If the dehumidifier is installed in an attic or an area requiring leak 

protection, the unit must be placed in a drain pan with a normally 

closed condensate overflow safety switch (float switch). The float 

switch should be wired to the FLOAT SWITCH terminals on the circuit 

board on the outlet panel (See 

Figure 12

). The compressor is disabled 

when the float switch is open.

WIRING INSTRUCTIONS 

1.   Remove wiring access panel on the outlet panel. 
2.   Unplug the FLOAT SWITCH terminals and remove the jumper.
3.   Run a 2-wire cable from the dehumidifier to the float switch.
4.   Wire float switch to FLOAT SWITCH terminals and plug the 

terminals back into circuit board (

Figure 12

). 

5.   Replace the wiring access panel.

FLOAT SWITCH

FLOAT
SWITCH 

LOW VOLTAGE

NORMALLY CLOSED

FLOAT SWITCH

FIGURE 12 – Wiring to Float Switch

90-1429

START UP/SySTEM CHECKOUT

1.  Check the wiring and restore power to the HVAC equipment (if 

applicable).

2.  Plug in the dehumidifier and turn on/off switch ON.
3.  Check LED indicators located below the wiring access panel. Verify 

the green LED is on. The green LED is on when power is applied to 

the system.

4.  Rotate the dehumidistat knob fully clockwise to ON position.
5.  If setup is correct, the dehumidifier blower, and HVAC fan 

(if applicable) will turn on. The compressor will turn on after 

the dehumidifier blower has run for 3 minutes. Refer to the 

TROUBLESHOOTING GUIDE

 if the dehumidifier blower and/or 

compressor do not activate. 

6.  Check LED indicators. Green should remain on. If Red LED is on, 

refer to the 

TROUBLESHOOTING GUIDE

. The red LED turns on 

when a fault condition is active. Possible fault conditions include 

open float switch or open high temperature switch.

7.  After verifying operation, rotate the dehumidistat knob counter-

clockwise to set the dehumidifier to the desired dryness level. 

Start at 3 for most installations. Moving the knob towards “MORE 

DRY” will increase the amount of time the dehumidifier runs, 

making conditions dryer. Moving the knob towards “LESS DRY” 

reduces the amount of time the dehumidifier runs, allowing for 

higher humidity levels. See 

Figure 13

 for knob setpoints and 

corresponding %RH levels (+/- 6% RH). 

67%

55%

30%

80%

42%

FIGURE 13 – Dehumidistat Setpoints

90-1430

6

Содержание 1730A

Страница 1: ...e required to protect from moving parts and electrical components CAUTION 1 Do not use in pool applications 2 If unit has been shipped or stored on its side wait 24 hours before running 3 Do not use s...

Страница 2: ...y 5 feet above the floor on an inside wall of the living space Do not locate dehumidistat in the direct path of drafts from open doors and windows Do not install where operation might be affected by l...

Страница 3: ...ORATION OFF A COIL AIR IS PULLED FROM MAIN RETURN DUCT DEHUMIDISTAT WITH SET POINT KNOB CONDENSATE HOSE TO COMMON DRAIN OR OUTSIDE Figure 5 Basement Installation 90 1423 MAIN RETURN DUCT DEHUMIDIFIER...

Страница 4: ...e wired to activate the HVAC blower during dehumidification This is recommended because it offers better circulation and balancing of the indoor air conditions Note Running the HVAC blower during dehu...

Страница 5: ...E terminals from the circuit board remove the two wires and cut off bare leads Once cut the wires may remain in the unit 9 Run a 2 wire cable 18 22AWG from the dehumidifier to the wall mount location...

Страница 6: ...ow the wiring access panel Verify the green LED is on The green LED is on when power is applied to the system 4 Rotate the dehumidistat knob fully clockwise to ON position 5 If setup is correct the de...

Страница 7: ...ocedure Red LED On Blower compressor not running Open Float Switch If float switch not installed confirm jumper installed at FLOAT SWITCH terminals If float switch installed confirm switch is not open...

Страница 8: ...ESEARCH PRODUCTS CORPORATION P O Box 1467 Madison WI 53701 1467 Phone 608 257 8801 Fax 608 257 4357 www aprilairepartners com 10008611 6 09 B2204896A 2009 Research Products Corporation Printed in U S...

Отзывы: