8
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
•
Electrical Connections and System Wiring Diagrams
IMPORTANT
: Refer to Chapter 5 for Hazardous Location and Non-Incendive Wiring
diagram.
Modbus System Wiring
Modbus System Wiring with RST-6001
Power
Supply
+12-24 Vdc
GND
Use Shielded Cable
120 Ω
terminating
resistor
120 Ω
terminating
resistor at
last sensor
V+
B
A
Sensor 1
GND
V+
B
A
Sensor 2
GND
V+
B
A
Sensor 3
GND
Server
Device
RS-485 A
RS-485 B
MPX Modbus
series sensor
MPX Modbus
series sensor
MPX Modbus
series sensor
EARTH
GND
Note: Earth Ground terminal is factory
connected to internal housing ground
lug.
EARTH
GND
EARTH
GND
Power
Supply
+12-24 Vdc
GND
Use Shielded Cable
Equivalent 120 Ω
terminating resistor
internal to RST-6001
120 Ω
terminating
resistor at
last sensor
USB to computer
with APG Modbus
software
RST-6001
Modbus
Controller
V+
B
A
Sensor 1
GND
V+
B
A
Sensor 2
GND
V+
B
A
Sensor 3
GND
A
B
-5V
MPX Modbus
series sensor
+5V
MPX Modbus
series sensor
MPX Modbus
series sensor
Note: An indep12-24 Vdc
power supply is required when
using an RST-6001 Modbus Controller.
The RST-6001 can only supply ±5 Vdc,
not the +12-24 Vdc required by the MPX.
EARTH
GND
EARTH
GND
EARTH
GND
Note: Earth Ground terminal is factory
connected to internal housing ground lug.
IMPORTANT
: For surge protection on MPX-E4 or -R4, either connect the grounding
screw (see pages 1-3) to an earth ground, or ensure that the tank mounting of the MPX is
grounded.