background image

June 2013 

12 

80-0180-347 Rev. A 

RIM Exit Device Application:    A100-3090H for 8700/8800 

 

 

On  the  back  side  of  the  exit  device,  re-
move only the lower Phillips head screw, 
depending on hand of door, to free up the 
cylinder actuator for use.  (F

IG

. 10) 

 

 

 
 

 

 

 
 

 

MS 1850 Application:  A100-3090H for 
MS

® 

Series Deadbolt

 

 

 

Two (2) brass hex head screws and the 

set  screw  from  the  MS1850  will  fasten 
the cam plug to the MS1850. (F

IG

. 11) 

 

 

For MS

®

 Deadbolt, insert Cam Plug (F

IG

12) into lock case with notch on the cam 
plug aligned with lock case setscrew.  

 

 

Tighten  setscrew  and  secure  with  the 

two  (2)  brass  cam  plug  screws.  Cam 
Plug must be positioned below door sur-
face.  

 

 
 
 
 
 
 
 
 

 
 

 
 
 
 

C

YLINDER

 A

CTUATOR

 

SCREW

 

F

IG

. 11 

F

IG

. 10 

F

IG

. 12 

June 2013 

80-0180-347 Rev. A 

STEP 1     DOOR PREPARATION 

 
F

IG

. 2 

 

Select the stick-on template to match the appli-
cation. 

 

For  Yale,  Corbin  Russwin  and  SARGENT  exit     
devices, use template 80-0180-396-01. 

 

Mark the backset and horizontal centerlines. 

 

Apply

 

clear

 

template over the centerline marks  

(F

IG

. 2). 

 

Center-punch  four  (4)  referenced  mounting 
holes and remove template. 

 

Drill holes at center-punch locations using a ¼” 
drill bit. 

 

Install Rivnuts.  Refer to instructions supplied in  
Rivnut kit. 

 

Install  mounting  bracket  (Item  1)  with  two  (2) 
each  of  #10-32  x  5/8”  (Item  2)  Phillips  pan 
head screws. (F

IG

. 3) 

 

         
 
 

 

F

IG

. 3

 

 

Содержание eForce A100 A100-3090H

Страница 1: ... S 51st St Suite 102 Phoenix AZ 85044 Phone 800 872 3267 Fax 800 232 7329 www adamsrite com NORMAL OPERATION LOCK INDICATIONS Aperio eForce A100 Narrow Stile Keyless Entry Adams Rite Manufacturing Co Phone 800 872 3267 www adamsrite com Owner s Manual Installation Instructions For Models A100 3090H ...

Страница 2: ...n credential card in front of eForce If the eForce emits one short tone but lock does not activate check Wiegand data lines for connectivity and proper connec tion Green light comes on but lever will not retract latch or deadbolt Check the eForce body connection with lock latch mechanism Check the spindle length see installation instructions Check for proper door preparation refer to door template...

Страница 3: ...evice pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference w...

Страница 4: ... Exit Devices Corbin Russwin ED4000 Series and SARGENT 8500 Narrow Design Rim Exit Devices OPERATIONAL SPECIFICATIONS IEEE 802 15 4 UHF Interface operating at 2 4GHz iCLASS or PROX Reader technology AES 128 bit encryption 4 AA battery operated Operating Temperature Range 31 to 150 F 35 to 65 C Operating Humidity Range 5 to 95 relative humidity non condensing June 2013 17 80 0180 347 Rev A STEP 8 B...

Страница 5: ...are valid The LED will change states from off to green and a short audible tone will be heard to indicate a valid unlock status Rotate the lever to gain entry into the building Deadlatch versions will return to a secured locked state after the access control system unlock pe riod has expired Deadbolt versions will remain unlocked until the deadbolt is thrown again NOTE the access control system wi...

Страница 6: ...the Hub The included hub mounting adapter plate can be used to mount the hub on a single or double gang box A B C June 2013 15 80 0180 347 Rev A STEP 6 REX DPS CABLE INSTALLATION PIN WIRE COLOR FUNCTION CONTACT 1 Yellow D P S Door Position Switch N C 2 Blue COM 3 Brown N O 4 Orange N C REX Request to Exit 5 White COM 6 Green N O Using a Phillips Head screwdriver remove the eight 8 10 32 x 5 8 scre...

Страница 7: ...are wires connect ing the housing and back plate assembly Handle with care Do not over tighten Do not use Dummy Cylinder June 2013 7 80 0180 347 Rev A HUB WIRING The Aperio hub connects to the Access Control system via Wiegand wiring The hub requires 8 24VDC power 250mA The hub has four form C relays that can be used to transmit door position status re quest to exit low battery signal and a tamper...

Страница 8: ...tem Description Qty 1 Mounting Bracket Part 22 9076 1 2 10 32 X 5 8 Phillips Pan Head Screws w Lockwasher 4 3 Spindle Part 22 9154 1 4 5 64 Allen Key 1 5 Cylinder Locking Ring Part 24 0061 1 6 Locking Ring Spanner Tool Part 22 0594 1 FIG 1 June 2013 13 80 0180 347 Rev A STEP 4 HANDING THE eForce The eForce is shipped in a non handed neutral position with the access cover off as shown To hand the e...

Страница 9: ...screw and secure with the two 2 brass cam plug screws Cam Plug must be positioned below door sur face CYLINDER ACTUATOR SCREW FIG 11 FIG 10 FIG 12 June 2013 9 80 0180 347 Rev A STEP 1 DOOR PREPARATION FIG 2 Select the stick on template to match the appli cation For Yale Corbin Russwin and SARGENT exit devices use template 80 0180 396 01 Mark the backset and horizontal centerlines Apply clear templ...

Страница 10: ... FIG 6 For 2 thick doors add two notches FIG 6 Insert T end into exit devices Fourteenth notch FIG 5 Sixth notch Insert Flat end into exit devices FIG 4 Fifth notch Insert Flat end into exit devices June 2013 11 80 0180 347 Rev A STEP 3 CONFIGURE FOR LOCK SERIES Mortise Latch Application A100 3090H for 4500 4900 including 8300 8400 Exit Devices Configure the supplied cam plug to match the hand of ...

Отзывы: