Alarm Sequences
Ring Back (Sequence Code R)
Auto Reset First Out (Sequence Code F1A)
With No Subsequent Alarm State
Acknowledge
while Abnormal
(First-out Reset)
Acknowledge
while Normal
(First-out Reset)
First to
Abnormal
Return to
Normal
Subsequent
to Abnormal
P: Normal
S: Normal
V: Off
A: Silent
A
w
(F
P: Abnormal or Normal
S: Acknowledged
V: On
A: Silent
P: Abnormal or Normal
S: Alarm
V: Flashing
A: Audible
Acknowledge
while
Abnormal
return
to normal
Reset
Acknowledge
while Normal
Return
to Normal
To
Abnormal
Return
to Abnormal
return
to normal
P: Normal
S: Ringback
V: Slow Flashing
AA: Silent
RA: Audible
P: Abnormal or Normal
S: Alarm
V: Fast Flashing
AA: Audible
RA: Silent
P: Abnormal
S: Acknowledged
V: On
AA: Silent
RA: Silent
To
A
P: Normal
S: Normal
V: Off
AA: Silent
RA: Silent
Legends:
P: Process S: Sequence V: Visual A: Audible AA: Alarm Audible RA: Ringback Audible
AIS750
03
04
H21
V1
1
N
1
0
Serial Comm.
1: With
0: Without
Push Button & Buzzer Module
1: With
0: Without
Number of Windows
in a Column (wide)
Number of Windows
in a Row (high)
Window
type
Signal Voltage
V0: Dry Contact
V1: 24VDC/AC
V2: 48VDC/AC
V3: 125VDC/AC
V4: 250VDC/AC
V5: Others (Specify)
Model #
Auxiliary Relay
1: With
0: Without
Order Number
Visit the bellow links for Manual Reset & Auto Reset demonstration.
http://www.youtube.com/watch?v=XgYib4a5PoE
http://www.youtube.com/watch?v=j7n6RerSviQ
AIS750 Series Annunciators
(30)
Integral Push Button & Buzzer Module (option)
Standard AIS750 Series Annunciator supports four remote
Pushbuttons (Acknowledge, Reset, Test, Mute) and two Horns. As an option, an
integral “Pushbutton & Buzzer Module” can be fi tted in the bottom right window.