Operation Mode Setting
:
Switch 1 On: Stand-alone
4
2
3
1
J13
The non alarm state of each individual channel can be configured to allow the
channel to operate from either a NO or NC contact.
AIS750 supports all
ISA-S18.1/1979 (R1985)
sequences. These sequences are Field
Selectable for each Alarm Controller (Logic Card). For example for H11 type, each individual
channel and for H21 type, each two channels will be confi gured at the same time.
Flowcharts of all sequences are available at the end of this document.
Switch 1 Off: Serial Mode
Manual Reset (M)
Auto Reset (A)
No Lock (N)
Ring Back (R)
First Out-1A (F1A)
First Out-2M (F2M)
First Out-3A (F3A)
Off
Off
Off
Off
On
On
On
Off
Off
On
On
Off
Off
On
Off
On
Off
On
Off
On
Off
Input 1 Input 2 Input 3 Input 4
switch 5
switch 6 switch 7 switch
8
Switch On: Normally Open Input
Switch Off: Normally Close Input
Sequence
switch 2 switch 3 switch
4
ON
1
23
4
5
6
7
8
Stand-alone Mode DIP Switch setting:
Logic Card Settings in Stand-alone Mode:
Visit the bellow links for Manual Reset & Auto Reset demonstrations
http://www.youtube.com/watch?v=XgYib4a5PoE
http://www.youtube.com/watch?v=j7n6RerSviQ
AIS750 Series Annunciators