inverter is still in a standby mode at this moment, and is waiting for the mains 

power to restore and the input of PV energy.

When the battery voltage is charged to 52V, the PV inverter will automatically 

switch back to the inverter power output to supply power to the loads.

Remark:

The  advantage  of  PV  power  saving  mode  is  to  maximally  supply  power  to 

loading devices by using solar energy, while the mains power is only used as a 

backup  power  supply  under  extreme  conditions.  Accordingly,  PV  power 

saving mode is suitable to use at the places where the mains power supply is 

unstable  or  unavailable,  such  as  in  the  remote  mountain  areas,  plateau, 

yachts,  vehicles,  etc.  However,  batteries  might  stay  in  a  relatively  low  level 

under  extreme  weather  conditions  for  a  long  time.  Therefore,  we  suggest 

users  to  manually  switch  the  mode  into  UPS  and  wait  for  a  better  weather 

condition before switch it back to a PV mode.

3.3 System Initial Setting

All  series  of  product  models  contained  in  this  User  Manual  are  having  the 

inverter  output  of  230V/50Hz  in  the  PV  power  saving  mode  as  factory  default 

setting.  Users  can  adjust  the  setting  values  via  the  front  panel  “Setting”  function 

keys  (Refer  to  Section  3.4  for  setting  procedure)  to  suit  different  environment  or 

individual needs. After the new setting is completed, the PV inverter needs to be 

switched  off  and  then  restarted,  and  the  user's  setting  values  are  saved  as  the 

initial  setting  values. And  in  the  subsequent  reset,  the  last  setting  values  will  be 

applied as the system initial setting values.

3.4 Steps for System Mode Setting

The 1st layer is an uninterrupted mode (UPS mode) and the PV power saving 

mode settings through the following steps:

Smart HF Series

 

Single-phase

 

PV

 

Off

-

grid

 

Inverter

--

System

 

Operation

 

Mode

 

Introduction

Step 1:

 When reset the PV inverter, please turn it off beforehand. The battery 

pack  must  be  connected  to  the  inverter,  whereas  the  mains  power  input  can  be 

connected  or  not  be  connected  and  no  loads  should  be  connected  with  the  PV 

inverter.

Step  2:

  After  turning  on  the  PV  inverter's  power  switch  to  the  “ON”  position 

and  wait  for  the  LED  display  to  light  up,  press  and  hold  the  “Setting”  button  for 

about 5 seconds with a no-conductive tool, and wait until the PV inverter sounding 

a  long  beeping  alarm  before  releasing  the  setting  button.  It  is  an  indication  that 

the  PV  inverter  has  entered  to  the  setup  program,  in  which  the  LOAD  LED  1  is 

lighted as an implication of the PV inverter is at the 1st layer setting.

Step  3:

  Please  refer  to  Table  3.1  to  decide  whether  it  is  a  desirable  mode  of 

operation.  If  the  LED  light  indicator  shows  it  is  the  correct  mode  of  operation, 

please  press  and  hold  the  “Setting”  button  for  about  3  –  5s,  until  the  PV  inverter 

making  a  beep  sound  and  entering  to  the  2nd  level  output  voltage  setting 

(LOADLED2 is lighted). If not, please press and hold the “Setting” button for about 

1s  then  release. The  light  signal  changes  at  each  press,  and  after  adjusting  it  to 

the required mode, press the “Setting” button for about 3 – 5s until the PV inverter 

is making a beep sound to indicate the completion of setting. At this time, release 

the “Setting” button to enter to the 2nd layer of output voltage setting. The LOAD 

LED 2 is lighted means that the PV inverter is entering to the 2nd layer setting.

PV Saving Mode 

(Initial setting)

Run

Min.ALM

Maj.ALM

Run

Min.ALM

Maj.ALM

Uninterrupted 

Mode (UPS mode)

Bright

Dark

Table3.1: Operation mode LED display

The 2nd layer output voltage setting is described as follows:

Step  1:

  Please  refer  to  the  LED  signal  comparison  detailed  in  Table  3.2  to 

determine whether a desirable output voltage is being selected. If the selection is 

correct, please press and hold the “Setting” button for 3 – 5s until the PV inverter 

sounds  a  beep  before  entering  to  the  3rd  layer  output  frequency  setting  (LOAD 

LED 2 is lighted). If not, please follow Step 2 for setting the output voltage.

Step  2:

  Please  press  and  hold  the  “Setting”  button  for  about  1s  and  then 

release  it.  In  this  way,  the  light  signal  changes  for  each  press  (Change  of  order: 

208V→220V→230V→240V). And when adjusting it until the required voltage

Smart HF Series

 

Single-phase

 

PV

 

Off

-

grid

 

Inverter

--

System

 

Operation

 

Mode

 

Introduction

17/36

PROFESSIONAL

 

INNOVATIVE

 

BRANDING

 

SERVICE

16/36

PROFESSIONAL

 

INNOVATIVE

 

BRANDING

 

SERVICE

Содержание PV248-2000HFPR

Страница 1: ...www apmtech cn APM Technologies Dongguan Co Ltd USER MANUAL APM TECHNOLOGIES PROFESSIONAL INNOVATIVE BRANDING SERVICE Smart HF Series Single phase PV Off grid Inverter ...

Страница 2: ......

Страница 3: ...說 明 INTRODUCTION 1 9 Part NO 18950 358 00 PD USER MANUAL APM Technologies Dongguan Co Ltd Smart HF Series Single phase PV Off grid Inverter ...

Страница 4: ......

Страница 5: ...nitial Setting 3 4 Steps for System Mode Setting 3 5 Monitoring Software Optional 3 6 Protection Malfunction Warning Display 4 Installation and Wiring 4 1 Battery Connection Cables 4 2 Proposed Battery Pack Configuration 4 3 Packing List 4 4 Quick Installation Guide 4 5 Schematic Diagram of System Installation 4 6 Deduction Amount Usage 4 7 Precautions of Load Application 5 Common Faults Solutions ...

Страница 6: ...le for the following models of single phase PV off grid inverters PV248 2000HFR W PV248 2500HFR W PV248 3000HFR W PV248 3500HFR W PV248 4000HFR W PV248 4500HFR W All descriptions given in this User Manual are applicable to the following models of Series Single phase PV Off grid Inverter Pure PV off grid inverters without mains complementary or mains charging function PV248 2000HFPR W PV248 2500HFP...

Страница 7: ...uced without permission The contents of this User Manual will be constantly updated and revised and therefore mismatches or wrong descriptions of the products might occur Please refer to the actual purchase download or acquire the latest User Manual from www apmtech cn or salesperson 1 36 PROFESSIONAL INNOVATIVE BRANDING SERVICE ...

Страница 8: ...Never put the battery or battery bank nearby a fire source 7 Battery aging problem is increased with its increasing usage Once the aging problem is surfaced please has the battery changed by a professional technician to avoid incident of battery cell leakages that may result in a spontaneous combustion It is recommended to perform a routine maintenance inspection on the battery Smart HF Series Sin...

Страница 9: ... output and then to household appliances 3 For battery terminal side External Miniature circuit breakers shall be used for final installation hazardous voltage and eneygy on battery terminal Battery compartments shall be used The battery compartments shall be at least basic insulation between it s live parts and metal frame 4 For PV input side External Miniature circuit breakers and Array insulati...

Страница 10: ...g components when the power supply is applied Hazardous voltages may still be present in the inverter even if the external circuit breakers are all switched off Wait at least 500 s after switching off the inverter This ensures that the capacitors are electrically discharged Do not dispose of the product together with household waste but only in accordance with the locally applicable regulations fo...

Страница 11: ...n order to cut back the amount of electricity energy feeding by the local power grid Only when the battery power is lower than the battery protection shutdown point the power supply will be obtained from the bypass local grid or the inverter shutdown so as to prolong the battery life Users can choose the correct operating mode according to their own needs or weather conditions Smart HF series prod...

Страница 12: ...sformer isolation technology Max efficiency is up to 93 Rated output power 100 load Instantaneous output power 150 load Output voltage efficiency and operating mode are adjustable via the front panel or remote monitoring Built in input and output bypass protection functions UPS and PV energy saving modes that can easily be switched over Equipped with a controllable bypass for local grid power outp...

Страница 13: ...ntinuous AC output power VA Maximum continuous AC output current A Power factor range Maximum output fault current Maximum output over current protection Protections 230 Va c 208 Va c 220 Va c 230 Va c 240 Va c 50 Hz Pure sine wave THD 3 0 Max 93 2500VA 3000VA 3500VA 4000VA 4500VA 9A 11 5A 14A 16 5A 19A 21 5A 1 1 1 1 1 1 18A 23A 28A 33A 38A 43A 13 5A 17A 21A 25A 28 5A 32A SCP OLP OPT AC input Nomi...

Страница 14: ... 2000W 2500W 3000W 3500W 4000W 4500W General parameters OCP Battery RCP Low battery automatic alarm Low battery automatic cutoff Protective class Ingress protection IP Relative humidity range Allowable Altitude Storage temperature range Ambient service temperature range Dimension Reference Weight Reference I IP20 5 to 85 Non condensing 2000m For over 2000m the rated power decreases 10 by every 100...

Страница 15: ...FF switch When switch is at ON position the inverter is operating whereas when it is at Off position the inverter is shut down LED display panel Display the operating condition load capacity battery voltage and other information of the inverter Setting work mode output voltage frequency and power saving mode and other function settings Air intake hole For heat dissipation continuous ventilation mu...

Страница 16: ...e LED is flashing it implies the PV input is LED display panel To display the operating status loading capacity battery voltage and other information Function setting button Operation mode output voltage frequency and power saving mode and other function settings Wall mounting hole 2 2 Front Panel LED Display LED Display Loading LED 1 ON 0 25 LED 1 2 ON 26 50 LED 1 3 ON 51 75 LED 1 4 ON 76 100 LOA...

Страница 17: ...elay There will be intermittent alarm go off to remind the users despite the PV inverter can still supply output power to loading devices Maj ALM PV inverter s malfunction indicator with the ON implying the PV inverter cannot operate normally due to a fault that the user is required to troubleshoot the issue immediately 2 3 Rear Panel Display A B Figure 2 3 1 Overview of the rear panel for rack mo...

Страница 18: ...nal PV Input Terminal PV PV Battery Input Terminal BAT BAT Exhaust Vent of Fan POWER ON OFF switch Switch to the ON position to start the PV inverter whereas switch to the OFF position to turn off the PV inverter RS485 interface Overcurrent protection device for mains power input Smart HF Series Single phase PV Off grid Inverter Display Panel Introduction 12 36 PROFESSIONAL INNOVATIVE BRANDING SER...

Страница 19: ...V inverter will take priority using the solar power source and consequently the proportion of energy saving is very high Only when the PV energy input is not available and the battery power is critically low will the PV inverter switch over to the power grid for a power supply If the power supply from a power grid is not available at this time the system will automatically shut down 3 1 UPS Mode W...

Страница 20: ...ut to shut down When battery voltage falls to 43V the battery power is almost completely drained If the mains power is still not available at this time the PV inverter will automatically shut down its output At this stage the PV inverter remains in a standby mode and waiting for the mains power to restore and the input of PV energy If the user turns the PV inverter s power switch to the OFF positi...

Страница 21: ...put to supply power to the loading devices and start the solar charger to charge the battery When the PV charging energy is lower than the energy required by the loads the battery voltage will gradually decrease When the battery voltage is below 45V the PV inverter will start rapid beeping alarm at a frequency of about 1 beep per second to alert the users that the battery power is about to run out...

Страница 22: ...witch the mode into UPS and wait for a better weather condition before switch it back to a PV mode 3 3 System Initial Setting All series of product models contained in this User Manual are having the inverter output of 230V 50Hz in the PV power saving mode as factory default setting Users can adjust the setting values via the front panel Setting function keys Refer to Section 3 4 for setting proce...

Страница 23: ...l changes at each press and after adjusting it to the required mode press the Setting button for about 3 5s until the PV inverter is making a beep sound to indicate the completion of setting At this time release the Setting button to enter to the 2nd layer of output voltage setting The LOAD LED 2 is lighted means that the PV inverter is entering to the 2nd layer setting PV Saving Mode Initial sett...

Страница 24: ...M will be all lighted LOAD LED1 4 is lighted and 10s later the inverter will be automatically restarted Then the inverter output will be based on the latest setting values If not please follow the Step 2 for setting the output frequency Step 2 Please press and hold the Setting button for about 1s and then release it In this way the light signal changes for each press And after adjusting it to the ...

Страница 25: ... Battery OCP When the battery input is over current the fuse at inverter battery input terminal will blow and it cannot be used as normal When that happened please contact a local dealer or return the appliance to manufacturer for a repair B PV Reverse Connection Protection When the PV input is reversely connected the PV inverter will stop operating and the corresponding LED light indicator light ...

Страница 26: ... When the battery voltage is extremely high or low exceeded the battery operating range PV inverter will shut down the output and Maj ALM is lighted When the battery voltage is restored to a safe range the output will be restored automatically as well Storage battery reverse connection is forbidden Battery cells cannot exceed their rated number or severe damage could happen to the PV inverter I Pa...

Страница 27: ...tial BUS Over Current AC Output Overload BUS UnderVoltage AC Output Overvoltage Over Temperature AC Output Overvoltage Fan Abnormality Table 3 5 LED indications for panel malfunction information Smart HF Series Single phase PV Off grid Inverter System Operation Mode Introduction 21 36 PROFESSIONAL INNOVATIVE BRANDING SERVICE ...

Страница 28: ...r to Table 4 1 for wire selection Rated Current A 8A 20A 20A 40A 55A 80A 80A 120A CSA mm 2 4 6 16 25 AWG Remarks 10 8 4 2 Table 4 1 Minimum recommended cross sectional areas CSA of cable 40A 55A 8 6 4 2 Proposed Battery Pack Configuration The configuration of battery pack capacity is varied according to the PV charging power load power and standby time Please refer to Table 4 2 below for battery ca...

Страница 29: ...g environment is recommended 1 1 Clean well ventilated and indoor environment 1 2Ambient temperature of ranged 20 J to 40 J 1 3 Place it out of reach of children to avoid scalding or electric shock 1 4 Installation should meet the requirement for minimum clearance of space around the inverter 2 It is prohibited to perform installation in the following environment 2 1 Environment with flammable exp...

Страница 30: ...t End Voltage Specification Current Specification 300Vac Vac 300Vac Vac 150Vdc Vdc 100Vdc Vdc 25A I 32A 25A I 32A 50A I 100A I 2 Pay attention to the surface of inverter as it is likely that the temperature remain high after the power supply of inverter is being switched off for a period of time 3 If maintenance for inverter is required please contact the authorized system installation maintenance...

Страница 31: ...on a standard communication cabinet in accordance with the requirements set forth for the cabinet Alternatively the inverter can also be installed on a horizontal platform with that all the predescribed important instructions and position requirements are fulfilled 1 4 Schematic of cable connection for a rack mounted inverter is shown in Figure 4 1 below Figure 4 1 Schematic of cable connection fo...

Страница 32: ...ed Inverter Wall mounted inverter can be installed on a wall and alternatively be placed on a horizontal platform When the inverter is to be installed on a wall the user is required to fit mounting screws on the wall according to the dimension as shown in Figure 4 2 and then securely install the inverter on the wall Smart HF Series Single phase PV Off grid Inverter Installation and Wiring 26 36 PR...

Страница 33: ... live neutral and ground wires through the 1st cable grommet from the right and pass these wires through the cable duct on the right side inner wall and then use a slot head screwdriver to connect the wires according to marking on the 3rd 4th and 5th positions It is suggested to use a standard 4mm or 10AWG wire and that the wire ends using for connection are stripped off 5mm 8mm B PV Input Termina...

Страница 34: ...After all the checks are confirmed close ON status the battery input circuit breaker and the power switch of inverter and wait for a moment until the Run LED indicator on the display panel is lighted then close the circuit breakers of PV input and AC input and check according to the user manual that the LED indicators and the inverter output voltage are in accordance with requirements After confir...

Страница 35: ...o deduction of 60 It is prohibited to operate the PV inverter at an ambient temperature of higher than 60 2 When the altitude is over 2000m the PV inverter s rated power decreases 10 by every 1000m rise 3 The use of output voltage will be lowered when the battery voltage is low which will not be higher than the 5 rated value Wire specifications length frequency transformer MCCB RCD IRDD AC input P...

Страница 36: ...uently prompt an overload message For instance the PV248 3000HF can carry the max inductive load of 1500W with the same feature like a 2P air conditioner 2P electrical motor 2P water bump and 2P motor When carrying such a load other loads should be turned off or only be added after the load is being stably operated 2 When the loading device is either capacitive or inductive please beware of that t...

Страница 37: ...lease identify the types of signal alarm according to the instructions given in User Manual and resolve it accordingly Inspect the input AC and if the battery is in an open circuit or battery voltage is too low or high Replace with a new battery Check battery specifications and increase battery capacity After being connected with PV inverter confirm that the PV charging indicator is lighted at the f...

Страница 38: ...source prior to connecting or disconnecting battery terminals f Determine if battery is inadvertently grounded If inadvertently grounded remove source from ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies no...

Страница 39: ...he claimed defect within the warranty period and timely send a scanned copy of warranty card and invoice to the APM Customer Service Center email mk apmtech cn APM will provide a service at no additional charge for the maintenance or replacements of defected product or components 2 In case of product replacement or refund all replaced or exchanged parts which are removed under this warranty will b...

Страница 40: ...F Series Single phase PV Off grid Inverter Common Faults Solutions 1 APM will bear no responsibility for the compensation of power loss caused by direct or consequential damage from product failure APM will not be responsible for the data loss in the operation of an inverter and the users should appropriately back up the data by themselves Nor will APM be responsible for the personal injury or pro...

Страница 41: ...ct Person Address Product information Product Serial No Product Name Spec Purchase Date Invoice No Warranty Period Remark Signature Date Product Malfunction Information Product Name Product Item No Product Serial No Installation Date Malfunction Date Malfunction descriptions and solutions Name Address Tel Cell Phone Fax Email Installed place User s Information System Information ...

Страница 42: ...ter and result in public health hazards You may contact the relevant agencies of the local authority in order to ensure the waste disposal is in accordance with all related local requirements and regulations The replaced products or components should be handed over to APM Technologies authorized retailer distributor or dealer and our company will recycle the used product or components within a cer...

Страница 43: ......

Страница 44: ...Service Hotline 86 76922028588 Fax 86 76922026771 Website www apmtech cn Email mk apmtech cn Add 7 Link Information Industry Park Shuilianshan Road Nancheng Dongguan Guangdong China ...

Отзывы: