OPERATION MODE

- Stand-alone (standard) Mode
- Serial Mode with serial communication 

SYSTEM SETUP

- In Stand-alone Mode: By DIP switches
- In Serial Mode: Through ALCON 
  software

SERIAL COMMUNICATION

Protocol:

 

AIS750 supports Modbus RTU-Slave, 
DNP3 Serial, DNP3 Ethernet and many 
other protocols including; Modbus TCP, 
BACnet MS/TP, BACnet IP, AB EtherNet IP, 
Allen Bradley EtherNet, AB DF1, SNMP, 
GE-EGD, GE-SRTP, GE-SNP, OPC, 
Omron Fins, Metasys N2 Open,...

Multi-drop RS485 communication is    
available. Up to 7 Annunciators can be 
connected together and also to another 
device. 

 INPUTS

Isolation and Polarity:

- Each input is optically isolated up to  
  2000VAC
- All inputs are bipolar and can accept
  AC or DC voltages

Alarm Inputs:

- Wet (voltage supplied) or dry (voltage free)  
  contacts. Field Selectable for each channel 
  individually
- Normally Open (NO) or Normally Closed  
  (NC). Field Selectable for each channel 
  individually
 - Dry Contact and 24V (DC or AC) are  
  standard inputs and other voltages are 
  optional as bellow
- Other input Voltages; 48V,125V and 
  250V (DC or AC)

Response Time:

- Standard unit: 25ms milliseconds
- Made to order from 1ms to 2s 

 OUTPUTS

Supported outputs:

- Light Output
- Critical Audible Relay 
- Non-critical Audible Relay
- Critical/Non-critical Buzzer
- Group Relay
- Common Relay
- Auxiliary (Repeat) Relay (can be set to 
  follow Input or Output)
- Common Alarm Relay
- First_Up Relay

Relay Rating:

 - 1A@24VDC

                         - 0.5A@ 120VAC

ALARM SEQUENCES

System supports all 

ISA-S18.1/1979

(R1985)

 sequences including: 

- Manual Reset (M)
- Automatic Reset (A)
- Automatic Reset First Out (F3A)
- Automatic Reset First Out (F1A)
- Manual Reset First Out (F2M-1)
- Ringback (R)
- No Lock In

These sequences are Field Selectable 
for each Alarm Controller (for example for 
H21 window type, two channels have the 
same sequence)

 DISPLAY

Confi guration:

- One single large window:
  (H11 type): 75x50mm (WxH)
- Two medium window: 
  (H21 type): 75x25mm (WxH)
  (H12 type): 37.5x50mm (WxH)
  (V21 type): 50x37.5mm (WxH)
- Four small window: 
  (H44 type): 37.5x25mm (WxH)

Each window is backlit by almost unlimited 
life time  “plug-in” LED Modules with 120° 
high bright LEDs 

Number of LED(s) per LED module: 2
Number of LED module per Alarm Point:      

        H11: 4 LED modules
        H21, H12, V21: 2 LED modules
        H44: 1 LED module

LED Module Color: 

Yellow, Red, Green, White

Legends: 

- Laser Engraved & color fi lled

                

  

 -  Printed translucent fi lm

Environment:

Operating temperature : -20 to 60ºC
Storage temperature -20 to 80°C
Humidity 0-95% RH, non condensing

Protection:

Front Panel: IP41
Enclosure: IP20

Weight:

Approximately 0.35 kg per H11 window

Supply Voltage:

24VDC Nominal (20-30VDC)

Supply Current Per Alarm Point:

Quiescent: 5mA (

at 24VDC)

LEDs:  H11: 24mA (

at 24VDC)

            H21, H12, V21:  12mA (

at 24VDC)

            H44: 6mA (

at 24VDC)

Relay: 10mA per relay (

at 24VDC)

Additional 100mA current is required 
for Interface Module, Pushbutton/
Buzzer Module, Common Relay and 
Buzzer and Serial Communication 
Module

GENERAL

Technical Specifi cation

Connection Terminals:

- Two-part removable screw type
- Maximum wire size: 2.5 mm

2

Mounting:

Panel (fl ush) Mount

 PUSHBUTTONS

“Acknowledge”, Reset”, “Test” and “Mute” 
pushbuttons are supported by the system 
with two choices; Remote and/or Integral 
pushbuttons

AIS750 Series Annunciators

(3)

Visit 

www.annunciator.ca

for updated specifi cation

Содержание AIS750 Series

Страница 1: ...ciator User Manual Ver 2 3 JUNE 2014 3 350 John Street Thornhill Ontario L3T 5W6 Phone 289 597 APEX 2739 Fax 289 597 2200 Toll Free 1 866 776 2943 Email mail annunciator ca Web www ANNUNCIATOR ca AIS7...

Страница 2: ...cation feature is disabled and system works as a stand alone unit No unique address needed for cards in this mode and generally Stand alone mode is recommended if no serial communication needed with o...

Страница 3: ...omatic Reset A Automatic Reset First Out F3A Automatic Reset First Out F1A Manual Reset First Out F2M 1 Ringback R No Lock In These sequences are Field Selectable for each Alarm Controller for example...

Страница 4: ...ules and Connectors AIS750 is an unparallel modular dual operation mode Annunciator The annunciator is made up of windows window being 75 x 50mm 3 x 2 The type of cards installed dependent on system s...

Страница 5: ...ow address 3 Window address n Window address n 2 Window address n 3 Window address n 4 Window address m Window address n 1 Window address m 2 Window address m 3 Window address m 4 Window address x Win...

Страница 6: ...modes Stand alone Standard and Serial The DIP switch on Logic Card has different settings in each mode Each 4 channel Logic Card can be supplied with an optional 4 channel Relay Module RM which plugs...

Страница 7: ...l be configured at the same time Flowcharts of all sequences are available at the end of this document Switch 1 Off Serial Mode Manual Reset M Auto Reset A No Lock N Ring Back R First Out 1A F1A First...

Страница 8: ...ic Card can be supplied with an optional 4 channel Relay Module RM which plugs into Logic Card and provides the user with a dry contact volt free contact per alarm channel to be used by 3rd party devi...

Страница 9: ...5 6 7 8 9 10 110 Logic Cards Addressing Examples ON 1 2 3 4 5 6 7 8 In Serial operation mode each Logic Card in the system has its own unique address This unique address is set using the switches 2 8...

Страница 10: ...shown bellow These Repeat relays can be configured by Logic Card jumper setting in Stand alone mode or in software in Serial mode to operate in accordance with one of the following Input Follower The...

Страница 11: ...ledge pushbutton has been pressed Horn 1 Horn2 First up Activates when the first alarm occurs within a group Common Alarm Group Alarms Once channels have been assigned to groups Critical Non critical...

Страница 12: ...s Stand alone standard and Serial mode Stand alone mode is recommended if no serial communication needed with other devices The operation mode of Interface Module should be set as bellow table Interfa...

Страница 13: ...There are two relays on Interface module Function of relays can be set by jumpers as showing bellow allowing the relays to operate as Audible Alarm Horn Activates on alarm and remain active within a...

Страница 14: ...h 4 1 2 3 4 5 6 7 ON Operation Mode switch 1 Interface Module Setting in Serial Mode For operation in Serial mode Interface module DIP switch must be set switch1 Off For Multi Drop connection connecti...

Страница 15: ...cation Module Com Module optional Com 1 APEX Automation Solutions Com Module 1 2 3 1 2 3 1 2 3 1 2 3 Com 2 Com 1 APEX Automation Solutions Com Module 1 2 3 1 2 3 1 2 3 1 2 3 Com 2 Termination Jumper M...

Страница 16: ...recommended as shown above Depend on system options every 7 10 Logic Cards usually each row needs one 24VDC power connection One power connection for Interface module is mandatory On standard systems...

Страница 17: ...Using this terminal for common wire for inputs is permitted ONLY when using the same power source which is supplying the system Input 1 Input 2 1 2 1 2 1 2 1 2 power supply 0 0 Input 3 Input 4 0 0 Ala...

Страница 18: ...alarm and remain active within a group until the Mute or Acknowledge pushbutton has been pressed Horn 1 Horn2 First up Activates when the first alarm occurs Common Alarm Group Alarm Once channels hav...

Страница 19: ...e Reset Mute Test Momentary Normally Open Pushbutton External remote pushbutton wiring diagram As an alternative Pushbutton Module can be supplied as a remote item or the user can use conventional pan...

Страница 20: ...nel Repeat Relays Each 4 channel Logic Card can be supplied with an optional 4 channel Relay Module RM to provide dry contact potential free contacts per alarm channel to be used with 3rd party device...

Страница 21: ...ector Pin Configuration Slave Annunciator RS232 DB9 Female Connections 21 Slave Annunciator RS485 DB9 Female Connections PIN 1 2 3 4 5 6 7 8 9 RS232 DCD RXD TXD DTR GND DSR RTS CTS RS485 D GND D Seria...

Страница 22: ...to 7 annunciators to another device each Interface Module in the system each Annunciator requires a unique address node address starting with 1 for the first Annunciator address 2 for second Annuncia...

Страница 23: ...E SRTP GE SNP OPC Omron Fins Metasys N2 Open AIS750 Series Annunciators 23 24VDC 0V RS485 GND RS485 Data RS485 Data To Master DNP3 Serial Communication Gateway SCG Serial communication wiring to Maste...

Страница 24: ...First Up Com Alarm Crtcl Horn Alarm Horn 40002 Interface module data Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 40003 Logic card data Alrm4 Alrm3 Alrm2 Alrm1 In 4 In 3 In 2 In 1 Ack4 Ack3 Ack2 Ack1 L...

Страница 25: ...ble a white or coloured lens and a plastic bezel on top of them There are two options for alarm labeling Engraving and using Translucent film Bellow diagram shows the arrangement of clear lens coloure...

Страница 26: ...ly lever the lens forward To replace a window lens follow the following simple steps 1 Insert the screwdriver inside the slot between the windows and pop it up gently 2 Remove the plastic bezel 3 Ther...

Страница 27: ...e new lens inside the frame 7 Put the screwdriver inside the slot and push the lens in 8 Secure the lens 9 Put the plastic bezel back in place 10 Push the corners of plastic bezel AIS750 Series Annunc...

Страница 28: ...11 large window has 4 LED modules so each H21 has 2 and each H44 has 1 LED module No special tools needed to replace the LED modules To remove and install LED modules just a general purpose pointed pl...

Страница 29: ...Off A Silent P Abnormal or Normal S Subsequent Alarm V On A Audible P Abnormal or Normal S First Silenced V Flashing A Silent P Abnormal or Normal S First Alarm V Flashing A Audible P Abnormal or Nor...

Страница 30: ...t RA Silent To A P Normal S Normal V Off AA Silent RA Silent Legends P Process S Sequence V Visual A Audible AA Alarm Audible RA Ringback Audible AIS750 03 04 H21 V1 1 N 1 0 Serial Comm 1 With 0 Witho...

Отзывы: