3
Customer Service
(704) 841-6000
backflow.apollovalves.com
ES1597 REV A.
BFMMDC4ANLBF
FIGURE 1
TC: TEST COCK
CV: CHECK VALVE
The Double Check Valve (DC) device consists of two independently-acting, spring-loaded check valves. Two resilient seated
shut-off valves and four test cocks complete the assembly. Each check is designed to maintain a minimum of 1 psi across the
check during normal operation. If at any time the pressure downstream of the device increases above the supply pressure, both
check valves will close to prevent any backflow from occurring. The no flow condition is illustrated in Figure 1. To initiate flow, supply
pressure must be sufficient to open both checks and overcome friction, normally a minimum of 3 to 5 psi above the downstream pressure.
I.
DESCRIPTION AND OPERATION
II. INSTALLATION
1. The DC must be installed in an accessible location to facilitate periodic field testing and maintenance.
2. Flush all upstream POST INDICATORPOST INDICATORng thoroughly to remove foreign matter prior to installing the device.
3. The device may be installed in the n-flow position as shown in Figure 1. Adequate clearance between the lower most portion of the device and
flood grade or floor should be provided for ease of maintenance.
4. If shut-off valves are provided separately, they should be installed with test cocks on the upstream and downstream sides of
5. The wedge of the inlet shut-off valve (as shown in Figure 1). Contact local jurisdictional authorities for local requirements.
6. After installing the assembly and with downstream or #2 shut-off valve closed, pressurize the device and bleed air through test cock #4. Then
open #2 shut-off valve.
Note: Pressures are for illustrative purposes only and are not necessarily indicative of any actual valve.