Installation 

 
Before commissioning the unit you are recommended to check the installation with the aid of 
the check list for installation/fault finding. 
 
Before  switching  on  the  voltage  supply  and  the  supply  for  the  inputs  and  outputs  you  must 
ensure that the voltage values are within the permissible limits (see Technical Data). Voltage 
which is too high or false polarity of the voltage can lead to damage of the LSC System. 
 
After  switching  on  the  voltage  supply  of  the  LSC  System  (system  voltage)  the  green  LED 
"POWER  ON"  on  the  Basic  Module  must  light  up.  If  this  is  not  the  case,  then  the  system 
voltage is outside the permissible range. If you use more than one device (e.g. two BM and 
one RM) you need to set the module addresses as explained below. 
 
Then  every  individual  function  of  the  LSC  System  must  be  checked.  In  doing  so,  not  only 
must  the  configuration  of  the  system  be  verified  but  also  the  external  wiring  and  the 
interaction  with  connected  equipment.  Before  testing  take  precautions  that  a  (possibly 
inadvertent) activation of the outputs in association with equipment connected to them cannot 
lead to dangerous operating states. When testing, all inputs must be systematically activated 
in turn and the reaction of the system checked for its correctness. 
 
 

Setting the module ID-address: 

 
Please refer to the following points to set the module ID-addresses: 

 

o

  Turn off the supply voltage of the module. 

o

  Press and hold the lamp-test button, meanwhile turn on the supply voltage. 

o

  The actual module address is now showed as follows: 

-All LED are activated for stand alone (factory setting)  
-One of the LED 1 to 8 blinks (ID already set). 

o

  Release  the  lamp  test  button  and  press  it  again  to  set  the  ID  address.  With  every 

pressing the address counts one up, shown by the appropriate blinking LED. 

o

  Press  and  hold  the  lamp  test  button  for  3  seconds  to  save  your  settings.  After 

successfully  saving  your  changes,  the  module  acknowledges  with  a  beep  tone  and 
switches back to operation mode. 

 

 

 Lamp test button 

 
 
 
 
 

Содержание LSC

Страница 1: ...APS Annunciator System LSC Installation User Manual ...

Страница 2: ...ings 7 CAN Bus 8 Installation check list 9 Basic Module BM 10 Application Characteristics 10 Function 10 Technical data 10 Wiring diagram 11 Relay Module RM 12 Application Characteristics 12 Function 12 Technical data 12 Wiring diagram 13 Panel Module PM 14 Application Characteristics 14 Function 14 Technical data 14 Wiring diagram 15 Bus connector CIM 15 Application Characteristics 15 Additional ...

Страница 3: ...or the voltage supply and for the various inputs and outputs is connected to the terminals of the module The connection of the modules to each other is effected with factory made cables At its begin and end the BUS must be terminated with a resistor This termination resistor is on the Basic and Relay Module and it is connecting to the BUS with switch 1 on the modules The power circuit for the volt...

Страница 4: ...4 LSC Connection principle ...

Страница 5: ...r configuration via PC and expansion functions System components BM Basic Module Basic module with 8 signal inputs with RS232 interface Housing for DIN rail mounting RM Relay Module Expansion device with 8 relay outputs only RS232 interface Housing for DIN rail mounting PM Panel Module Optional module for external indication Front mounted CIM Connector Interface between system bus and building cab...

Страница 6: ...e external wiring and the interaction with connected equipment Before testing take precautions that a possibly inadvertent activation of the outputs in association with equipment connected to them cannot lead to dangerous operating states When testing all inputs must be systematically activated in turn and the reaction of the system checked for its correctness Setting the module ID address Please ...

Страница 7: ...her module LED blinking ID address LED blinking ID address 1 0 6 5 2 1 7 6 3 2 8 7 4 3 1 8 8 5 4 Factory settings Please refer to the following points to set a Basic Module BM back to factory settings o Turn of the supply voltage o Press and hold the two buttons lamp test and horn acknowledgement then turn on the supply voltage o The module acknowledges the restoration of the factory settings by b...

Страница 8: ...or it is LED Bus LED Horn Type of the error Bus OFF The module has switched off the bus Possible reasons are a short circuit or a module operating with the same module ID address Connection error The module has no connection to the bus Bus conflict Several modules are using the same module ID address Failure neighbour module The next module has lost it s connection or does not work properly Steady...

Страница 9: ...h ON 1 Termination resistor Last Switch ON 1 Alarm inputs BM 8 15 Alarm inputs BM 7 Horn acknowledgement BM 4 Horn acknowledgement BM 3 Lamp acknowledgement BM 5 Lamp acknowledgement BM 3 Lamp test BM 6 Lamp test BM 3 Relay output horn BM 20 21 Group alarm BM 18 19 Relay common alarm BM 16 17 Potential free contacts RM 8 9 22 23 Connections All Bus Module address BM RM Configuration ...

Страница 10: ... horn annunciator relay is activated and the LED for this relay is illuminated After expiry of the set delay time the relays for collective alarm and group alarm are triggered and signalled with a LED in accordance with the operating mode set After the expiry of the preset delay time the fault is indicated at the alarm input by the blinking of the related LED Horn acknowledgement The integrated bu...

Страница 11: ...11 LSC Wiring diagram ...

Страница 12: ...ling o Integrated lamp test button o Built in LED showing the status of the supply voltage and the bus function Function The control of the Relay Module RM is effected via the internal BUS Optionally the alarm inputs can be linked with the individual outputs of the Relay Module OR linking of the alarm inputs Button lamp test All LED are activated for appr five seconds Outputs in BLINK mode are act...

Страница 13: ...13 LSC Wiring diagram ...

Страница 14: ... and common relay Function The PM has a red LED for each signal input of the BM Furthermore it has green LED for the system outputs The LED are illuminated when a signal input or a system output is active Horn acknowledgement The integrated buzzer and the relay contact for the horn are switched off Lamp acknowledgement LED goes out or changes to continuous light if the input is still activated Lam...

Страница 15: ...teristics When you are using modules at different venues the CIM bus connector is the interface between the cabling The CIM provides a plug for the standard BCC cable on one side and cage clamp connectors on the other side The CIM can be clamped on a DIN rail ...

Страница 16: ...ms ch Do not forget to make a safety copy after finishing your work Order overview 832 600 012 BM Basic Module 832 600 022 RM Relay Module 832 600 000 PM Panel Module 832 600 031 BCCS4 Bus cable 0 2m 4 poles 832 600 030 BCCS6 Bus cable 0 1m 6 poles 832 600 033 BCCL6 Bus cable 3 0m 6 poles 832 600 032 CIM Bus Connector DIN rail mounted 832 600 095 LSC configuration cable 832 600 903 Replacement ins...

Отзывы: