SET-UP

The dehumidifier can be installed as shipped, with the supply collar 

on the outlet panel, or if space is restricted, the supply collar can be 

relocated to the top of the unit. 

TOP MOUNT SUPPLy COLLAR (FIGURE 3)

1.  Remove the four screws securing the supply collar (with backflow 

damper) and screen to the outlet panel.

2.  Remove the four screws securing the top mounted outlet cover plate.
3.  Attach screen and supply collar with damper to the top of the unit.
4.  Attach outlet cover plate to the outlet panel.

SUPPLy COLLAR

FIGURE 3 – Top Mount Supply Collar

The dehumidistat mounted to the dehumidifier can remain on the unit 

or be removed and mounted in the living space. 

Attic installations 

require that the dehumidistat be moved to the living space.

 

Note: Any dry contact, normally open humidity control can be used 

as the controlling device for the dehumidifier. If using a control other 

than the one provided, remove the dehumidistat as described in 

steps 1-6 in the 

WIRING, Dehumidistat Wall Mount Installation

 

section. Follow steps 7-10 to wire an alternate control.

WALL MOUNT LOCATION 

•  Mount approximately 5 feet above the floor on an inside wall of the 

living space.

•  Do not locate dehumidistat in the direct path of drafts from open 

doors and windows.

•  Do not install where operation might be affected by lamps, outside 

sources of humidity (i.e. shower), fireplace, registers, or radiators.

DEHUMIDISTAT LOCATION

90-1425

Supply collar 

mounted to 

top of unit

Outlet cover 

plate moved to 

outlet panel

2-1/8" CLEARANCE

FOR LEVELING FEET

VIBRATION ISOLATORS

FILTER ACCESS DOOR

OUTLET

INLET

5-1/8"

MECHANICAL INSTALLATION

Run vinyl or pvc tubing from the 3/4” drain outlet on the dehumidifier inlet to a floor drain. Make sure the drain line has a constant downward 

slope and is not kinked. Refer to local codes to determine if a p-trap is required. In attic installations a drain pan with float switch is required.

See 

Float Switch

 section for wiring instructions. 

DRAIN 

FIGURE 4 – Suspended Installation

If hanging the unit, use 1/4” threaded rod and two unistruts to 

support the base just inside the leveling feet. It is recommended that 

vibration isolators be placed between the unistruts and dehumidifier 

base. See 

Figure 4

. Do not position threaded rods over filter access 

doors. There must be a minimum clearance of 12” on one side of the 

unit to allow for removal of the filter. 

SUSPENDED INSTALLATION

90-1427

OUTLET VIEW

2

Содержание 1730A

Страница 1: ...e required to protect from moving parts and electrical components CAUTION 1 Do not use in pool applications 2 If unit has been shipped or stored on its side wait 24 hours before running 3 Do not use s...

Страница 2: ...y 5 feet above the floor on an inside wall of the living space Do not locate dehumidistat in the direct path of drafts from open doors and windows Do not install where operation might be affected by l...

Страница 3: ...ORATION OFF A COIL AIR IS PULLED FROM MAIN RETURN DUCT DEHUMIDISTAT WITH SET POINT KNOB CONDENSATE HOSE TO COMMON DRAIN OR OUTSIDE Figure 5 Basement Installation 90 1423 MAIN RETURN DUCT DEHUMIDIFIER...

Страница 4: ...e wired to activate the HVAC blower during dehumidification This is recommended because it offers better circulation and balancing of the indoor air conditions Note Running the HVAC blower during dehu...

Страница 5: ...E terminals from the circuit board remove the two wires and cut off bare leads Once cut the wires may remain in the unit 9 Run a 2 wire cable 18 22AWG from the dehumidifier to the wall mount location...

Страница 6: ...ow the wiring access panel Verify the green LED is on The green LED is on when power is applied to the system 4 Rotate the dehumidistat knob fully clockwise to ON position 5 If setup is correct the de...

Страница 7: ...ocedure Red LED On Blower compressor not running Open Float Switch If float switch not installed confirm jumper installed at FLOAT SWITCH terminals If float switch installed confirm switch is not open...