4.6.2 Connect the AC Terminal
!
1. Strip the 5-core wire that has a correct specification per the length indicated below:
2. The AC side connector includes the following parts:
Danger!
The electrical connection of solar inverter with power grid can only be started after obtai-
ning an approval from the local power supply department.
3. Insert the cable through the nut and socket:
4. The cable joint is illustrated as below:
8mm
12mm
50mm
Cable Joint
Socket
Fastening Nut
Grid L1 wire to the terminal marked “1”.
Grid L2 wire to the terminal marked “2”.
Grid L3 wire to the terminal marked “3”.
Grid Neutral wire to the terminal marked “4”.
PE wire to the terminal marked .
Smart MTL Series 3-Phase Inverter User Manual--Installation
14/38