

 

Fig.  4.1.- Placement of current transformer (CT) 

Содержание REG-12S-100

Страница 1: ...Power factor regulators REG 6S 100 REG 12S 100 Instructions Manual M982282AP 03 13A ...

Страница 2: ...8 4 INSTALLATION AND START UP 9 4 1 TECHNICAL CHARACTERISTICS 9 4 2 DEVICE INSTALLATION 10 4 2 1 Mechanical Installation 10 4 2 2 Connections 10 4 2 3 Cabling cross sections and protections 11 4 2 4 Schematics 11 5 CONFIGURABLE PARAMETERS 12 5 1 TARGET COSΦ 12 5 2 SMALLER AVAILABLE CAPACITOR STEP 12 5 3 C K PARAMETER CALCULATION 13 5 4 STAGE S CONFIGURATION OF PF CORRECTION EQUIPMENT CONFIGURATION...

Страница 3: ...uipment make sure that the earth terminals have been properly connected A defective earth connection may cause a wrong operation of equipment and involves a danger of electric shock to the user or system operator Maintenance must be performed taking the necessary precautions to avoid electrocution and electric shock Ensure that the unit has been disconnected and wait the necessary time to ensure t...

Страница 4: ...CP program control the switching of capacitor stages in order to minimize the number of switching operations to reach the required PF compensation Moreover the program assigns the capacitor stages to be connected or disconnected using a FIFO criterion FIFO First IN first OUT that way the times of use of all stages are equalized 1 3 3 Stages and steps We must distinguish between these two terms In ...

Страница 5: ... stage are equal twice four times etc 2 GENERAL CHARACTERISTICS The power factor regulators of types REG 6S 100 and 2S 100 measure the cos φ sometimes called Displacement Power Factor DPF in a supply network and control the connection and disconnection of power capacitors in order to regulate such parameter The difference between the two types is the number of output relays which determines the nu...

Страница 6: ...itive Fig 2 1 Power signs in four quadrants measurements 3 FRONT PANEL SCREEN AND KEYBOARD The PF regulator s front panel shows the following items Fig 3 1 Front cover and screen NOTE The set up procedure the description of different parameters and the different control modes are described in detail in the SET UP section section 6 Front Screen Configurable Parameters Measured Parameters Navigation...

Страница 7: ...ted with the navigation keys and is indicated by the cursor 3 3 Errors and ERROR messages In case that the regulator detects a possible error the front screen shows an error code The possible error codes are listed and explained in table 3 1 Table 3 1 Possible errors and messages displayed on the screen ERROR message Description Load current below the threshold current or current transformer CT no...

Страница 8: ... connecting new steps in a sequential mode respecting the adjusted connection times ton Manual disconnection of capacitor stages If this key is pushed for more than 1s the regulator starts disconnecting steps in a sequential mode respecting the adjusted disconnection times toff 3 5 2 Key functions in SET UP status Long Push 1 s This is to initiate or exit the set up mode Exiting the set up mode wi...

Страница 9: ...urement circuit Terminals A B External Current Transformer CT Current ratio In 5 To be placed preferably in phase L1 Cables for the current measurement circuit CT secondary side Minimum cross section 2 5 mm 2 If cable length between regulator and CT must exceed 25 m increase the cross section by 1mm 2 every 10 m or use a CT with a higher primary rated current Current margin 0 05 to 5 A maximum ove...

Страница 10: ... sensing of the installation A current transformer CT must be installed externally to perform this function Usually the current ratio of the CT is In 5 A where In must be at least 1 5 times the maximum expected load current The CT must be installed at the incoming supply line point of coupling of the user so that it measures the total current of all the loads including also the compensation capaci...

Страница 11: ...TERMINALS V P1 P2 Fig 4 2 Connection schematic for REG 6S 100 Nº Terminals functions A Current input S1 B Current input S2 COM Relays common 1 Relay Output 1 2 Relay Output 2 3 Relay Output 3 4 Relay Output 4 5 Relay Output 5 6 Relay Output 6 C Supply Measure Input 0V D Supply Measure Input Rated voltage depending on type See device label REG 12S 100 COM 7 8 9 10 11 12 COM 0 1 2 3 4 5 6 A B S1 S2 ...

Страница 12: ...erent values of smaller capacitor step kvar For conditions other than those given in table 5 1 the paragraph 5 13 shows a simple calculation to obtain the C K value See also foot NOTE Table 5 1 C K factor according to smaller capacitor power and CT ratio CT ratio Ip Is Smaller capacitor power in kvar at 400 V 2 5 5 00 7 5 10 0 12 5 15 0 20 0 25 0 30 0 37 5 40 0 50 0 60 0 75 0 80 0 150 5 0 12 0 24 ...

Страница 13: ...ge the powers of the rest of stages can be given in terms of multiples of the smaller step Then we could state the configuration configuration program of PF equipment as Program 1 1 1 All the stages have the same power in kvar Program 1 2 2 The second stage and successive have a power double than the 1st step The available programs of REG 6S 100 and REG 12S 100 regulators are listed in table 5 2 T...

Страница 14: ...alue between 0 7 and 1 Table 5 3 Phase shift options in REG 6S 100 and REG 12S 100 Screen U I phase shift at cos 1 V measured in phases CT placed in phase T1 30º L3 L2 L3 T2 270º L3 L2 L1 T3 150º L3 L2 L2 T4 210º L3 L2 L3 P1 P2 or S1 S2 reversed T5 90º L3 L2 L1 P1 P2 or S1 S2 reversed T6 330º L3 L2 L2 P1 P2 or S1 S2 reversed 5 8 Programming the CT rated current primary The set up of this parameter...

Страница 15: ...een C K Program Delay times Nr of stages CT phase CT primary current 5 1 5 12 5 13 5 14 5 15 5 16 5 17 5 18 IMPORTANT While the device is in set up mode if there isn t any key pushing for more than 3 minutes the device returns automatically to normal RUN mode and none of the previously edited parameters are changed nor saved To exit the set up menu changing the edited parameters push the key for m...

Страница 16: ...will sequentially connect the different steps following the normal program and respecting the delay time ton set in the set up procedure long Manual disconnection of capacitor stages Keep the key pushed during more than 1s and the regulator will sequentially disconnect the different steps following the normal program and respecting the delay time toff set in the set up procedure Displaying the num...

Страница 17: ...d Alarm relay if exists disconnects see paragraph 3 3 Although the regulation may be wrong the device tries to regulate the PF normally Overvoltage The measured voltage is 15 above rated voltage Possible causes Connection to a wrong supply voltage Alarm relay if exists disconnects see paragraph 3 3 Although the regulation may be wrong the device tries to regulate the PF normally 8 MAINTENANCE REG ...

Отзывы: