NOTE
: Your MNU IS must be calibrated (see Calibration in Chapter 5) before initiating
QuickMode.
To successfully use QuickMode:
•
Ensure that your Modbus Master is set up to listen for and receive the response packet after
initiating QuickMode.
•
Ensure that your MNU IS settings are optimized for the installation (Sensitivity, Pulses, Pulse Power,
etc).
•
Ensure that your MNU IS is calibrated for the distance.
•
Set the desired time delay in QuickMode Delay (40422).
•
When all other settings are properly configured, set the number of QuickMode samples to be
averaged (40421).
The following general sensor settings must be configured for optimal sensor operation prior to initiating
QuickMode for accurate QuickMode readings:
•
Max Distance (Holding Register 40405)
•
Pulses (Holding Register 40409), Sensitivity (Holding Register 40408), and Pulse Power (Holding
Register 40423)
To initiate QuickMode:
•
Write the number of desired QuickMode samples to Holding Register 40421.
To exit QuickMode (return to normal sensor operation):
•
Write 0 to Holding Register 40421.
•
Using QuickMode