background image

TROUblESHOOTING

TAblE 7 – Green lED Codes

Activity

Status

Solid ON

Compressor ON

Blinking 1 sec . ON & 1 sec . OFF

Sampling

Blinking 1/2 sec . ON & 1/2 sec . OFF

Defrosting

Alternating Green & Red

Control knob was left in Test Mode

Technical Support is available Monday through Friday, 7:00 a .m . to 5:00 p .m . CST, at (800) 334-6011 . Use the guides on the following pages to 
identify and correct system faults . Contact Technical Support before replacing the unit or components and for additional troubleshooting . 

lED CODES

The dehumidifier control board uses the Status LED to communicate 
current status or a fault code . Faults can be either critical or non-
critical . In either case, when a fault is detected, the red LED will flash 
the fault code and all outputs will immediately turn off . A critical 
fault can be cleared by repairing the fault 

and

 cycling power to the 

dehumidifier . A non-critical fault will be cleared when the fault is 
repaired . Cycling power is not required . 

TAblE 8 – Red lED Codes

Number  

of blinks

fault Type

failure Mode

failure Condition

Action

1

Non-Critical

Internal RH 

sensor fault .

RH sensor open or shorted .

1 .  Check connection between sensor board and control board .
2 .  If connection okay, replace sensor board, Part No . 4752 .

2

Critical

Internal 

temperature 

sensor fault .

Temperature sensor open or shorted .

1 .  Check connection between sensor board and control board .
2 .  If connection okay, replace sensor board, Part No . 4752 .

3

Non-Critical

Model 76 

Remote Control

 

fault .

Model 76 

Remote Control

 not 

communicating with dehumidifier .

1 .  Check connections between Model 76 and dehumidifier 

control board .

2 .  If connections are correct and secure, turn off the 

dehumidifier and remove the Model 76 . Use a short section 

of 4-wire cable to reconnect the Model 76 to the control 

board . Turn the dehumidifier back on and increase the 

dryness level setting on the Model 76 . If the dehumidifier 

turns on, the problem is with the wiring between the 

dehumidifier and control .

3 .  If the dehumidifier does not turn on, call Technical Support .

4

Critical

Insufficient 

capacity .

After 20 minutes of compressor operation, 

the frost sensor temperature is not at least 

5°F below the inlet air temperature .

1 .  Check the frost sensor connection at the control board .
2 .  Remove the side panel (when facing side of unit, on/off 

switch will be on left) and verify the temperature sensor is 

not damaged, is fully inserted in the sensor well, and the 

well is filled with thermal paste .

3 .  If the sensor is not damaged and positioned correctly, 

contact Technical Support .

5

Non-Critical

Inlet air 

temperature out 

of range .

Internal temperature sensor reads out 

of 50°F –105°F range for compressor 

operation . NOTE: If compressor is on when 

fault condition occurs, the compressor will 

turn off . If the compressor is not on when 

the fault condition occurs, there is no fault .

1 .  Circulate air through the unit by setting the Cycle Period to 

1 hour and Cycle Time to 60 minutes . After a minimum of 

10 minutes, cycle power to the dehumidifier .

2 .  If fault persists, call Technical Support .

6

Critical

Frost sensor 

failure .

Frost temperature sensor open or shorted .

1 .  Check the frost sensor connection at the control board .
2 .  Remove the side panel (when facing side of unit, on/off 

switch will be on left) and verify the temperature sensor is 

not damaged, is fully inserted in the sensor well, and the 

well is filled with thermal paste . 

3 .  If the fault persists, contact Technical Support .

7

Non-Critical

Float switch 

open .

Open circuit between float switch inputs .

1 .  Empty the condensate pan .
2 .  Check the float switch connection at the control board .
3 .  If not using float switch, verify jumper is between float 

switch terminals on dehumidifier control board .

4 .  If the problem persists, replace the float switch .

23

Содержание 1750A

Страница 1: ...disconnected until installation service is completed 3 Sharp edges may cause serious injury from cuts Use care when cutting plenum openings and handling ductwork 4 Dropping may cause personal injury o...

Страница 2: ...SINGLE ZONE DUCTED TO HVAC SYSTEM see page 7 SINGLE ZONE NOT DUCTED TO HVAC SYSTEM see page 9 TWO ZONE PRIMARY AND SECONDARY ZONED see page 11 In a Single Zone Ducted to HVAC System installation the d...

Страница 3: ...non condensing Filter MERV 8 washable Compressor Minimum Off Time 3 minutes Compressor Minimum On Time 3 minutes Airflow 1750A External Static Pressure Airflow 0 0 w c 380 CFM 0 4 w c 310 CFM 0 6 w c...

Страница 4: ...6mm Minimum Clearance for Filter and Front Panel Removal 20 in 508mm Minimum Clearance for Filter Removal 6 in 152mm Minimum Clearance for Filter Removal Air Inlet 8 in Round Collar Service Access Pan...

Страница 5: ...OUTLET 4 MIN BACKFLOW DAMPER CAUTION Only install damper on outlet Dehumidifier will not function if damper is installed on inlet GENERAL DUCTWORK RECOMMENDATIONS When ducted to the HVAC supply the ou...

Страница 6: ...drip pan located below the coil CAUTION 1 Drain trap must be primed with water before use 2 A condensate pan with a float switch is required in attic installations High Side Low Side Drain Outlet Dra...

Страница 7: ...ly Closed Float Switch Grille Model 76 Control Model 8910 Home Comfort Control Third Party Control Figure 9 Single Zone Ducted to HVAC System Basement Installation AIR IS PULLED FROM RETURN DUCT DEHUM...

Страница 8: ...d to the supply side The Alternate Installation see Figure 12 minimizes re evaporation of moisture off the cooling coil Attic Installation Notes The dehumidifier must be installed in a secondary conde...

Страница 9: ...n and the green Status LED switches to solid illumination If the dew point is below the setting the dehumidifier damper output turns off and the dehumidifier blower turns off along with the green Stat...

Страница 10: ...14 Leave the LOCAL EXTERNAL switch in the LOCAL position if using the dehumidifier s onboard control If installing a separate control see MODEL 76 EXTERNAL CONTROL on page 19 MODEL 76 REMOTE CONTROL o...

Страница 11: ...ary Zone Required Components Duct Work 18 22 AWG Wire Grilles 2 Aprilaire Model 6508 8 Normally Closed Damper 2 Aprilaire Model 6608 8 Normally Open Damper 24 VAC Transformer 40VA min for Dampers NOTE...

Страница 12: ...hrough the unit dehumidified and circulated solely by the dehumidifier blower CYCLE PERIOD This determines how frequently the dehumidifier will sample the air to check the humidity level Set to 1 hour...

Страница 13: ...n Status LED switches to solid illumination If the dew point is below the setting the dehumidifier damper output turns off and the green Status LED begins flashing as the dehumidifier begins Secondary...

Страница 14: ...unction in Air Cycling mode activating the HVAC blower to cycle air through the home based on the Cycle Period and Cycle Time Required Components Aprilaire Model 6506 6 Normally Closed Damper 24 VAC T...

Страница 15: ...QUIREMENTS See page 17 for outdoor temperature sensor installation 1 The MINIMUM ventilation requirement is calculated using ASHRAE 62 2 ASHRAE Airflow in CFM House Area in Sq Ft x 0 01 Number of Bedr...

Страница 16: ...d a fully opened damper Rigid pipe values are based on 6 duct two 90 elbows and a fully open damper In both cases the air intake is through a metal vent hood with inlet screen Airflow may need to be a...

Страница 17: ...requirement is met ventilation will not occur until the next cycle period SETTING DIP SWITCHES CYCLE TIME TO MEET VENTILATION REQUIREMENTS Figure 22 VENT TIMED DIP Switch Settings 90 1538 ON 1 2 3 4 4...

Страница 18: ...s active The dew point of the air is measured 3 minutes after the dehumidifier blower is turned on and every 15 seconds while the blower is running If the dew point of the air is above the setting on...

Страница 19: ...EM SETUP HVAC FAN ON VENT TIMED VENT AUTO PRIMARY HVAC FAN OFF ON 1 2 3 4 MODEL 76 DAMPERS Rf DH W Gh Gs Cf VENT HVAC EQUIP REMOTE DEH B A DEHUMIDIFIER CONTROL BOARD HVAC EQUIPMENT THERMOSTAT G R C G...

Страница 20: ...90 1538 LOCAL PRIMARY SECONDARY EXTERNAL SYSTEM SETUP HVAC FAN ON VENT TIMED VENT AUTO PRIMARY HVAC FAN OFF ON 1 2 3 4 MODEL 76 DAMPERS Rf DH W Gh Gs Cf VENT HVAC EQUIP REMOTE DEH B A DEHUMIDIFIER CO...

Страница 21: ...Rf DAMPERS C R RC RH HC W W2 W3 Y Y2 Y3 C L G DH VENT EAC DH DH HUM HP B W2 W G O Y2 Y nc com no EQ DEHUMIDIFIER CONTROL BOARD HVAC EQUIPMENT MODEL 8910 HOME COMFORT CONTROL EQUIPMENT CONTROL MODULE...

Страница 22: ...structions for the Model 76 Control Model 8910 Home Comfort Control or Third Party Control for setting adjustments Figure 33 Control Knob Setpoint 90 1327 EXAMPLE At an indoor temperature of 75 F and...

Страница 23: ...rd Turn the dehumidifier back on and increase the dryness level setting on the Model 76 If the dehumidifier turns on the problem is with the wiring between the dehumidifier and control 3 If the dehumi...

Страница 24: ...tage across the R C terminals on the dehumidifier control board Voltage should be 18 VAC 30 VAC Incorrect wiring Verify wiring and connections between the thermostat HVAC and dehumidifier HVAC fan ope...

Страница 25: ...ly included with Model 1710A only 1 4863 12 LED Control Door 1 4864 No Part Description Qty Ctn Part No 13 10 VA Transformer 1 5262 14A Capacitor 60MF 1770A 1 5255 14B Capacitor 55MF 1710A 1750A 1 492...

Страница 26: ......

Страница 27: ......

Страница 28: ...P O Box 1467 Madison WI 53701 1467 Phone 800 334 6011 Fax 608 257 4357 www aprilairepartners com 10009845 5 12 B2205733B Printed in U S A 2012 Aprilaire A division of Research Products Corporation...

Страница 29: ......

Отзывы: