UIM

ip

 - TAD 

02.03.2017 

 

7 / 19 

 

4.3

 

KNX

 

T

ELEGRAMS IN THE 

IP

 

N

ETWORK

 

 
The 

UIM

ip

 can be used as an interface in a network installation field.  In accordance with the 

KNXnet/IP  protocol  specification  the 

UIM

ip

  sends  telegrams  from  theKNX  network  to  the 

IP network and vice versa.

 

If the IP address is changed from the IP sideit might happen that the 

ETS  does  no  longer  recognize  the  device.  Then  the  connection  canno  longer  be  established 
(Tunneling uses IP addresses!). 
 

Please note: 

 

As a precaution, always run a restart or change the IP address from the TP side. 

 

If there are problems with the IP address assignment please ask your administrator. 

 

According  to  the  topology,  the  additional  physical  addresses  for  tunnelling  always 
have to be assigned in the range of sub line addresses. For more information about 
the  additional  tunneling  addresses  please  refer  to 

Tunneling  Addresses  (Additional 

Physical Addresses)

.

 

 
 
 
 
 

5

 

A

PPLICATION 

D

ESCRIPTION

 

 
The  IP  Interface  is  designed  for  use  in  10/100  BaseT  networks  compliant  to  IEEE802.3. 
The  device  features  an  AutoSensing  function  and  sets  the  baud  rate  (10  Mbit  or  100  Mbit) 
automatically.  The  IP  address  of  the  device  can  be  received  from  a  DHCP  server. 
For  this  purpose  the  ETS  automatic  assignment  setting  of  the  IP  address  is  required. 
If  no  DHCP  server  is  found  with  this  setting,  the  device  starts  an  AutoIP  procedure  and 
autonomously  assigns  an  IP  address.  The  IP  address  which  the  device  receives  during 
its  start-up  (via  DHCP  or  AutoIP)  is  retained  until  the  next  start-up  (e.g.  due  to 
switching  on/off  or  reprogramming).  If  the  IP  address  of  the 

UIM

ip

  is  supposed 

to  have  a  fixed  assignment,  in  the  ETS  a  fixed  IP  address  (as  well  as  a  subnet  mask  and 
a standard gateway) can be set. 
 
 

 

Содержание UIMip

Страница 1: ... The reproduction transmission and use of this document or its contents is not permitted without written authority All rights reserved DOCUMENTATION UIMip TECHNICAL AND APPLICATION DESCRIPTION Authors Manouchehr Ghahramanian Golzar Peter Hauner Last Modification 2017 03 02 2001 2017 Apricum d o o Mažuranićeva 4 21312 Podstrana Hrvatska ...

Страница 2: ...ware Update 6 4 3 KNX Telegrams in the IP Network 7 5 Application Description 7 6 ETS Parameters 8 6 1 General 8 6 2 IP Configuration 8 7 Web Front End 10 7 1 Accessing the Device 10 7 1 1 Via the Windows Network with UPnP 10 7 1 2 Via the MAC Address 10 7 1 3 Via the IP Address 10 7 2 Device Info 11 7 3 KNX 11 7 4 Update 12 7 5 Tunneling Addresses Additional Physical Addresses 14 8 State of Deliv...

Страница 3: ... BUSY on the bus etc Picture 1 Front view 1 Bus state LAN LED 2 Bus state KNX TP line LED 3 Bus traffic LAN line LED 4 Bus traffic KNX TP line LED 5 Programming LED A Ethernet connector B Function button C Program button D KNX connector 1 Information basics about tunnelling and device management The presence of the Internet Protocol IP has led to the definition of KNXnet IP KNXnet IP provides the ...

Страница 4: ...is using LAN as a fast medium to exchange telegrams between the lines and or areas The UIMip is featuring a high internal amount of communication buffers being capable of smoothening peaks in the communication load course Using a high internal amount of communication buffers is suitable for networks with a high bus load UPnP is available to discover the device in an IP network In terms of topology...

Страница 5: ...ne LED 5 Programming N A On device in Boot Mode Blinking LAN line error 4 1 1PROGRAMMING BUTTON AND PHYSICAL ADDRESS ASSIGNMENT To download the desired physical address or a full ETS setting into the device during the procedure the programming button needs to be pressed The programming button is used to put the device into Program Mode With the ETS the physical address can be assigned to the devic...

Страница 6: ...button 3 s When operating in Boot Mode it is possible to update the UIMip s firmware For more detailed information concerning the update procedure please refer to the section Update In order to switch from Normal Mode to Boot Mode it is necessary to begin the firmware update procedure and use the Request Update button in the Web Front End 1 Press the programming button in Normal Mode 2 Press the f...

Страница 7: ...ub line addresses For more information about the additional tunneling addresses please refer to Tunneling Addresses Additional Physical Addresses 5 APPLICATION DESCRIPTION The IP Interface is designed for use in 10 100 BaseT networks compliant to IEEE802 3 The device features an AutoSensing function and sets the baud rate 10 Mbit or 100 Mbit automatically The IP address of the device can be receiv...

Страница 8: ...ce name 30 signs max providing an easy search of the device with the ETS or any KNXnet IP visualisation system Note If the Host name is changed by an ETS4 download a manual restart is recommended 6 2 IP CONFIGURATION Picture 5 IP configuration ETS Text Selection Factory default Comment DHCP use do not use use If DHCP is used no parameterisation of the IP parameters must be done If DHCP is not used...

Страница 9: ... address 0 255 0 255 0 255 0 255 0 0 0 0 IP Byte 1 to 4 manual input Net mask 0 255 0 255 0 255 0 255 255 255 255 0 NM Byte 1 to 4 manual input Gateway 0 255 0 255 0 255 0 255 0 0 0 0 GW Byte 1 to 4 manual input Note The configuration of the IP connectivity Host name IP address KNX multicast address is not updated automatically after an ETS download To get these values updated it is essential exec...

Страница 10: ...ual restart is recommended Then wait until the device gets visible in the list of network devices If it is still not visible make sure that the UPnP function of the network is enabled 7 1 2VIA THE MAC ADDRESS The MAC address is printed on a label of the UIMip housing Use this MAC address of the UIMip without brackets as described here http knx ipif XX YY ZZ 8080 Example XX byte 4 of the MAC addres...

Страница 11: ...Program Mode of the UIMip can be turned On or Off This function is similar to the programming button function With this the regarded device is easy to distinguish from other interfaces in the same IP network It can also be noticed what the particular device is currently processing after a change in the settings for example With the Set button and the ETS it is possible to set the Tunneling Address...

Страница 12: ... and continue with step 3 refresh request update Step 1 Open the Update tab of the Web front end Picture 10 Update Step 2 Either use the Change Program Mode function in the KNX tab or press the programming button once Picture 11 Program mode Step 3 After the Program Mode is turned to On give a short key press to the function button Then the refresh button in the Update tab needs to be pressed Alte...

Страница 13: ...select the update file and enter Boot Mode Picture 13 Request update Step 5 The device now switches to Boot Mode The update file can be selected and uploaded Pressing the Abort button cancels the firmware update procedure and the device exits the Boot Mode Picture 14 Select update file ...

Страница 14: ...ETS and select the UIMip as the Current Interface In the IP Tunneling window the already assigned host physical address can be read Picture 15 First additional physical address tunnelling address Step 2 Type the additional physical address into the Individual Address field Click on the Test button If the green Ok appears the first tunneling address is already set In this example it is set to 9 1 2...

Страница 15: ...All dimensions shown here are specified in mm The device width is 2 modules at 18 mm Picture 17 Dimension drawings Marking Design UIMip Physical address 15 15 255 Physical address for tunneling connections 15 15 241 15 15 242 15 15 243 15 15 244 IP configuration IP address assignment DHCP AutoIP IP routing multicast address 224 0 23 12 ...

Страница 16: ...t rail TH35 according to IEC60715 Protection type IP20 according to IEC60529 Pollution degree 2 according to IEC60664 1 Protection class III according to IEC61140 Overvoltage category II according to IEC60664 1 Approbation KNX certified according to ISO IEC14543 3 CE Marking According to low voltage and EMC guidelines Compliance EN50428 EN50581 EN61000 6 EN62479 Power supply Safety extra low volta...

Страница 17: ...rovided with the distribution 3 The name of the author may not be used to endorse or promote products derived from this software without specific prior written permission THIS SOFTWARE IS PROVIDED BY THE AUTHOR AS IS AND ANY EXPRESS OR IMPLIED WARRANTIES INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED IN NO EVENT SHALL THE ...

Страница 18: ...the configuration of the IP network please refer to IP Configuration Q I tried to reach the Web front end of my UIMip but I wasn t successful What can I do A Make sure the http matches your device IP along with the port address 8080 Or type the MAC address into the browser s address bar in exactly the way as explained see Via the MAC Address Then wait for about 5 15 seconds refresh your browser an...

Отзывы: