Model 8051 FluSh Mount SenSor InStallatIon InStructIonS
Step 1:
Use a 1” paddle bit to drill a 1” dia. hole in the drywall/sheetrock. Keep the drill steady and horizontal to ensure a clean finished hole.
Step 2:
Wire nut the sensor to cable run between the flush mount sensor and the thermostat or support module. Press the sensor into the 1” hole
after the wires are connected.
IMportant:
Do not spackle or mud over the sensor. The sensor must protrude 1/64” from the wall for accurate temperature reporting.
Step 3:
Wire the sensor to the thermostat or support module. Refer to the instructions provided with these devices for additional details.
1”
1.00”
THERMOSTAT
OR
SUPPORT MODULE
note:
Paint or apply wall paper to the sensor
disk prior to installing the sensor into the wall.
PRESS FLUSH MOUNT TEMPERATURE SENSOR
INTO 1” HOLE. NO FASTENERS REQUIRED.