21
20
1. Replace the cover by snapping it into the Humidifier Control
base. Also replace the knob onto the Control.
2. Restore power to the heating system.
3. Activate the HVAC system or heat pump.
4. Once the blower is operating, rotate the knob of the Humidifier
Control Clockwise to the “Test/Reset” position. When the knob
is set in the “Test/Reset” position, the green “Humidifier On”
light will illuminate. After 5 seconds, the green “Humidifier On”
light will blink, indicating a system reset.
5. If the Humidifier Control and humidifier are set up properly,
you should hear the solenoid valve click into the open position.
In the “Test/Reset” position, the humidifier will operate for
1 minute. If the Humidifier Control is left in the “Test/Reset”
position for more than 1 minute, the “H” terminals will
de-energize (closing the solenoid valve), and the knob and
display backlights will flash, indicating that the Humidifier
Control is still in the “Test/Reset” position.
6. If the humidifier does not activate with the Humidifier Control
in the “Test/Reset” position, refer to the troubleshooting guide.
7. Setting the Humidifier Control:
• If the home is occupied, set the Humidifier Control to
“Normal” (For Manual Mode, set to 35%)
• If the home is vacant, set the Humidifier Control to “OFF”
• If in Manual Mode and system is installed during cooling
season, set the Humidifier Control to “OFF”
8. Instruct the homeowner to refer to the Aprilaire Owner’s
Manual for the initial adjustment period.
9. Make sure the red “Call Dealer for Service” light is not
flashing. If the red “Call Dealer for Service” light is flashing,
refer to the troubleshooting guide.
SYSTEM CHECKOUT
OUTDOOR TEMPERATURE
SENSOR OR MANUAL
MODE RESISTOR
24 VAC
TRANSFORMER
(SEE INSTRUCTIONS)
MODEL 8570 THERMOSTAT
ZA
ZB
H
DIGITAL HUMIDIFIER CONTROL TERMINAL STRIP
W/G Cf
ODT
B
A
C
R
MODEL 8570 THERMOSTAT OPTION (FIGURE Q)
The Model 8570 Thermostat provides the signal that the HVAC is
operating. The outdoor temperature sensor can be connected to
the Humidifier Control or to the Model 8570. If the Humidifier
Control is operating in Manual Mode, the Model 8570 will
display a constant outdoor temperature of about 20°F.
Figure Q
90-1226