InSTallaTIon InSTRUCTIonS
(ConTInUeD)
ManUal DIGITal HUMIDISTaT anD fan PaCk wIRInG (MoDel 865)
Mount the Digital Manual Humidistat in the area to be humidified
according to installation instructions included with control . Install the
humidistat in the same room or area as the Fan Pack discharge, but at least ten feet away . Wire the Digital Manual Humidistat to the Steam
Humidifier using standard 24 volt thermostat wire . See
figure 18
.
Disconnect all power to Steam Humidifier before wiring the Fan Pack terminals to the FAN PACK terminals on the Steam Humidifier . Use
standard 24 volt thermostat wire . See
figure 18
.
fIGURe 18 – wiring Diagram for Manual Humidistat and fan Pack
90-1662
FA
N
PA
CK
HUMIDIS
TAT
H
H
R
C
24VAC
24VAC
P4
YELLOW
BLUE
Model 65 Digital Control
Tap Connectors
Circuit Board
Transformer
Steam Humidifier Fan Pack
Aprilaire Steam Humidifier
WIRE
– 18 Awg acceptable for 24 VAC application.
%
*
OFF
ON
SET
21