1. Please ensure the DC switch is switched off.
2. Strip the cable insulating layer for 15 mm long according to the diagram below.
4.6.4 Connect to DC Terminals
!
Danger
!
!
Caution
!
Before electrical connection, please ensure the circuit breaker of DC side is cutoff.
Please ensure the voltage of each PV string does not excess 1000 V, or the solar inverter
is risking an unrecoverable damage.
3. The DC end connector includes the following parts:
15mm
15mm
Must be connected with all the strings of solar inverter.
It is suggested to connect a 1000 V/25 A circuit breaker on the DC side.
Smart MTL Series 3-Phase Inverter User Manual--Installation