11
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Holding Registers (0x03) - MNU IS
Register
Function
Value Range
40400 Device
Address
1
to
247
40401
Units
1 = Feet, 2 = Inches, 3 = Meters
40402
Application Type
0 - 11
40403
Volume Units
1 - 7
40404 Decimal
(Calculated)
0
-
3
40405 Max
Distance
0
-
15,250
mm
40406
Full Distance
0 - 15,250 mm
40407
Empty Distance
0 - 15,250 mm
40408 Sensitivity
0
-
100
40409 Pulses
0
-
20
40410 Blanking 0
-
15,250
mm
40411 Gain
Control
0
-
5
40412 Averaging
1
-
100
40413 Filter
Window
0
-
15,250
mm
40414 Out
of
Range
1
-
255
40415 Sample
Rate
50
-
1000
milliseconds
40416
Multiplier
1 - 1999 (1,000 = 1.000)
40417
Offset
-15,250 - 15,250 mm
40418 N/A
40419 N/A
40420
Temperature Compensation
0 = No, 1 = Yes
40421 QuickMode
Enable
0
-
98
40422
QuickMode Delay
0 - 65535 ms
40423
Pulse
Power
10
-
100%
40424-40425
N/A
40426 4
mA
Set
Point
*N/A
40427
20
mA
Set
Point *N/A
40428 4
mA
Calibration *N/A
40429
20
mA
Calibration
*N/A
40430
Trip 1 Value
0 - 15,250 (mm)
40431
Trip 1 Window
0 - 15,250 (mm)
40432 Trip
1
Type
0
-
29
40433
Trip 2 Value
0 - 15,250 (mm)
40434
Trip 2 Window
0 - 15,250 (mm)
40435 Trip
2
Type
0
-
29
40436-40437
Parameter 1
0 - 1,000,000 (mm)
40438-40439
Parameter 2
0 - 1,000,000 (mm)
40440-40441
Parameter 3
0 - 1,000,000 (mm)
40442-40443
Parameter 4
0 - 1,000,000 (mm)
40444-40445
Parameter 5
0 - 1,000,000 (mm)
40187 QuickMode
Resample
Non-Zero
Number
40201
Reset to Factory Defaults
1
*These registers are not used by the MNU IS, even though they are labeled in the APG Modbus software.