DCR-1006A Level Controller
17
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
CUSTOM
(Custom Units):
Allows the user to define a custom alphanumeric label for the Curve Fit and
Linear Calculation Application Types.
VOLUNI
(Volume Units):
Determines the unit of measure for the volumetric Application Types. Options:
Cubic Feet, Million Cubic Feet, Gallons, Cubic Meters, Liters, Cubic Inches, Bar-
rels.
IN SEL
(Input Select):
Selects the sensor input used by the controller.
DST: Standard DST sensor
LR DST: Long Range DST (DST-3434)
RS485: (MNU or MPX sensors only)
NOTE: when connecting a new RS-485 sensor to the DCR-1006A, set the Input
Select to DST (with the new RS-485 sensor connected), then switch the Input
Select to RS485. This will initiate the DCR-1006A to upload and configure the
parameter settings in the RS-485 sensor for proper operation with the DCR-
1006A.
dECIML
(Decimal Place):
Sets the decimal place position in the Calculated Reading.
Example: a reading of 26.573 (gallons, etc.) will be displayed as follows:
Decimal Place = 0
Volume = 27
Decimal Place = 1
Volume = 26.6
Decimal Place = 2
Volume = 26.57
Decimal Place = 3
Volume = 26.573
NOTE: the decimal place in all dimensional parameters is fixed based on the
unit of measure selected (see Units on previous page)
SENS N
(Sensor Number)
:
Sets the Modbus address number for the DCR-1006A when its interfacing with
an RST-5003 module or the APG Modbus software.