SEQUENCE OF OPERATION

The dehumidistat continually measures the humidity of the air in which it is located and controls to the dryness level set on the dial. When the 

humidity level rises above the dial setting on the dehumidistat, the dehumidifier blower will turn on and the first amber LED on the power board 

(not visible unless dehumidifier cover is removed) will illuminate. The HVAC system blower, along with the third amber LED (not visible unless 

dehumidifier cover is removed) will also turn on if the dehumidifier is wired to the HVAC system. After three minutes of blower operation, the 

dehumidifier compressor will turn on along with the second amber LED (not visible unless dehumidifier cover is removed). When the humidity 

level drops below the dial setting on the dehumidistat, both the compressor and dehumidifier blower will turn off. If wired to the HVAC 

system, the HVAC blower will also turn off unless the system thermostat keeps it running. To prevent short-cycling, the compressor will turn on 

3 minutes after the blower.
The dehumidifier is equipped with an automatic defrost feature. When the evaporator coil temperature drops below the cut-out point of the frost 

sensor, the dehumidifier begins the defrost cycle and the dehumidistat will turn off the compressor and the blower will continue to run. The 

compressor will remain off until the evaporator coil temperature rises above the cut-in point of the frost sensor. 

TROUBLESHOOTING GUIDE

SyMPTOM

POSSIBLE REASON/TROUBLESHOOTING PROCEDURE

Red LED On
Blower & compressor not running.

Open Float Switch
•  If float switch not installed, confirm jumper installed at FLOAT SWITCH terminals. 
•  If float switch installed, confirm switch is not open.
•  Clear obstruction in drain pan/tubing. 

Red LED On
Blower is on but compressor not running.

High System Pressure/High Discharge Line Temperature Due to Lack of Airflow or Excessive 

Inlet Temperature
•  Check dehumidifier air filter and wash or replace. 
•  Check for blocked ductwork and clear.

Dehumidifier blower is running but little  

or no airflow.

Pressure Drop Across Dehumidifier is Higher than 0.8” w.c. 
•  Check dehumidifier air filter and wash or replace. 
•  Check for blocked ductwork and clear.
•  Check if back flow damper is blocked or stuck and remove obstruction.

Blower is running but compressor is not.

Coil Frosting
•  Lack of or reduced airflow, check/clean filter.
•  Inlet air conditions too low (below 60°F), turn down dryness setting.

Dehumidifier is not draining properly.

Incorrect Drain Installation
•  Check drain line for continuous downward slope.
•  Verify there are no kinks, traps or debris in drain line.
•  If drain trap installed, confirm trap is properly installed, clear and primed.
•  Unit is not level, adjust feet.

The dehumidifier does not run.

No Power to Unit – Green LED Off (dedicated 15 amp circuit recommended)
•  Check that the power switch on the dehumidifier is ON.
•  Check if circuit breaker has tripped. 
Dehumidistat is OFF
•  Turn on dehumidistat.

Dehumidifier is loud when operating.

Fan Noise
•  If inlet is not ducted to HVAC return, install approximately 2’ of 8” flex duct on inlet collar.
Vibration
•  Install vibration isolators under dehumidifier feet.

Dehumidifier is producing hot air.

This is normal operation.

7

Содержание 1730A

Страница 1: ...e required to protect from moving parts and electrical components CAUTION 1 Do not use in pool applications 2 If unit has been shipped or stored on its side wait 24 hours before running 3 Do not use s...

Страница 2: ...y 5 feet above the floor on an inside wall of the living space Do not locate dehumidistat in the direct path of drafts from open doors and windows Do not install where operation might be affected by l...

Страница 3: ...ORATION OFF A COIL AIR IS PULLED FROM MAIN RETURN DUCT DEHUMIDISTAT WITH SET POINT KNOB CONDENSATE HOSE TO COMMON DRAIN OR OUTSIDE Figure 5 Basement Installation 90 1423 MAIN RETURN DUCT DEHUMIDIFIER...

Страница 4: ...e wired to activate the HVAC blower during dehumidification This is recommended because it offers better circulation and balancing of the indoor air conditions Note Running the HVAC blower during dehu...

Страница 5: ...E terminals from the circuit board remove the two wires and cut off bare leads Once cut the wires may remain in the unit 9 Run a 2 wire cable 18 22AWG from the dehumidifier to the wall mount location...

Страница 6: ...ow the wiring access panel Verify the green LED is on The green LED is on when power is applied to the system 4 Rotate the dehumidistat knob fully clockwise to ON position 5 If setup is correct the de...

Страница 7: ...ocedure Red LED On Blower compressor not running Open Float Switch If float switch not installed confirm jumper installed at FLOAT SWITCH terminals If float switch installed confirm switch is not open...

Страница 8: ...ESEARCH PRODUCTS CORPORATION P O Box 1467 Madison WI 53701 1467 Phone 608 257 8801 Fax 608 257 4357 www aprilairepartners com 10008611 6 09 B2204896A 2009 Research Products Corporation Printed in U S...

Отзывы: