background image

9

Retro operation

The XP95 beam detector may be con

fi

 gured so as 

to operate in ‘retro’ mode*, in which the  transmitter 
and  receiver are mounted adjacent and as close as 
possible to each other, no more than 5mm apart.  The 
infra-red beam is projected onto re

fl

 ectors mounted on 

the opposite wall, which re

fl

 ect it back to the  receiver.  

This type of operation is useful when access to the wall 
opposite the  transmitter is restricted or where wiring 
is dif

fi

 cult.  The re

fl

 ectors should be mounted at right 

angles to the infra-red beam.  See ‘Technical Data’ for 
number of re

fl

 ectors to use.  If more than one re

fl

 ector 

is used, they should 
be  fitted  so  that 
there are no gaps 
between them.

A clear line of sight 
has to be main-
tained between 
the  transmitter and 
 receiver at one end 
and the reflectors 
at the other end 
of the area to be 
protected.

The following 
extra test should 
be performed after installation for retro operation:

When the system is aligned and in normal operat-
ing mode, cover the re

fl

 ectors.  The XP95 beam 

detector should indicate ‘

fi

 re’ or ‘fault’, depending 

on the setting in the  interface.  (See section ‘Instal-
lation of  interface’).  If not, it is possible that the 
signal has been returned via a surface other than 
the re

fl

 ectors.

Alignment and calibration

The  transmitter produces a conical beam of  light which 
is approximately 3 metres in diameter at a distance of 
100 metres.  The purpose of 

alignment

 is to ensure 

that the centre of the beam is projected onto the centre 
of the  receiver (Fig 7).

The purpose of 

calibration 

is to ensure that the amount 

of light sent by the  transmitter is correct for the distance 
between the  transmitter and the  receiver.

The accuracy of calibration depends on the accuracy 
of alignment.  The XP95 beam detector is tolerant, to 
a certain extent, of alignment and calibration that is 
not optimal, but misalignment may lead to faults at a 
time subsequent to commissioning, perhaps because 
structural movement in the building occurs (Fig 8).

The XP95 beam detector has been designed with ease 
of commissioning in mind and is aligned and calibrated 
using an LED.

*In retro operation smoke passes 
through the projected beam twice;  
the alarm level should therefore be 
set to 65% obscuration.

Fig 8

  Beam detector misaligned

receiver

light cone

transmitter

Side view of transmitter and receiver

End view of receive

r

centre of beam misses receiver

receiver

light cone

transmitter

Side view of transmitter and receiver

End view of receive

r

Fig 7

  Beam detector correctly aligned 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Smoke Detector XP95

Страница 1: ...DETECTOR INSTALLATION GUIDE Apollo Fire Detectors 36 Brookside Road Havant Hampshire England www apollo fire co uk PP2079 2002 Issue 6 FIRE DETECTORS LIMITED www acornfiresecurity com www acornfiresec...

Страница 2: ...the total obscuration signal 6 Setting the address 7 Address settings 7 Installing transmitter and receiver 8 Retro operation 9 Alignment and calibration 9 Aligning the beam detector 10 Calibrating th...

Страница 3: ...sts Read the guide through once in order to understand the steps needed to install and align correctly Then when installing keep the guide handy and use it to find help on the subject you are currentl...

Страница 4: ...fault signal In the event of a fire being detected when the beam detector has reached its compensation limit the fire signal will override the fault signal SYSTEM DESIGN Positioning beam detectors Th...

Страница 5: ...es of practice A ceiling or roof with a slope in excess of 3 5 should be regarded as a pitched roof calculation it is recommended that not more than five beam detector sets are powered from each loop...

Страница 6: ...ation signal Total obscuration is defined as obscuration of the beam to greater than 93 in 8 10 seconds The interface must be set so that either a fire or a fault signal is generated when this occurs...

Страница 7: ...16 32 64 NORMAL OPERATION Address 1 ALIGNMENT MODE 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 91 41 42 43 44 45 46 47 48 49 50 51 52...

Страница 8: ...ye Ensure that the transmitter is fitted so that access to the range potentiometer under the clear plug on the side is not impeded 4 Tighten both the receiver thumbwheel screws securely using a suitab...

Страница 9: ...s been returned via a surface other than the reflectors Alignment and calibration The transmitter produces a conical beam of light which is approximately 3 metres in diameter at a distance of 100 metr...

Страница 10: ...the LED to be visible over the entire beam length ie up to 100 metres During commissioning of the beam detector the LED will be in one of the following states Calibrating the beam detector The beam de...

Страница 11: ...an be moved with slight resistance up down left and right 4 Remove the plug on the transmitter 5 Using a 0 point cross head or terminal screwdriver turn the potentiometer fully anti clockwise This adj...

Страница 12: ...d if there is no flash after carrying out the movements described 11 Tighten the securing bolts and screws of the transmitter making sure it does not move and replace the plug covering the potentiomet...

Страница 13: ...the HI and LO LEDs have extinguished If they have not the alignment procedure has to be repeated 13 Set segment 8 of the DIL switch on the interface to normal opera tion 64 No Op de www acornfiresecu...

Страница 14: ...output in the interface is enabled The remote indicator output is useful in locations where the interface is not easily visible from the ground and confirmation of a fire signal is required Notes 1 Wh...

Страница 15: ...and it is not possible to replace older versions with the enhanced version separately In such cases both interface and receiver must be replaced if a new receiver is to be installed The transmitter i...

Страница 16: ...nsmitter not aligned with receiver Transmitter power too low No power to transmitter Receiver not pointing toward transmitter Interface alarm LED illuminated Beam is in alarm condition See notes Inter...

Страница 17: ...Screened 4 core MICC for example 100m Finish White IP Rating 50 Operating temperature 200 C to 550 C Sizes and weights Interface 147 x 85 x 22 mm 200g Heads with Brackets 83 x 115 x 135 mm 400g each...

Страница 18: ...18 FIRE DETECTORS LIMITED www acornfiresecurity com www acornfiresecurity com...

Отзывы: