40404 - Decimal Place
Determines the number of decimal places included in the Calculated Reading(s). The Calculated Reading will
always be returned as a whole number.
For example, a Calculated Reading of 1126.658 (gallons, ft
3
, etc.) will be returned as follows:
Decimal Place = 0 Volume = 1127 (rounded to nearest whole number)
Decimal Place = 1 Volume = 11267 (divide by 10 to get true result)
Decimal Place = 2 Volume = 112666 (divide by 100 to get true result)
Decimal Place = 3 Volume = 1126658 (divide by 1000 to get true result)
40405 - Maximum Distance (Factory Calibrated)
Sets the distance (beginning from the Zero Reference) to the point where the sensor will stop looking for float
signals, usually the bottom of the stem. A float beyond the Maximum Distance value will not be detected.
40406 - Full Distance
Sets the positive distance (beginning from the sensor Zero Reference) to the point where the monitored
vessel is considered full.
40407 - Empty Distance
Sets the positive distance (beginning from the Zero Reference) to the point where the monitored vessel is
considered empty (usually the bottom of the stem).
40408 - Sensitivity (Factory Calibrated)
Sets the level of gain that is applied to the returning float signal.
40409 - Pulses (Factory Calibrated)
Controls the duration of the signal being sent down the magnetostrictive wire.
40410 - Blanking (Factory Calibrated)
S
ets the blanking distance, which is the zone from the Zero Reference of the sensor to the point from which
the first signal will be valid. Signals from a float in the blanking area will be ignored.