Model 1730A Compact Dehumidifier

Installation Instructions

SPECIFICATIONS

Dimensions:

  Width: 12.5” cabinet, 13” with doors 

Height: 14.5” cabinet, 17” with 2.5” leveling feet 

Length: 22” cabinet, 27” with collars

Weight:

 65 lbs.

Capacity:

  65 pints/day @ 150 cfm 

AHAM DH-1-2003 80°F, 60% RH conditions

Efficiency:

  1.8 Liters per kilowatt hour 

AHAM DH-1-2003 80°F, 60% RH conditions

Power:

  115VAC, 60 Hz, 8A Operating Current 

Unit equipped with 8 ft. grounded power cord 

Dedicated 15 Amp circuit recommended

Airflow: 
 

 

 

Inlet Air Operating Conditions:

 60°F to 95°F, 30% RH to 99% RH 

Installation Conditions:

 40°F to 140°F, 0% RH to 99% RH

Evaporator Frost Sensor:

  25°F +/- 5°F, circuit opens (cut-out) 

55°F +/- 5°F, reset temperature (cut-in)

Filter:

 MERV 8, washable

Dehumidistat Control Accuracy:

 +/- 6%RH with +/-6% Differential

 WARNING

1.  120 volts may cause serious injury from electric shock. Disconnect electrical power 

before starting installation. Leave power disconnected until installation is complete.

2.  Sharp edges may cause serious injury from cuts. Use care when cutting plenum 

openings and handling ductwork.

3.  Dropping may cause personal injury or equipment damage. Handle with care.
4.  Do not remove the inlet or outlet screen. Both screens are required to protect from 

moving parts and electrical components. 

 CAUTION

1.  Do not use in pool applications.
2.  If unit has been shipped or stored on 

its side, wait 24 hours before running.

3.  Do not use solvents or cleaners on or 

near the circuit board.

P ("w.c.)

Airflow (cfm)

0

230

0.25

190

0.50

150

LOCATION CONSIDERATIONS

1. 

 Install Unit Indoors:

 Do not expose to elements.

2. 

 Drain Accessibility:

 If a drain is not located in the 

installation area, a condensate pump may be required.

3. 

 Power:

 Dedicated outlet within 8 feet of unit.

4. 

 Filter Access:

 Allow for 12” clearance on one side of 

the unit for removal of filter. (

Figure 1

)

5. 

 Inlet:

 If inlet is not ducted, a minimum of 6” of open 

space is required from the inlet panel to an adjacent 

surface.

TOP VIEW

FILTER

12" MINIMUM CLEARANCE

      FOR FILTER

      (EITHER SIDE)

6" MINIMUM CLEARANCE

FOR PROPER AIR FLOW

90-1426

FIGURE 1 – Filter 

Access Clearance

UNPACKING AND CONTENTS

Do not tip unit to remove from carton.

1.  Open carton completely using cut line shown along bottom 

perimeter of carton.

2.  Remove all cardboard inner pack (top edges and duct collars).
3.  See 

Figure 2

 for opening view and contents. 

a.

 Installation Manual 

b.

 Owner’s Manual 

c.

 Dehumidistat (mounted to inlet panel) 

d.

 Bag with Dehumidistat Cover Plate, Screws (2), Anchors (2) 

e.

 Outlet with Back Flow Damper 

f.

  8 ft. Grounded Power Cord 

g.

 Wiring Access Panel

a b

c

d

e

f

g

FIGURE 2 – Carton 

Opening & Contents

90-1464

Содержание 1730A

Страница 1: ...e required to protect from moving parts and electrical components CAUTION 1 Do not use in pool applications 2 If unit has been shipped or stored on its side wait 24 hours before running 3 Do not use s...

Страница 2: ...y 5 feet above the floor on an inside wall of the living space Do not locate dehumidistat in the direct path of drafts from open doors and windows Do not install where operation might be affected by l...

Страница 3: ...ORATION OFF A COIL AIR IS PULLED FROM MAIN RETURN DUCT DEHUMIDISTAT WITH SET POINT KNOB CONDENSATE HOSE TO COMMON DRAIN OR OUTSIDE Figure 5 Basement Installation 90 1423 MAIN RETURN DUCT DEHUMIDIFIER...

Страница 4: ...e wired to activate the HVAC blower during dehumidification This is recommended because it offers better circulation and balancing of the indoor air conditions Note Running the HVAC blower during dehu...

Страница 5: ...E terminals from the circuit board remove the two wires and cut off bare leads Once cut the wires may remain in the unit 9 Run a 2 wire cable 18 22AWG from the dehumidifier to the wall mount location...

Страница 6: ...ow the wiring access panel Verify the green LED is on The green LED is on when power is applied to the system 4 Rotate the dehumidistat knob fully clockwise to ON position 5 If setup is correct the de...

Страница 7: ...ocedure Red LED On Blower compressor not running Open Float Switch If float switch not installed confirm jumper installed at FLOAT SWITCH terminals If float switch installed confirm switch is not open...

Страница 8: ...ESEARCH PRODUCTS CORPORATION P O Box 1467 Madison WI 53701 1467 Phone 608 257 8801 Fax 608 257 4357 www aprilairepartners com 10008611 6 09 B2204896A 2009 Research Products Corporation Printed in U S...

Отзывы: