EXTRA FUNCTIONS
The following three options are only available if you have made the corresponding selection on the
Service / Extra
menu discussed in Section
1.4.
2.11 Thermostat Function:
2.11.1 Start:
When the water temperature at the top of the system tank (
T3
) falls below this setting,
P3
will
engage and start to transfer additional heat from the external tank or heat source.
(Adjustable from 68°F to 194°F with factory default set at 104°F)
2.11.2 Hysteresis:
When the water temperature at the top of the system tank (
T3
) exceeds the
Start
temperature
(see
2.11.1
above) plus the
Hysteresis
setting,
P3
will disengage.
(Adjustable from 3°F to 54°F with factory default set at 18°F)
Service
--------- - ---
English
Time and date
System
Extra thermostat
--
External sensor
no
Protection func.
Flow meter
no
Settings
--
------------
dT Max tank1
49°F
dTMin tank1
38°F
Maxtemp tank2
149°F
dT Max tank2
49°F
dT Min tank2
38°F
Min rev pump
100%
Thermostat Start 104°F
Settings
--
------------
dTMin tank1
38°F
Maxtemp tank2
149°F
dT Max tank2
49°F
dT Min tank2
38°F
Min rev pump
100%
Thermostat Start
104°F
Thermostat Hyst 12°F
Water temperature at top of tank1
T3
(°F)
T3 start
T3 start +
hysteresis
Extra P3