7.  Move the  transmitter left, right, up, down until the LED on the  receiver 

fl

 ashes fast

.  Hold the  transmitter in this position.

8.  Reduce the signal strength by turning the potentiometer slowly clock-

wise until the  receiver stops 

fl

 ashing.

9.  Move the  transmitter from right to left, in order to see if the  receiver 

LED can be made to 

fl

 ash fast again.  If it can, repeat step 8.

     Repeat this procedure but this time move the transmitter up and 

down.

10.The beam detector is correctly aligned if there is no 

fl

 ash after carrying 

out the movements described.

11. Tighten the securing bolts and screws of the  transmitter, making sure 

it does not move and replace the plug covering the potentiometer.  
Failure to replace the plug may result in false alarms due to  ingress 
of contaminants.

 fast 

fl

 ash 

signal too strong 

 slow 

fl

 ash 

signal too weak

 no 

fl

 ash 

signal correct

     To con

fi

 rm the correct alignment of the detector move the  transmitter 

slowly up, down, left and right.  Each movement should cause the LED 
in the  receiver to 

fl

 ash slowly.  Leave in centre position with no LED 

fl

 ashing.

Tx

100m

00m

Tx

Rx

Receiver
LED

Rx

!

NO

FLASH

Rx

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Smoke Detector XP95

Страница 1: ...DETECTOR INSTALLATION GUIDE Apollo Fire Detectors 36 Brookside Road Havant Hampshire England www apollo fire co uk PP2079 2002 Issue 6 FIRE DETECTORS LIMITED www acornfiresecurity com www acornfiresec...

Страница 2: ...the total obscuration signal 6 Setting the address 7 Address settings 7 Installing transmitter and receiver 8 Retro operation 9 Alignment and calibration 9 Aligning the beam detector 10 Calibrating th...

Страница 3: ...sts Read the guide through once in order to understand the steps needed to install and align correctly Then when installing keep the guide handy and use it to find help on the subject you are currentl...

Страница 4: ...fault signal In the event of a fire being detected when the beam detector has reached its compensation limit the fire signal will override the fault signal SYSTEM DESIGN Positioning beam detectors Th...

Страница 5: ...es of practice A ceiling or roof with a slope in excess of 3 5 should be regarded as a pitched roof calculation it is recommended that not more than five beam detector sets are powered from each loop...

Страница 6: ...ation signal Total obscuration is defined as obscuration of the beam to greater than 93 in 8 10 seconds The interface must be set so that either a fire or a fault signal is generated when this occurs...

Страница 7: ...16 32 64 NORMAL OPERATION Address 1 ALIGNMENT MODE 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 91 41 42 43 44 45 46 47 48 49 50 51 52...

Страница 8: ...ye Ensure that the transmitter is fitted so that access to the range potentiometer under the clear plug on the side is not impeded 4 Tighten both the receiver thumbwheel screws securely using a suitab...

Страница 9: ...s been returned via a surface other than the reflectors Alignment and calibration The transmitter produces a conical beam of light which is approximately 3 metres in diameter at a distance of 100 metr...

Страница 10: ...the LED to be visible over the entire beam length ie up to 100 metres During commissioning of the beam detector the LED will be in one of the following states Calibrating the beam detector The beam de...

Страница 11: ...an be moved with slight resistance up down left and right 4 Remove the plug on the transmitter 5 Using a 0 point cross head or terminal screwdriver turn the potentiometer fully anti clockwise This adj...

Страница 12: ...d if there is no flash after carrying out the movements described 11 Tighten the securing bolts and screws of the transmitter making sure it does not move and replace the plug covering the potentiomet...

Страница 13: ...the HI and LO LEDs have extinguished If they have not the alignment procedure has to be repeated 13 Set segment 8 of the DIL switch on the interface to normal opera tion 64 No Op de www acornfiresecu...

Страница 14: ...output in the interface is enabled The remote indicator output is useful in locations where the interface is not easily visible from the ground and confirmation of a fire signal is required Notes 1 Wh...

Страница 15: ...and it is not possible to replace older versions with the enhanced version separately In such cases both interface and receiver must be replaced if a new receiver is to be installed The transmitter i...

Страница 16: ...nsmitter not aligned with receiver Transmitter power too low No power to transmitter Receiver not pointing toward transmitter Interface alarm LED illuminated Beam is in alarm condition See notes Inter...

Страница 17: ...Screened 4 core MICC for example 100m Finish White IP Rating 50 Operating temperature 200 C to 550 C Sizes and weights Interface 147 x 85 x 22 mm 200g Heads with Brackets 83 x 115 x 135 mm 400g each...

Страница 18: ...18 FIRE DETECTORS LIMITED www acornfiresecurity com www acornfiresecurity com...

Отзывы: