background image

Model 8051 Flush Mount Sensor

Installation Instructions

IntroductIon

InStallatIon InStructIonS

The 8051 is a temperature sensor. It can be used to remotely measure temperature with compatible Aprilaire

®

 thermostats and support modules.

1.  Select a location for mounting the sensor.

  Locate the sensor as you would locate a thermostat.
    •  Mount on an interior wall, in a frequently occupied space.
    •  Keep the sensor 18” away from an outside wall.
    •  DO NOT mount the sensor:
      –   Behind doors, in corners or other dead air spaces.
      –   In direct sunlight or near lamps, appliances, dimmer 

switches or other sources of heat.

      –   On an outside wall or wall exposed to an unconditioned 

space (i.e. garage).

      –   In the flow path of a supply register, in stairways or near 

outside doors.

      –   On a wall where a concealed pipe or ductwork could 

influence the sensor.

      –   Near sources of electrical interference such as light 

switches.

   Maximum wire length from the sensor to the thermostat or support 

module is 300 feet.

2.  Install the sensor – see back page.

3.  disconnect power to the thermostat or support module to 

which the sensor will be wired.

 cautIon

Damage to components can occur if power is not 
disconnected.

4.  Verify the sensor resistance.

   Use an ohm-meter or multimeter to measure the resistance 

of the sensor. Measure at the wires near the thermostat or 
support module to check any wire splices. Confirm the resistance 
corresponds (within 5%) to the temperature where the sensor  
is installed.

temperature (°F)

resistance (k )

30

34.6

40

26.1

50

19.9

60

15.3

70

11.9

80

9.4

90

7.4

100

5.9

5.  Wire the sensor to the component.

 cautIon

Excessive bare wire can lead to shorts. Strip only as much 
insulation as is necessary.

  •  The sensor is not polarity specific. Either sensor lead may be 

connected to either terminal on the component to which it is 
wired. To select the appropriate terminals for wiring please see 
the installation manual for the thermostat or support module.

  •  Use care when routing and stripping the wire. Sharp bends (kinks) 

or cuts in the wire (particularly susceptible where the insulation 
has been stripped) can lead to eventual conductor failure.

6.  reconnect power to the thermostat or support module to 

which the sensor is installed.

Sensor Specifications

Voltage

20-30 VAC

Resistance @ 25°C (77°F)

10 k

Tolerance @ 25°C (77°F)

±3%

The following table shows the correct resistance at various ambient 
temperatures without the sensor wires attached to a thermostat or 
support module.

61000944A AA 8051 Flush Mount Sensor Install.indd   1

3/28/12   11:38 AM

Отзывы: